Extends from Modelica.Icons.VariantsPackage (Icon for package containing variants).
Name | Description |
---|---|
UsersGuide | User's Guide |
FlowMachine_y | Fan or pump with ideally controlled normalized speed y as input signal |
FlowMachine_Nrpm | Fan or pump with ideally controlled speed Nrpm as input signal |
FlowMachine_dp | Fan or pump with ideally controlled head dp as input signal |
FlowMachine_m_flow | Fan or pump with ideally controlled mass flow rate as input signal |
FlowMachinePolynomial | Fan or pump with head and efficiency declared by a non-dimensional polynomial |
Examples | Collection of models that illustrate model use and test models |
BaseClasses | Package with base classes for Buildings.Fluid.Movers |
This model describes a fan or pump with prescribed normalized speed. The input connector provides the normalized rotational speed (between 0 and 1). The head is computed based on the performance curve that take as an argument the actual volume flow rate divided by the maximum flow rate and the relative speed of the fan. The efficiency of the device is computed based on the efficiency curves that take as an argument the actual volume flow rate divided by the maximum possible volume flow rate, or based on the motor performance curves.
See the User's Guide for more information.
Extends from Buildings.Fluid.Movers.BaseClasses.PrescribedFlowMachine (Partial model for fan or pump with speed (y or Nrpm) as input signal).
Type | Name | Default | Description |
---|---|---|---|
replaceable package Medium | PartialMedium | Medium in the component | |
Boolean | addPowerToMedium | true | Set to false to avoid any power (=heat and flow work) being added to medium (may give simpler equations) |
Characteristics | |||
Boolean | use_powerCharacteristic | false | Use powerCharacteristic (vs. efficiencyCharacteristic) |
Boolean | motorCooledByFluid | true | If true, then motor heat is added to fluid stream |
efficiencyParameters | motorEfficiency | Normalized volume flow rate vs. efficiency | |
efficiencyParameters | hydraulicEfficiency | Normalized volume flow rate vs. efficiency | |
AngularVelocity_rpm | N_nominal | 1500 | Nominal rotational speed for flow characteristic [1/min] |
flowParameters | pressure | Volume flow rate vs. total pressure rise | |
powerParameters | power | Volume flow rate vs. electrical power consumption | |
Initialization | |||
Real | r_V.start | 1 | Ratio V_flow/V_flow_max [1] |
MassFlowRate | m_flow.start | 0 | Mass flow rate from port_a to port_b (m_flow > 0 is design flow direction) [kg/s] |
Pressure | dp.start | 0 | Pressure difference between port_a and port_b [Pa] |
Advanced | |||
Boolean | homotopyInitialization | true | = true, use homotopy method |
MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
Diagnostics | |||
Boolean | show_T | false | = true, if actual temperature at port is computed (may lead to events) |
Dynamics | |||
Filtered speed | |||
Boolean | filteredSpeed | true | = true, if speed is filtered with a 2nd order CriticalDamping filter |
Time | riseTime | 30 | Rise time of the filter (time to reach 99.6 % of the speed) [s] |
Init | init | Modelica.Blocks.Types.Init.I... | Type of initialization (no init/steady state/initial state/initial output) |
Real | N_start | 0 | Initial value of speed |
Equations | |||
Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Formulation of energy balance |
Dynamics | massDynamics | energyDynamics | Formulation of mass balance |
Boolean | dynamicBalance | true | Set to true to use a dynamic balance, which often leads to smaller systems of equations |
Nominal condition | |||
Time | tau | 1 | Time constant of fluid volume for nominal flow, used if dynamicBalance=true [s] |
Initialization | |||
AbsolutePressure | p_start | Medium.p_default | Start value of pressure [Pa] |
