Buildings.Fluid.HeatPumps.ModularReversible.Controls.Safety
Contains typical safety controllers for heat pumps
Information
Package with safety controls typically applied in heat pumps and chiller devices.
Extends from Modelica.Icons.Package (Icon for standard packages).
Package Content
Name | Description |
---|---|
![]() |
Model to prevent source from freezing |
![]() |
Safety control for minimum mass flow rate |
![]() |
Controlls if the Safety constraints for on-time, off-time, and cycle rate |
![]() |
Indicates if the heat pump operation is within a defined envelope |
![]() |
Model including all safety levels |
![]() |
Package with parameters for safety control blocks |
![]() |
Examples package |
![]() |
Package with base classes for Buildings.Fluid.HeatPump.Controls.Safety |
Buildings.Fluid.HeatPumps.ModularReversible.Controls.Safety.AntiFreeze
Model to prevent source from freezing
Information
This model is used to prevent freezing of the condenser or evaporator side. A real device would shut off as well.
This models takes the minimum of the two temperatures evaporator outlet and condenser inlet. If this minimal temperature falls below the given lower boundary, the hystereses will trigger an error and cause the device to switch off.
Assumptions
This block does not check the evaporator inlet or condenser outlet temperatures because they are assumed to be always higher than the other side.Extends from BaseClasses.PartialSafetyWithCounter (Safety control which adds an error counter to the I/O).
Parameters
Type | Name | Default | Description |
---|---|---|---|
ThermodynamicTemperature | TAntFre | 276.15 | Limit temperature for anti freeze control [K] |
Real | dTHys | 2 | Hysteresis interval width |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | ySet | Input for relative compressor speed from 0 to 1 |
output RealOutput | yOut | Output for relative compressor speed from 0 to 1 |
RefrigerantMachineControlBus | sigBus | Bus-connector for the heat pump |
output IntegerOutput | err | Integer for displaying number of errors during simulation |
Modelica definition
Buildings.Fluid.HeatPumps.ModularReversible.Controls.Safety.MinimalFlowRate
Safety control for minimum mass flow rate
Information
Safety control to prevent the device from turning on if the mass flow rate is too low in either condenser or evaporator.
Used in real devices to prevent overheating or freezing of components.
Extends from BaseClasses.PartialSafetyWithCounter (Safety control which adds an error counter to the I/O).
Parameters
Type | Name | Default | Description |
---|---|---|---|
MassFlowRate | mEvaMin_flow | Minimal mass flow rate in evaporator required to operate the device [kg/s] | |
MassFlowRate | mConMin_flow | Minimal mass flow rate in condenser required to operate the device [kg/s] |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | ySet | Input for relative compressor speed from 0 to 1 |
output RealOutput | yOut | Output for relative compressor speed from 0 to 1 |
RefrigerantMachineControlBus | sigBus | Bus-connector for the heat pump |
output IntegerOutput | err | Integer for displaying number of errors during simulation |
Modelica definition
Buildings.Fluid.HeatPumps.ModularReversible.Controls.Safety.OnOff
Controlls if the Safety constraints for on-time, off-time, and cycle rate
Information
Checks if the ySet
value is legal by checking if
the device can either be turned on or off,
depending on which state it was in.
The output yOut
equals ySet
, if the device
-
is on and
ySet
is greater thanySet_small
-
or is off and
ySet
is 0 - or is on and should turn off, and exceeds the minimal on-time (if active)
- or is off and should turn on, and does neither exceed the maximal cycle rate (if active) nor violates the minimal off-time (if active).
If the device is on and should turn off, but does not exceed
the minimal on-time (if active), yOut
equals min(ySet, ySetMin)
.
If the device is off and should turn on, but exceeds the maximal
cycle rate (if active) or violates the minimal
off-time (if active), yOut
equals 0.
