Buildings.Obsolete.Fluid.Movers.Data.Pumps.Wilo

Package with performance data for Wilo pumps

Information

This package contains performance data for Wilo pumps.

Extends from Modelica.Icons.Package (Icon for standard packages).

Package Content

Name Description
Buildings.Obsolete.Fluid.Movers.Data.Pumps.Wilo.Stratos25slash1to4 Stratos25slash1to4 Pump data for a Wilo Stratos 25/1-4 pump
Buildings.Obsolete.Fluid.Movers.Data.Pumps.Wilo.Stratos32slash1to12 Stratos32slash1to12 Pump data for a Wilo Stratos 32/1-12 pump

Buildings.Obsolete.Fluid.Movers.Data.Pumps.Wilo.Stratos25slash1to4 Buildings.Obsolete.Fluid.Movers.Data.Pumps.Wilo.Stratos25slash1to4

Pump data for a Wilo Stratos 25/1-4 pump

Information

Data from: http://productfinder.wilo.com/en/COM/product/0000000e000379df0002003a/fc_product_datasheet

See Buildings.Fluid.Movers.Data.Pumps.Wilo.Stratos25slash1to6 for more information about how the data is derived.

Extends from Generic (Generic data record for movers).

Parameters

TypeNameDefaultDescription
VolumeFlowRateV_flow_maxif havePressureCurve then (p...Volume flow rate on the curve when pressure rise is zero [m3/s]
PressureDifferencedpMaxif havePressureCurve then (p...Pressure rise on the curve when flow rate is zero [Pa]
Power computation
HydraulicEfficiencyMethodetaHydMetBuildings.Fluid.Movers.BaseC...Efficiency computation method for the hydraulic efficiency etaHyd
MotorEfficiencyMethodetaMotMetif powerOrEfficiencyIsHydrau...Efficiency computation method for the motor efficiency etaMot
BooleanpowerOrEfficiencyIsHydraulicfalse=true if hydraulic power or efficiency is provided, instead of total
efficiencyParametersefficiency Total or hydraulic efficiency vs. volumetric flow rate
efficiencyParametersmotorEfficiency Motor efficiency vs. volumetric flow rate
efficiencyParameters_yMotmotorEfficiency_yMot Motor efficiency vs. part load ratio yMot, where yMot = WHyd/WMot_nominal
peakpeak Volume flow rate, pressure rise, and efficiency (either total or hydraulic) at peak condition
PowerWMot_nominalif max(power.P) > Modelica.C...Rated motor power [W]
EfficiencyetaMot_max0.7Maximum motor efficiency [1]
Motor heat rejection
BooleanmotorCooledByFluidtrueIf true, then motor heat is added to fluid stream
Normalized speeds (used in model, default values assigned from speeds in rpm)
Realspeed_nominal1Nominal rotational speed for flow characteristic [1]
RealconstantSpeedconstantSpeed_rpm/speed_rpm_...Normalized speed set point, used if inputType = Buildings.Fluid.Types.InputType.Constant [1]
Realspeeds[:]speeds_rpm/speed_rpm_nominalVector of normalized speed set points, used if inputType = Buildings.Fluid.Types.InputType.Stages [1]
Speeds in RPM
AngularVelocity_rpmspeed_rpm_nominal1800Nominal rotational speed for flow characteristic [rev/min]
AngularVelocity_rpmconstantSpeed_rpmspeed_rpm_nominalSpeed set point, used if inputType = Buildings.Fluid.Types.InputType.Constant [rev/min]
AngularVelocity_rpmspeeds_rpm[:]{speed_rpm_nominal}Vector of speed set points, used if inputType = Buildings.Fluid.Types.InputType.Stages [rev/min]

Modelica definition

record Stratos25slash1to4 "Pump data for a Wilo Stratos 25/1-4 pump" extends Generic( speed_rpm_nominal=1800, final powerOrEfficiencyIsHydraulic=false, etaHydMet=Buildings.Fluid.Movers.BaseClasses.Types.HydraulicEfficiencyMethod.Power_VolumeFlowRate, power(V_flow={5.55555555556e-07, 0.000402190923318, 0.00052269170579, 0.000643192488263, 0.000752738654147, 0.000866979655712, 0.000973395931142, 0.00108607198748, 0.00115962441315}, P={ 14.2085618951, 21.2596204596, 23.3573239437, 25.1349149442, 26.581943662, 27.9121571534, 28.8498841148, 29.4981726255, 29.7520982304}), pressure(V_flow={5.55555555556e-07, 0.000402190923318, 0.00052269170579, 0.000643192488263, 0.000752738654147, 0.000866979655712, 0.000973395931142, 0.00108607198748, 0.00115962441315}, dp={ 17066.9518717, 16997.0053476, 16437.4331551, 15528.1283422, 14408.9839572, 13149.9465241, 11681.0695187, 9932.40641711, 8533.47593583})); end Stratos25slash1to4;