Temperature | T_start | Medium.T_default | Start value of temperature [K] |
MassFraction | X_start[Medium.nX] | Medium.X_default | Start value of mass fractions m_i/m [kg/kg] |
ExtraProperty | C_start[Medium.nC] | fill(0, Medium.nC) | Start value of trace substances |
ExtraProperty | C_nominal[Medium.nC] | fill(1E-2, Medium.nC) | Nominal value of trace substances. (Set to typical order of magnitude.) |
Assumptions | |||
Boolean | allowFlowReversal | system.allowFlowReversal | = true to allow flow reversal, false restricts to design direction (port_a -> port_b) |
Type | Name | Description |
---|---|---|
output RealOutput | N_actual | [1/min] |
FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
HeatPort_a | heatPort | |
input RealInput | y | Constant normalized rotational speed [1] |
model FlowMachine_y "Fan or pump with ideally controlled normalized speed y as input signal" extends Buildings.Fluid.Movers.BaseClasses.PrescribedFlowMachine( final N_nominal=1500 "fix N_nominal as it is used only for scaling");Modelica.Blocks.Interfaces.RealInput y(min=0, max=1, unit="1") "Constant normalized rotational speed"; protected Modelica.Blocks.Math.Gain gaiSpe(final k=N_nominal, u(min=0, max=1), y(final quantity="AngularVelocity", final unit="1/min", nominal=N_nominal)) "Gain for speed input signal"; equationconnect(y, gaiSpe.u); connect(filter.y, N_filtered); if filteredSpeed thenconnect(gaiSpe.y, filter.u); connect(filter.y, N_actual); elseconnect(gaiSpe.y, N_actual); end if;end FlowMachine_y;
See the User's Guide for more information.
Extends from Buildings.Fluid.Movers.BaseClasses.PrescribedFlowMachine (Partial model for fan or pump with speed (y or Nrpm) as input signal).
Type | Name | Default | Description |
---|---|---|---|
replaceable package Medium | PartialMedium | Medium in the component | |
Boolean | addPowerToMedium | true | Set to false to avoid any power (=heat and flow work) being added to medium (may give simpler equations) |
Characteristics | |||
Boolean | use_powerCharacteristic | false | Use powerCharacteristic (vs. efficiencyCharacteristic) |
Boolean | motorCooledByFluid | true | If true, then motor heat is added to fluid stream |
efficiencyParameters | motorEfficiency | Normalized volume flow rate vs. efficiency | |
efficiencyParameters | hydraulicEfficiency | Normalized volume flow rate vs. efficiency | |
AngularVelocity_rpm | N_nominal | 1500 | Nominal rotational speed for flow characteristic [1/min] |
flowParameters | pressure | Volume flow rate vs. total pressure rise | |
powerParameters | power | Volume flow rate vs. electrical power consumption | |
Initialization | |||
Real | r_V.start | 1 | Ratio V_flow/V_flow_max [1] |
MassFlowRate | m_flow.start | 0 | Mass flow rate from port_a to port_b (m_flow > 0 is design flow direction) [kg/s] |
Pressure | dp.start | 0 | Pressure difference between port_a and port_b [Pa] |
Advanced | |||
Boolean | homotopyInitialization | true | = true, use homotopy method |
MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
Diagnostics | |||
Boolean | show_T | false | = true, if actual temperature at port is computed (may lead to events) |
Dynamics | |||
Filtered speed | |||
Boolean | filteredSpeed | true | = true, if speed is filtered with a 2nd order CriticalDamping filter |
Time | riseTime | 30 | Rise time of the filter (time to reach 99.6 % of the speed) [s] |
Init | init | Modelica.Blocks.Types.Init.I... | Type of initialization (no init/steady state/initial state/initial output) |
Real | N_start | 0 | Initial value of speed |
Equations | |||
Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Formulation of energy balance |
Dynamics | massDynamics | energyDynamics | Formulation of mass balance |
Boolean | dynamicBalance | true | Set to true to use a dynamic balance, which often leads to smaller systems of equations |
Nominal condition | |||