Extends from BaseClasses.PartialSafety (Safety control with I/O).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Boolean | use_minOnTime | true | =false to ignore minimum on-time constraint |
Time | minOnTime | Minimum on-time [s] | |
Boolean | use_minOffTime | true | =false to ignore minimum off time constraint |
Time | minOffTime | Minimum off time [s] | |
Boolean | use_maxCycRat | true | =false to ignore maximal cycle rate constraint |
Integer | maxCycRat | Maximum cycle rate | |
Boolean | onOffMea_start | true | Start value for the on-off signal of the device, true for on |
Real | ySet_small | Threshold for relative speed for the device to be considered on | |
Real | ySetRed | ySet_small | Reduced relative compressor speed to allow longer on-time |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | ySet | Input for relative compressor speed from 0 to 1 |
output RealOutput | yOut | Output for relative compressor speed from 0 to 1 |
RefrigerantMachineControlBus | sigBus | Bus-connector for the heat pump |
Modelica definition
Buildings.Fluid.HeatPumps.ModularReversible.Controls.Safety.OperationalEnvelope
Indicates if the heat pump operation is within a defined envelope
Information
Model to check if the operating conditions of a heat pump are inside the given boundaries. If not, the heat pump or chiller will switch off.
Read the documentation of Buildings.Fluid.HeatPumps.ModularReversible.Controls.Safety.BaseClasses.PartialOperationalEnvelope for more information.
Extends from BaseClasses.PartialOperationalEnvelope (Indicates if the device operation is within a defined envelope).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Temperature | tabUppHea[:, 2] | Upper boundary for heating with second column as useful temperature side [K] | |
Temperature | tabLowCoo[:, 2] | Lower boundary for cooling with second column as useful temperature side [K] | |
TemperatureDifference | dTHys | 5 | Temperature deadband in the operational envelope [K] |
Operational Envelope | |||
Boolean | use_TConOutHea | true | =true to use condenser outlet temperature for envelope in heating mode, false for inlet |
Boolean | use_TEvaOutHea | false | =true to use evaporator outlet temperature for envelope in heating mode, false for inlet |
Boolean | use_TConOutCoo | false | =true to use useful side outlet temperature for envelope in cooling mode, false for inlet |
Boolean | use_TEvaOutCoo | true | =true to use evaporator outlet temperature for envelope in cooling mode, false for inlet |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | ySet | Input for relative compressor speed from 0 to 1 |
output RealOutput | yOut | Output for relative compressor speed from 0 to 1 |
RefrigerantMachineControlBus | sigBus | Bus-connector for the heat pump |
output IntegerOutput | err | Integer for displaying number of errors during simulation |
Modelica definition
Buildings.Fluid.HeatPumps.ModularReversible.Controls.Safety.Safety
Model including all safety levels
Information
Aggregation of the four main safety controls of a refrigerant machine (heat pump or chiller).
The order is based on the relevance to a real system. Antifreeze control and mininmum flow rate control are put last because of the relevance for the simulation. If the medium temperature falls below or rises above the critical values, the simulation will fail.
All used functions are optional. See the used models for more information on each safety function:
- Buildings.Fluid.HeatPumps.ModularReversible.Controls.Safety.OnOff
- Buildings.Fluid.HeatPumps.ModularReversible.Controls.Safety.OperationalEnvelope
- Buildings.Fluid.HeatPumps.ModularReversible.Controls.Safety.AntiFreeze
- Buildings.Fluid.HeatPumps.ModularReversible.Controls.Safety.MinimalFlowRate
Extends from BaseClasses.PartialSafety (Safety control with I/O).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | ySet_small | Threshold for relative speed for the device to be considered on | |
Generic | safCtrPar | redeclare parameter Building... | Safety control parameters |
OperationalEnvelope | opeEnv | redeclare Buildings.Fluid.He... | Block for operational envelope |
Mass flow rates | |||
MassFlowRate | mEva_flow_nominal | Nominal mass flow rate in evaporator medium [kg/s] | |
MassFlowRate | mCon_flow_nominal | Nominal mass flow rate in condenser medium [kg/s] |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | ySet | Input for relative compressor speed from 0 to 1 |
output RealOutput | yOut | Output for relative compressor speed from 0 to 1 |
RefrigerantMachineControlBus | sigBus | Bus-connector for the heat pump |
output IntegerOutput | opeEnvErr | Number of errors from violating the operational envelope |
output IntegerOutput | antFreErr | Number of errors from antifreeze control |
output IntegerOutput | minFlowErr | Number of errors from violating minimum flow rates |