Buildings.Obsolete.Fluid.Movers.Data.Pumps.Wilo.Stratos32slash1to12 Buildings.Obsolete.Fluid.Movers.Data.Pumps.Wilo.Stratos32slash1to12

Pump data for a Wilo Stratos 32/1-12 pump

Information

Data from: http://productfinder.wilo.com/en/COM/product/0000000e000379df0002003a/fc_product_datasheet

See Buildings.Fluid.Movers.Data.Pumps.Wilo.Stratos25slash1to6 for more information about how the data is derived.

Extends from Generic (Generic data record for movers).

Parameters

TypeNameDefaultDescription
VolumeFlowRateV_flow_maxif havePressureCurve then (p...Volume flow rate on the curve when pressure rise is zero [m3/s]
PressureDifferencedpMaxif havePressureCurve then (p...Pressure rise on the curve when flow rate is zero [Pa]
Power computation
HydraulicEfficiencyMethodetaHydMetBuildings.Fluid.Movers.BaseC...Efficiency computation method for the hydraulic efficiency etaHyd
MotorEfficiencyMethodetaMotMetif powerOrEfficiencyIsHydrau...Efficiency computation method for the motor efficiency etaMot
BooleanpowerOrEfficiencyIsHydraulicfalse=true if hydraulic power or efficiency is provided, instead of total
efficiencyParametersefficiency Total or hydraulic efficiency vs. volumetric flow rate
efficiencyParametersmotorEfficiency Motor efficiency vs. volumetric flow rate
efficiencyParameters_yMotmotorEfficiency_yMot Motor efficiency vs. part load ratio yMot, where yMot = WHyd/WMot_nominal
peakpeak Volume flow rate, pressure rise, and efficiency (either total or hydraulic) at peak condition
PowerWMot_nominalif max(power.P) > Modelica.C...Rated motor power [W]
EfficiencyetaMot_max0.7Maximum motor efficiency [1]
Motor heat rejection
BooleanmotorCooledByFluidtrueIf true, then motor heat is added to fluid stream
Normalized speeds (used in model, default values assigned from speeds in rpm)
Realspeed_nominal1Nominal rotational speed for flow characteristic [1]
RealconstantSpeedconstantSpeed_rpm/speed_rpm_...Normalized speed set point, used if inputType = Buildings.Fluid.Types.InputType.Constant [1]
Realspeeds[:]speeds_rpm/speed_rpm_nominalVector of normalized speed set points, used if inputType = Buildings.Fluid.Types.InputType.Stages [1]
Speeds in RPM
AngularVelocity_rpmspeed_rpm_nominal3580Nominal rotational speed for flow characteristic [rev/min]
AngularVelocity_rpmconstantSpeed_rpmspeed_rpm_nominalSpeed set point, used if inputType = Buildings.Fluid.Types.InputType.Constant [rev/min]
AngularVelocity_rpmspeeds_rpm[:]{speed_rpm_nominal}Vector of speed set points, used if inputType = Buildings.Fluid.Types.InputType.Stages [rev/min]

Modelica definition

record Stratos32slash1to12 "Pump data for a Wilo Stratos 32/1-12 pump" extends Generic( speed_rpm_nominal=3580, final powerOrEfficiencyIsHydraulic=false, etaHydMet=Buildings.Fluid.Movers.BaseClasses.Types.HydraulicEfficiencyMethod.Power_VolumeFlowRate, power(V_flow={2.11830535572e-05, 0.000167865707434, 0.000700939248601, 0.0012450039968, 0.00177258193445, 0.00227268185452, 0.00272332134293, 0.00312450039968, 0.00345423661071}, P={ 103.427852653, 110.225580543, 135.414121033, 162.955749719, 191.043411366, 216.051565678, 230.204882307, 236.346847436, 239.552825212}), pressure(V_flow={2.11830535572e-05, 0.000167865707434, 0.000700939248601, 0.0012450039968, 0.00177258193445, 0.00227268185452, 0.00272332134293, 0.00312450039968, 0.00345423661071}, dp={ 59279.4925671, 59115.2927989, 59000.1476354, 57351.238791, 54446.2693068, 50284.7374612, 44865.6398104, 38328.4550274, 32066.9663984})); end Stratos32slash1to12;