This package contains examples for the use of models that can be found in Buildings.Fluid.HeatExchangers.CoolingTowers.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
Name | Description |
---|---|
FixedApproachDryBulb | Test model for cooling tower with fixed approach temperature using the dry-bulb temperature |
FixedApproachWetBulb | Test model for cooling tower with fixed approach temperature using the wet-bulb temperature |
YorkCalc | Test model for cooling tower using the York performance correlation |
BaseClasses | Package with base classes for Buildings.Fluid.HeatExchangers.CoolingTowers.Examples |
vol
. An on/off controller
switches the cooling loop water pump on or off based on the temperature of
this volume.
The cooling tower outlet temperature has a fixed approach temperature to the
outdoor dry-bulb temperature.
Extends from Modelica.Icons.Example (Icon for runnable examples), Buildings.Fluid.HeatExchangers.CoolingTowers.Examples.BaseClasses.PartialStaticTwoPortCoolingTower (Base class for test models of cooling towers).
Type | Name | Default | Description |
---|---|---|---|
Nominal condition | |||
MassFlowRate | mWat_flow_nominal | 0.5 | Design air flow rate [kg/s] |
Type | Name | Description |
---|---|---|
Bus | weaBus |
model FixedApproachDryBulb "Test model for cooling tower with fixed approach temperature using the dry-bulb temperature" extends Modelica.Icons.Example; extends Buildings.Fluid.HeatExchangers.CoolingTowers.Examples.BaseClasses.PartialStaticTwoPortCoolingTower ( redeclare Buildings.Fluid.HeatExchangers.CoolingTowers.FixedApproach tow); equationconnect(weaBus.TDryBul, tow.TAir); end FixedApproachDryBulb;
vol
. An on/off controller
switches the cooling loop water pump on or off based on the temperature of
this volume.
The cooling tower outlet temperature has a fixed approach temperature to the
outdoor wet-bulb temperature.
Extends from Modelica.Icons.Example (Icon for runnable examples), Buildings.Fluid.HeatExchangers.CoolingTowers.Examples.BaseClasses.PartialStaticTwoPortCoolingTowerWetBulb (Partial test model for cooling tower with wet bulb temperature as potential for heat transfer).
Type | Name | Default | Description |
---|---|---|---|
Nominal condition | |||
MassFlowRate | mWat_flow_nominal | 0.5 | Design air flow rate [kg/s] |
Type | Name | Description |
---|---|---|
Bus | weaBus |
model FixedApproachWetBulb "Test model for cooling tower with fixed approach temperature using the wet-bulb temperature" extends Modelica.Icons.Example; extends Buildings.Fluid.HeatExchangers.CoolingTowers.Examples.BaseClasses.PartialStaticTwoPortCoolingTowerWetBulb ( redeclare FixedApproach tow); equationconnect(wetBulTem.TWetBul, tow.TAir); end FixedApproachWetBulb;
vol
. An on/off controller
switches the cooling loop water pump on or off based on the temperature of
this volume.
The cooling tower outlet temperature is controlled to track a fixed temperature.
Extends from Modelica.Icons.Example (Icon for runnable examples), Buildings.Fluid.HeatExchangers.CoolingTowers.Examples.BaseClasses.PartialStaticTwoPortCoolingTowerWetBulb (Partial test model for cooling tower with wet bulb temperature as potential for heat transfer).
Type | Name | Default | Description |
---|---|---|---|
Nominal condition | |||
MassFlowRate | mWat_flow_nominal | 0.5 | Design air flow rate [kg/s] |
Type | Name | Description |
---|---|---|
Bus | weaBus |
model YorkCalc "Test model for cooling tower using the York performance correlation" extends Modelica.Icons.Example; extends Buildings.Fluid.HeatExchangers.CoolingTowers.Examples.BaseClasses.PartialStaticTwoPortCoolingTowerWetBulb ( redeclare Buildings.Fluid.HeatExchangers.CoolingTowers.YorkCalc tow, onOffController(bandwidth=2));Modelica.Blocks.Sources.Constant TSetLea(k=273.15 + 18) "Setpoint for leaving temperature"; Controls.Continuous.LimPID conFan( k=1, Ti=60, Td=10, reverseAction=true) "Controller for tower fan"; equationconnect(wetBulTem.TWetBul, tow.TAir); connect(TSetLea.y, conFan.u_s); connect(conFan.y, tow.y); connect(tow.TLvg, conFan.u_m); end YorkCalc;