Buildings.Controls.Continuous.Examples

Collection of models that illustrate model use and test models

Information

This package contains examples for the use of models that can be found in Buildings.Controls.Continuous.

Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).

Package Content

NameDescription
Buildings.Controls.Continuous.Examples.LimPID LimPID Test model for PID controller with optional reverse action
Buildings.Controls.Continuous.Examples.PIDHysteresis PIDHysteresis Example model for PID controller with hysteresis
Buildings.Controls.Continuous.Examples.PIDHysteresisTimer PIDHysteresisTimer Example model for PID controller with hysteresis and timer
Buildings.Controls.Continuous.Examples.SignalRanker SignalRanker Example model for signal ranker
Buildings.Controls.Continuous.Examples.NumberOfRequests NumberOfRequests Example model for block that outputs the number of requests
Buildings.Controls.Continuous.Examples.OffTimer OffTimer Example model for off timer


Buildings.Controls.Continuous.Examples.LimPID Buildings.Controls.Continuous.Examples.LimPID

Test model for PID controller with optional reverse action

Buildings.Controls.Continuous.Examples.LimPID

Information

This model tests the implementation of the PID controller with optional reverse action. The model limPIDOri is the original implementation of the controller from the Modelica Standard Library. The models limPID and limPIDRev are the implementations from the Buildings library. The model limPIDRev is parameterized to have reverse action. The assertion blocks test whether the results of all three controllers are identical.

Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model LimPID 
  "Test model for PID controller with optional reverse action"
  extends Modelica.Icons.Example;
  import Buildings;

  Modelica.Blocks.Sources.Pulse pulse(period=0.25);
  Buildings.Controls.Continuous.LimPID limPID(
    controllerType=Modelica.Blocks.Types.SimpleController.PID,
    Ti=1,
    Td=1,
    yMax=1,
    yMin=-1,
    initType=Modelica.Blocks.Types.InitPID.InitialState);
  Buildings.Controls.Continuous.LimPID limPIDRev(
    controllerType=Modelica.Blocks.Types.SimpleController.PID,
    reverseAction=true,
    Ti=1,
    Td=1,
    yMax=1,
    yMin=-1,
    initType=Modelica.Blocks.Types.InitPID.InitialState) 
    "Controller with reverse action";
  Modelica.Blocks.Sources.Constant const(k=0.5);
  Modelica.Blocks.Math.Gain gain(k=-1);
  Buildings.Utilities.Diagnostics.AssertEquality assertEquality(threShold=1e-10);
  Modelica.Blocks.Continuous.LimPID limPIDOri(
    controllerType=Modelica.Blocks.Types.SimpleController.PID,
    Ti=1,
    Td=1,
    yMax=1,
    yMin=-1,
    initType=Modelica.Blocks.Types.InitPID.InitialState);
  Buildings.Utilities.Diagnostics.AssertEquality assertEquality1(
                                                                threShold=1e-10);
equation 
  connect(pulse.y, limPID.u_s);
  connect(pulse.y, limPIDRev.u_s);
  connect(const.y, limPID.u_m);
  connect(const.y, limPIDRev.u_m);
  connect(limPIDRev.y, gain.u);
  connect(gain.y, assertEquality.u2);
  connect(limPID.y, assertEquality.u1);
  connect(pulse.y, limPIDOri.u_s);
  connect(const.y, limPIDOri.u_m);
  connect(assertEquality1.u1, limPIDOri.y);
  connect(assertEquality1.u2, limPID.y);
end LimPID;

Buildings.Controls.Continuous.Examples.PIDHysteresis Buildings.Controls.Continuous.Examples.PIDHysteresis

Example model for PID controller with hysteresis

Buildings.Controls.Continuous.Examples.PIDHysteresis

Information

Example that demonstrates the use of the PID controller with hysteresis. The control objective is to keep the temperature of the energy storage cap at 40°C. The controller con is parameterized to switch on if the control error is bigger than eon=1. The output of the controller remains above ymin=0.3 until the control error is smaller than eoff=-1, at which time the controller outputs y=0 until the control error is again bigger than 1. The figure below shows the control error con.feeBac.y and the control signal con.y.

Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model PIDHysteresis 
  "Example model for PID controller with hysteresis"
  extends Modelica.Icons.Example;
  import Buildings;

  Buildings.Controls.Continuous.PIDHysteresis con(
    pre_y_start=false,
    controllerType=Modelica.Blocks.Types.SimpleController.PI,
    yMin=0.3,
    Ti=600,
    Td=60);
  Modelica.Blocks.Sources.Constant TSet(k=273.15 + 40, y(unit="K")) "Set point";
  Modelica.Thermal.HeatTransfer.Components.HeatCapacitor cap(C=1000000, T(start=
         313.15, fixed=true));
  Buildings.HeatTransfer.Sources.PrescribedTemperature TBC;
  Modelica.Thermal.HeatTransfer.Components.ThermalConductor theCon(G=20);
  Modelica.Blocks.Math.Gain gain(k=2000);
  Modelica.Thermal.HeatTransfer.Sensors.TemperatureSensor temSen;
  Buildings.HeatTransfer.Sources.PrescribedHeatFlow Q_flow;
  Modelica.Blocks.Sources.Sine sine(
    freqHz=1/86400,
    offset=273.15,
    amplitude=20,
    phase=-1.5707963267949,
    y(unit="K"));
equation 

  connect(TSet.y, con.u_s);
  connect(TBC.port, theCon.port_a);
  connect(theCon.port_b, cap.port);
  connect(con.y, gain.u);
  connect(cap.port, temSen.port);
  connect(temSen.T, con.u_m);
  connect(gain.y, Q_flow.Q_flow);
  connect(Q_flow.port, cap.port);
  connect(sine.y, TBC.T);
end PIDHysteresis;

