Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.BaseClasses
Base classes for rear door heat exchanger models
Information
Package with base classes for rear door heat exchanger models.
Extends from Modelica.Icons.BasesPackage (Icon for packages containing base classes).
Package Content
| Name | Description |
|---|---|
| Partial model of a rear door heat exchanger with coolant and air ports |
Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.BaseClasses.PartialRearDoorHeatExchanger
Partial model of a rear door heat exchanger with coolant and air ports
Information
Partial model of a rear door heat exchanger (RDHx) with four fluid ports: two for the liquid coolant side and two for the air side.
The heat exchanger is modeled using
Buildings.Fluid.HeatExchangers.DryCoilEffectivenessNTU
with a cross-flow unmixed configuration.
The performance data are provided through the record dat.
The coolant connections (port_a1 to port_b1) are included in this partial model. The air connections are left to the extending models, because the Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Active model inserts a fan in the air path while the Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Passive model connects the ports directly.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumCoo | Modelica.Media.Interfaces.Pa... | Medium for rear door heat exchanger coolant loop | |
| replaceable package MediumAir | Modelica.Media.Interfaces.Pa... | Medium for air side | |
| Nominal condition | |||
| Generic | dat | redeclare parameter Building... | Heat exchanger performance data |
| Assumptions | |||
| Boolean | allowFlowReversalCoo | true | = false to simplify equations on coolant side, assuming, but not enforcing, no flow reversal |
| Boolean | allowFlowReversalAir | true | = false to simplify equations on air side, assuming, but not enforcing, no flow reversal |
Connectors
| Type | Name | Description |
|---|---|---|
| replaceable package MediumCoo | Medium for rear door heat exchanger coolant loop | |
| replaceable package MediumAir | Medium for air side | |
| FluidPort_a | portCoo_a | Coolant inlet port |
| FluidPort_b | portCoo_b | Coolant outlet port |
| FluidPort_a | portAir_a | Air inlet port |
| FluidPort_b | portAir_b | Air outlet port |