Time | tau | 1 | Time constant of fluid volume for nominal flow, used if dynamicBalance=true [s] |
Initialization | |||
AbsolutePressure | p_start | Medium.p_default | Start value of pressure [Pa] |
Temperature | T_start | Medium.T_default | Start value of temperature [K] |
MassFraction | X_start[Medium.nX] | Medium.X_default | Start value of mass fractions m_i/m [kg/kg] |
ExtraProperty | C_start[Medium.nC] | fill(0, Medium.nC) | Start value of trace substances |
ExtraProperty | C_nominal[Medium.nC] | fill(1E-2, Medium.nC) | Nominal value of trace substances. (Set to typical order of magnitude.) |
Assumptions | |||
Boolean | allowFlowReversal | system.allowFlowReversal | = true to allow flow reversal, false restricts to design direction (port_a -> port_b) |
Type | Name | Description |
---|---|---|
output RealOutput | N_actual | [1/min] |
FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
HeatPort_a | heatPort | |
input RealInput | Nrpm | Prescribed rotational speed [1/min] |
model FlowMachine_Nrpm "Fan or pump with ideally controlled speed Nrpm as input signal" extends Buildings.Fluid.Movers.BaseClasses.PrescribedFlowMachine;Modelica.Blocks.Interfaces.RealInput Nrpm(unit="1/min") "Prescribed rotational speed"; equation if filteredSpeed thenconnect(Nrpm, filter.u); connect(filter.y, N_actual); connect(filter.y, N_filtered); elseconnect(Nrpm, N_actual); end if;end FlowMachine_Nrpm;
This model describes a fan or pump with prescribed head. The input connector provides the difference between outlet minus inlet pressure. The efficiency of the device is computed based on the efficiency curves that take as an argument the actual volume flow rate divided by the maximum possible volume flow rate.
If filteredSpeed=true
, then the parameter dp_nominal
is
used to normalize the filter. This is used to improve the numerics of the transient response.
The actual pressure raise of the mover at steady-state is independent
of the value of dp_nominal
. It is recommended to set
dp_nominal
to approximately the pressure raise that the fan has during
full speed.
See the User's Guide for more information.
Extends from Buildings.Fluid.Movers.BaseClasses.ControlledFlowMachine (Partial model for fan or pump with ideally controlled mass flow rate or head as input signal).
Type | Name | Default | Description |
---|---|---|---|
replaceable package Medium | PartialMedium | Medium in the component | |
Boolean | addPowerToMedium | true | Set to false to avoid any power (=heat and flow work) being added to medium (may give simpler equations) |
Boolean | control_m_flow | false | = false to control head instead of m_flow |
Nominal condition | |||
MassFlowRate | m_flow_nominal | Nominal mass flow rate [kg/s] | |
Initialization | |||
MassFlowRate | m_flow.start | 0 | Mass flow rate from port_a to port_b (m_flow > 0 is design flow direction) [kg/s] |
Pressure | dp.start | 0 | Pressure difference between port_a and port_b [Pa] |
Real | r_V.start | 1 | Ratio V_flow/V_flow_max = V_flow/V_flow(dp=0, N=N_nominal) |
Characteristics | |||
Boolean | motorCooledByFluid | true | If true, then motor heat is added to fluid stream |
efficiencyParameters | motorEfficiency | Normalized volume flow rate vs. efficiency | |
efficiencyParameters | hydraulicEfficiency | Normalized volume flow rate vs. efficiency | |
Dynamics | |||
Equations | |||
Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Formulation of energy balance |
Dynamics | massDynamics | energyDynamics | Formulation of mass balance |
Boolean | dynamicBalance | true | Set to true to use a dynamic balance, which often leads to smaller systems of equations |
Nominal condition | |||
Time | tau | 1 | Time constant of fluid volume for nominal flow, used if dynamicBalance=true [s] |
Filtered speed | |||
Boolean | filteredSpeed | true | = true, if speed is filtered with a 2nd order CriticalDamping filter |
