Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Data.Active
Data records for active rear door heat exchangers
Information
This package contains data records for active rear door heat exchangers. In an active rear door heat exchanger, an integrated fan drives airflow through the heat exchanger independently of the server fans inside the rack.
Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).
Package Content
| Name | Description |
|---|---|
| Data record for active rear door heat exchanger |
Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Data.Active.Generic
Data record for active rear door heat exchanger
Information
Data record for an active rear door heat exchanger used in IT rack models.
This record extends Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Data.Passive.Generic and adds performance data for the fans.
Extends from Buildings.Fluid.DataCenters.Racks.RearDoorHeatExchangers.Data.Passive.Generic (Data record for passive rear door heat exchanger).
Contents
| Type | Name | Default | Description |
|---|---|---|---|
| SpecificHeatCapacity | cpCoo_nominal | Buildings.Media.Water.cp_const | Specific heat capacity of rear door heat exchanger coolant fluid [J/(kg.K)] |
| SpecificHeatCapacity | cpAir_nominal | Buildings.Utilities.Psychrom... | Specific heat capacity of air [J/(kg.K)] |
| Nominal condition | |||
| MassFlowRate | mAir_flow_nominal | Design air mass flow rate for heat exchanger [kg/s] | |
| MassFlowRate | mCoo_flow_nominal | Design coolant flow rate for heat exchanger parameterization [kg/s] | |
| HeatFlowRate | Q_flow_nominal | Cooling capacity at design condition (negative number) [W] | |
| Temperature | TAirIn_nominal | Air inlet nominal temperature (air entering rear door heat exchanger) [K] | |
| Temperature | TCooIn_nominal | Rear door coolant inlet nominal temperature [K] | |
| PressureDifference | dpCoo_nominal | 10000 | Coolant-side pressure drop at nominal flow rate [Pa] |
| PressureDifference | dpAir_nominal | 200 | Air-side pressure drop at nominal flow rate [Pa] |
| Fan power | |||
| Power | PFan_nominal | mAir_flow_nominal*dpAir_nomi... | Fan power at full speed [W] |
| Fan | |||
| Real | eta_nominal | 0.7 | Fan and motor combined efficiency at nominal conditions [1] |