Buildings.Controls.Continuous.Examples.PIDHysteresisTimer Buildings.Controls.Continuous.Examples.PIDHysteresisTimer

Example model for PID controller with hysteresis and timer

Buildings.Controls.Continuous.Examples.PIDHysteresisTimer

Information

Example that demonstrates the use of the PID controller with hysteresis and off timer. The example is identical to Buildings.Controls.Continuous.Examples.PIDHysteresis, except that the controller also has an off timer. This timer keeps the control signal at y=0 for a period of minOffTime=1000 seconds. This may be used to avoid short-cycling if the load is small and the system has little heat capacity.

The figure below shows the control error con.feeBac.y and the control signal con.y.


Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model PIDHysteresisTimer 
  "Example model for PID controller with hysteresis and timer"
  extends Modelica.Icons.Example;
  import Buildings;

  Buildings.Controls.Continuous.PIDHysteresisTimer con(
    yMin=0.3,
    minOffTime=10000,
    controllerType=Modelica.Blocks.Types.SimpleController.PI,
    Ti=60,
    Td=10);
  Modelica.Blocks.Sources.Constant TSet(k=273.15 + 40, y(unit="K")) "Set point";
  Modelica.Thermal.HeatTransfer.Components.HeatCapacitor cap(C=100000, T(start=
          293.15, fixed=true));
  Buildings.HeatTransfer.Sources.PrescribedTemperature TBC;
  Modelica.Thermal.HeatTransfer.Components.ThermalConductor theCon(G=10);
  Modelica.Blocks.Math.Gain gain(k=800);
  Modelica.Thermal.HeatTransfer.Sensors.TemperatureSensor temSen;
  Buildings.HeatTransfer.Sources.PrescribedHeatFlow Q_flow;
  Modelica.Blocks.Sources.Sine sine(
    freqHz=1/86400,
    offset=273.15,
    amplitude=20,
    phase=-1.5707963267949);
equation 

  connect(TSet.y, con.u_s);
  connect(TBC.port, theCon.port_a);
  connect(theCon.port_b, cap.port);
  connect(con.y, gain.u);
  connect(cap.port, temSen.port);
  connect(temSen.T, con.u_m);
  connect(gain.y, Q_flow.Q_flow);
  connect(Q_flow.port, cap.port);
  connect(sine.y, TBC.T);
end PIDHysteresisTimer;

Buildings.Controls.Continuous.Examples.SignalRanker Buildings.Controls.Continuous.Examples.SignalRanker

Example model for signal ranker

Buildings.Controls.Continuous.Examples.SignalRanker

Information

Example that demonstrates the use of the signal ranker model. The figure below shows the input and output signals of the block. Note that sigRan.y[1] ≥ sigRan.y[2] ≥ sigRan.y[3].


Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model SignalRanker "Example model for signal ranker"
  extends Modelica.Icons.Example;
  Modelica.Blocks.Sources.Sine sine(freqHz=2);
  Modelica.Blocks.Sources.Pulse pulse(period=0.25);
  Buildings.Controls.Continuous.SignalRanker sigRan(
                                                  nin=3);
  Modelica.Blocks.Sources.ExpSine expSine(freqHz=10);
equation 
  connect(sine.y, sigRan.u[1]);
  connect(pulse.y, sigRan.u[2]);
  connect(expSine.y, sigRan.u[3]);
end SignalRanker;

Buildings.Controls.Continuous.Examples.NumberOfRequests Buildings.Controls.Continuous.Examples.NumberOfRequests

Example model for block that outputs the number of requests

Buildings.Controls.Continuous.Examples.NumberOfRequests

Information

Example that demonstrates the use of the block Buildings.Controls.Continuous.NumberOfRequests. The parameters of the block are such that the output is incremented for each input signal that is strictly larger than 0. The figure below shows the inputs and the output of the block.

Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model NumberOfRequests 
  "Example model for block that outputs the number of requests"
  extends Modelica.Icons.Example;
  Buildings.Controls.Continuous.NumberOfRequests numReq(
    nin=2,
    threShold=0,
    kind=0);
  Modelica.Blocks.Sources.Sine sine(freqHz=2);
  Modelica.Blocks.Sources.Pulse pulse(period=0.25);
equation 
  connect(sine.y, numReq.u[1]);
  connect(pulse.y, numReq.u[2]);
end NumberOfRequests;

Buildings.Controls.Continuous.Examples.OffTimer Buildings.Controls.Continuous.Examples.OffTimer

Example model for off timer

Buildings.Controls.Continuous.Examples.OffTimer

Information

Example that demonstrates the use of the model Buildings.Controls.Continuous.OffTimer. The input to the two timers are alternating boolean values. Whenever the input becomes false(=0), the timer is reset. The figures below show the input and output of the blocks.


Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model OffTimer "Example model for off timer"
  extends Modelica.Icons.Example;
  import Buildings;

  Modelica.Blocks.Sources.BooleanPulse booleanPulse(period=0.2);
  Buildings.Controls.Continuous.OffTimer offTim1;
  Buildings.Controls.Continuous.OffTimer offTim2;
  Modelica.Blocks.Logical.Not not1;
equation 
  connect(booleanPulse.y, offTim1.u);
  connect(booleanPulse.y, not1.u);
  connect(offTim2.u, not1.y);
end OffTimer;