Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers
Package with models for rear door heat exchangers
Information
Package with standalone models for rear door heat exchangers used in IT racks. A rear door heat exchanger is mounted at the back of the rack and removes heat from the warm server exhaust air using a liquid coolant loop.
Two variants are provided:
- Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Passive: the air is driven through the heat exchanger by the server fans inside the rack. No additional fan is required.
- Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Active: an integrated fan drives the air through the heat exchanger, allowing independent control of the air flow rate. A PI controller regulates the fan speed to maintain a target air outlet temperature.
Extends from Modelica.Icons.Package (Icon for standard packages).
Package Content
| Name | Description |
|---|---|
| Active rear door heat exchanger with integrated temperature controlled fan | |
| Passive rear door heat exchanger — air driven by fans in server | |
| Data records for rear door heat exchangers | |
| Example models for rear door heat exchangers | |
| Base classes for rear door heat exchanger models |
Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Active
Active rear door heat exchanger with integrated temperature controlled fan
Information
Model of an active rear door heat exchanger (RDHx) for IT racks.
In this configuration, an integrated fan drives the warm server exhaust air through
the heat exchanger mounted at the rear door of the rack.
The fan speed is modulated by a PI controller to maintain zero back pressure.
The fan power is reported through the output PFan.
The liquid coolant enters through portCoo_a and exits through
portCoo_b. The air enters through portAir_a (warm server
exhaust), passes through the fan and then through the heat exchanger, and exits through
portAir_b (cooled air leaving the rack).
The performance data are provided through the record dat of type
Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Data.Active.Generic.
Extends from Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.BaseClasses.PartialRearDoorHeatExchanger (Partial model of a rear door heat exchanger with coolant and air ports).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumCoo | PartialMedium | Medium for rear door heat exchanger coolant loop | |
| replaceable package MediumAir | PartialMedium | Medium for air side | |
| Fan controller | |||
| Real | k | 1 | Gain of PI controller |
| Time | Ti | 10 | Integrator time constant of PI controller [s] |
| Assumptions | |||
| Boolean | allowFlowReversalCoo | true | = false to simplify equations on coolant side, assuming, but not enforcing, no flow reversal |
| Boolean | allowFlowReversalAir | true | = false to simplify equations on air side, assuming, but not enforcing, no flow reversal |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance for fan |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | portCoo_a | Coolant inlet port |
| FluidPort_b | portCoo_b | Coolant outlet port |
| FluidPort_a | portAir_a | Air inlet port |
| FluidPort_b | portAir_b | Air outlet port |
| output RealOutput | PFan | Power consumed by rear door heat exchanger fan [W] |
Modelica definition
Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Passive
Passive rear door heat exchanger — air driven by fans in server
Information
Model of a passive rear door heat exchanger (RDHx) for IT racks.
In this configuration, the server fans inside the rack drive the warm exhaust air through the heat exchanger mounted at the rear door. No dedicated fan is added; the air-side pressure drop is overcome by the server fans.
The liquid coolant enters through portCoo_a and exits through
portCoo_b. The air enters through portAir_a (warm server
exhaust) and exits through portAir_b (cooled air leaving the rack).
The performance data are provided through the record dat of type
Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Data.Passive.Generic.
Extends from Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.BaseClasses.PartialRearDoorHeatExchanger (Partial model of a rear door heat exchanger with coolant and air ports).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumCoo | PartialMedium | Medium for rear door heat exchanger coolant loop | |
| replaceable package MediumAir | PartialMedium | Medium for air side | |
| Nominal condition | |||
| Generic | dat | redeclare parameter Building... | Heat exchanger performance data |
| Assumptions | |||
| Boolean | allowFlowReversalCoo | true | = false to simplify equations on coolant side, assuming, but not enforcing, no flow reversal |
| Boolean | allowFlowReversalAir | true | = false to simplify equations on air side, assuming, but not enforcing, no flow reversal |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | portCoo_a | Coolant inlet port |
| FluidPort_b | portCoo_b | Coolant outlet port |
| FluidPort_a | portAir_a | Air inlet port |
| FluidPort_b | portAir_b | Air outlet port |