Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Examples
Example models for rear door heat exchangers
Information
Package with example models for rear door heat exchangers.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
Package Content
| Name | Description |
|---|---|
| Example model for an active rear door heat exchanger | |
| Example model for a passive rear door heat exchanger | |
| Base classes for rear door heat exchanger example models |
Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Examples.Active
Example model for an active rear door heat exchanger
Information
Example model for an active rear door heat exchanger.
The model uses a constant water mass flow rate. The air mass flow rate is determined by the fan control. Because the IT load and the water mass flow rate are constant, the air mass flow rate is also constant after the initial transient.
Extends from Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Examples.BaseClasses.PartialExample (Partial example model for a rear door heat exchanger).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| HeatFlowRate | Q_flow_nominal | -10000 | Nominal cooling duty (negative = heat removed from air) [W] |
| Temperature | TAirIn_nominal | 273.15 + 40 | Nominal air inlet temperature (warm server exhaust) [K] |
| Temperature | TAirOut_nominal | 273.15 + 30 | Nominal air outlet temperature of rear door heat exchanger [K] |
| Temperature | TCooIn_nominal | 273.15 + 20 | Nominal coolant inlet temperature [K] |
| Temperature | TCooOut_nominal | 273.15 + 30 | Nominal coolant outlet temperature [K] |
| MassFlowRate | mAir_flow_nominal | Q_flow_nominal/(TAirOut_nomi... | Nominal air mass flow rate [kg/s] |
| MassFlowRate | mCoo_flow_nominal | -Q_flow_nominal/(TCooOut_nom... | Nominal coolant mass flow rate [kg/s] |
| Power | PIT_nominal | 10000 | Nominal IT load power handled by rear door heat exchanger [W] |
| Generic | dat | dat(mAir_flow_nominal=mAir_f... | Performance data |
Modelica definition
Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Examples.Passive
Example model for a passive rear door heat exchanger
Information
Example model for a passive rear door heat exchanger.
The model uses a constant air and water mass flow rate.
Extends from Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Examples.BaseClasses.PartialExample (Partial example model for a rear door heat exchanger).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| HeatFlowRate | Q_flow_nominal | -10000 | Nominal cooling duty (negative = heat removed from air) [W] |
| Temperature | TAirIn_nominal | 273.15 + 40 | Nominal air inlet temperature (warm server exhaust) [K] |
| Temperature | TAirOut_nominal | 273.15 + 30 | Nominal air outlet temperature of rear door heat exchanger [K] |
| Temperature | TCooIn_nominal | 273.15 + 20 | Nominal coolant inlet temperature [K] |
| Temperature | TCooOut_nominal | 273.15 + 30 | Nominal coolant outlet temperature [K] |
| MassFlowRate | mAir_flow_nominal | Q_flow_nominal/(TAirOut_nomi... | Nominal air mass flow rate [kg/s] |
| MassFlowRate | mCoo_flow_nominal | -Q_flow_nominal/(TCooOut_nom... | Nominal coolant mass flow rate [kg/s] |