Time | riseTime | 30 | Rise time of the filter (time to reach 99.6 % of the speed) [s] |
Init | init | Modelica.Blocks.Types.Init.I... | Type of initialization (no init/steady state/initial state/initial output) |
Pressure | dp_start | 0 | Initial value of pressure raise [Pa] |
Pressure | dp_nominal | 10000 | Nominal pressure raise, used to normalize filter [Pa] |
Initialization | |||
AbsolutePressure | p_start | Medium.p_default | Start value of pressure [Pa] |
Temperature | T_start | Medium.T_default | Start value of temperature [K] |
MassFraction | X_start[Medium.nX] | Medium.X_default | Start value of mass fractions m_i/m [kg/kg] |
ExtraProperty | C_start[Medium.nC] | fill(0, Medium.nC) | Start value of trace substances |
ExtraProperty | C_nominal[Medium.nC] | fill(1E-2, Medium.nC) | Nominal value of trace substances. (Set to typical order of magnitude.) |
Assumptions | |||
Boolean | allowFlowReversal | system.allowFlowReversal | = true to allow flow reversal, false restricts to design direction (port_a -> port_b) |
Advanced | |||
MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
Boolean | homotopyInitialization | true | = true, use homotopy method |
Diagnostics | |||
Boolean | show_T | false | = true, if actual temperature at port is computed (may lead to events) |
Type | Name | Description |
---|---|---|
FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
HeatPort_a | heatPort | |
input RealInput | dp_in | Prescribed pressure rise [Pa] |
output RealOutput | dp_actual | [Pa] |
model FlowMachine_dp "Fan or pump with ideally controlled head dp as input signal" extends Buildings.Fluid.Movers.BaseClasses.ControlledFlowMachine( final control_m_flow = false, preSou( dp_start=dp_start, m_flow_small=m_flow_small)); // Classes used to implement the filtered speed parameter Boolean filteredSpeed=true "= true, if speed is filtered with a 2nd order CriticalDamping filter"; parameter Modelica.SIunits.Time riseTime=30 "Rise time of the filter (time to reach 99.6 % of the speed)"; parameter Modelica.Blocks.Types.Init init=Modelica.Blocks.Types.Init.InitialOutput "Type of initialization (no init/steady state/initial state/initial output)"; parameter Modelica.SIunits.Pressure dp_start(min=0, displayUnit="Pa")=0 "Initial value of pressure raise"; parameter Modelica.SIunits.Pressure dp_nominal(min=0, displayUnit="Pa")=10000 "Nominal pressure raise, used to normalize filter";Modelica.Blocks.Interfaces.RealInput dp_in(min=0, final unit="Pa") "Prescribed pressure rise"; Modelica.Blocks.Interfaces.RealOutput dp_actual(min=0, final unit="Pa"); protected Modelica.Blocks.Math.Gain gain(final k=-1); Modelica.Blocks.Continuous.Filter filter( order=2, f_cut=5/(2*Modelica.Constants.pi*riseTime), final init=init, final y_start=dp_start, u_nominal=abs(dp_nominal), x(each stateSelect=StateSelect.always), u(final unit="Pa"), y(final unit="Pa"), final analogFilter=Modelica.Blocks.Types.AnalogFilter.CriticalDamping, final filterType=Modelica.Blocks.Types.FilterType.LowPass) if filteredSpeed "Second order filter to approximate transient of rotor, and to improve numerics"; Modelica.Blocks.Interfaces.RealOutput dp_filtered(min=0, final unit="Pa") if filteredSpeed "Filtered pressure"; equation assert(dp_in >= -Modelica.Constants.eps, "dp_in cannot be negative. Obtained dp_in = " + String(dp_in));connect(dp_in, gain.u); if filteredSpeed thenconnect(gain.y, filter.u); connect(filter.y, dp_actual); connect(filter.y, dp_filtered); elseconnect(gain.y, dp_actual); end if;connect(dp_actual, preSou.dp_in); end FlowMachine_dp;
This model describes a fan or pump with prescribed mass flow rate. The efficiency of the device is computed based on the efficiency curves that take as an argument the actual volume flow rate divided by the maximum possible volume flow rate.
See the User's Guide for more information.
Extends from Buildings.Fluid.Movers.BaseClasses.ControlledFlowMachine (Partial model for fan or pump with ideally controlled mass flow rate or head as input signal).
Type | Name | Default | Description |
---|---|---|---|
replaceable package Medium | PartialMedium | Medium in the component | |
Boolean | addPowerToMedium | true | Set to false to avoid any power (=heat and flow work) being added to medium (may give simpler equations) |
Boolean | control_m_flow | true | = false to control head instead of m_flow |
Nominal condition | |||
MassFlowRate | m_flow_nominal | Nominal mass flow rate [kg/s] | |
Initialization | |||
MassFlowRate | m_flow.start | 0 | Mass flow rate from port_a to port_b (m_flow > 0 is design flow direction) [kg/s] |
Pressure | dp.start | 0 | Pressure difference between port_a and port_b [Pa] |
Real | r_V.start | 1 | Ratio V_flow/V_flow_max = V_flow/V_flow(dp=0, N=N_nominal) |
Characteristics | |||
Boolean | motorCooledByFluid | true | If true, then motor heat is added to fluid stream |
efficiencyParameters | motorEfficiency | Normalized volume flow rate vs. efficiency | |
efficiencyParameters | hydraulicEfficiency | Normalized volume flow rate vs. efficiency | |
Dynamics | |||
Equations | |||
Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Formulation of energy balance |
Dynamics | massDynamics | energyDynamics | Formulation of mass balance |
Boolean | dynamicBalance | true | Set to true to use a dynamic balance, which often leads to smaller systems of equations |
Nominal condition | |||
Time | tau | 1 | Time constant of fluid volume for nominal flow, used if dynamicBalance=true [s] |
Filtered speed | |||
Boolean | filteredSpeed | true | = true, if speed is filtered with a 2nd order CriticalDamping filter |
Time | riseTime | 30 | Rise time of the filter (time to reach 99.6 % of the speed) [s] |
Init | init | Modelica.Blocks.Types.Init.I... | Type of initialization (no init/steady state/initial state/initial output) |
MassFlowRate | m_flow_start | 0 | Initial value of mass flow rate [kg/s] |
Initialization | |||
AbsolutePressure | p_start | Medium.p_default | Start value of pressure [Pa] |
Temperature | T_start | Medium.T_default | Start value of temperature [K] |
MassFraction | X_start[Medium.nX] | Medium.X_default | Start value of mass fractions m_i/m [kg/kg] |
ExtraProperty | C_start[Medium.nC] | fill(0, Medium.nC) | Start value of trace substances |
ExtraProperty | C_nominal[Medium.nC] | fill(1E-2, Medium.nC) | Nominal value of trace substances. (Set to typical order of magnitude.) |
Assumptions | |||
Boolean | allowFlowReversal | system.allowFlowReversal | = true to allow flow reversal, false restricts to design direction (port_a -> port_b) |
Advanced | |||
MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
Boolean | homotopyInitialization | true | = true, use homotopy method |
Diagnostics | |||
Boolean | show_T | false | = true, if actual temperature at port is computed (may lead to events) |
Type | Name | Description |
---|---|---|
FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
HeatPort_a | heatPort | |
input RealInput | m_flow_in | Prescribed mass flow rate [kg/s] |
output RealOutput | m_flow_actual | Actual mass flow rate [kg/s] |
model FlowMachine_m_flow "Fan or pump with ideally controlled mass flow rate as input signal" extends Buildings.Fluid.Movers.BaseClasses.ControlledFlowMachine( final control_m_flow=true, preSou(m_flow_start=m_flow_start, m_flow_small= m_flow_small));Modelica.Blocks.Interfaces.RealInput m_flow_in(final unit="kg/s", nominal=m_flow_nominal) "Prescribed mass flow rate"; // Classes used to implement the filtered speed parameter Boolean filteredSpeed=true "= true, if speed is filtered with a 2nd order CriticalDamping filter"; parameter Modelica.SIunits.Time riseTime=30 "Rise time of the filter (time to reach 99.6 % of the speed)"; parameter Modelica.Blocks.Types.Init init=Modelica.Blocks.Types.Init.InitialOutput "Type of initialization (no init/steady state/initial state/initial output)"; parameter Modelica.SIunits.MassFlowRate m_flow_start(min=0)=0 "Initial value of mass flow rate";Modelica.Blocks.Interfaces.RealOutput m_flow_actual(final unit="kg/s", nominal=m_flow_nominal) "Actual mass flow rate"; protected Modelica.Blocks.Continuous.Filter filter( order=2, f_cut=5/(2*Modelica.Constants.pi*riseTime), final init=init, final y_start=m_flow_start, u_nominal=m_flow_nominal, x(each stateSelect=StateSelect.always), u(final unit="kg/s"), y(final unit="kg/s"), final analogFilter=Modelica.Blocks.Types.AnalogFilter.CriticalDamping, final filterType=Modelica.Blocks.Types.FilterType.LowPass) if filteredSpeed "Second order filter to approximate transient of rotor, and to improve numerics"; Modelica.Blocks.Interfaces.RealOutput m_flow_filtered(final unit="kg/s") if filteredSpeed "Filtered mass flow rate"; equation if filteredSpeed thenconnect(m_flow_in, filter.u); connect(filter.y, m_flow_actual); elseconnect(m_flow_in, m_flow_actual); end if;connect(filter.y, m_flow_filtered); connect(m_flow_actual, preSou.m_flow_in); end FlowMachine_m_flow;
This is a model of a flow machine (pump or fan).
The normalized pressure difference is computed using a function of the normalized mass flow rate. The function is a polynomial for which a user needs to supply the coefficients and two values that determine for what flow rate the polynomial is linearly extended.
Note: This model is here for compatibility with older versions of this library. For new models, use instead Buildings.Fluid.Movers.FlowMachine_y.
Extends from Buildings.Fluid.Interfaces.PartialTwoPortInterface (Partial model transporting fluid between two ports without storing mass or energy), Modelica.Icons.ObsoleteModel (Icon for classes that are obsolete and will be removed in later versions).
Type | Name | Default | Description |
---|---|---|---|
replaceable package Medium | PartialMedium | Medium in the component | |
Length | D | Diameter [m] | |
Real | a[:] | Polynomial coefficients for pressure=p(mNor_flow) | |
Real | b[:] | Polynomial coefficients for etaSha=p(mNor_flow) | |
Real | mNorMin_flow | Lowest valid normalized mass flow rate | |
Real | mNorMax_flow | Highest valid normalized mass flow rate | |
Real | scaM_flow | 1 | Factor used to scale the mass flow rate of the fan (used for quickly adjusting fan size) |
Real | scaDp | 1 | Factor used to scale the pressure increase of the fan (used for quickly adjusting fan size) |
Nominal condition | |||
MassFlowRate | m_flow_nominal | Nominal mass flow rate [kg/s] | |
Initialization | |||
MassFlowRate | m_flow.start | 0 | Mass flow rate from port_a to port_b (m_flow > 0 is design flow direction) [kg/s] |
Pressure | dp.start | 0 | Pressure difference between port_a and port_b [Pa] |
Assumptions | |||
Boolean | allowFlowReversal | system.allowFlowReversal | = true to allow flow reversal, false restricts to design direction (port_a -> port_b) |
Advanced | |||
MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
Boolean | homotopyInitialization | true | = true, use homotopy method |
Diagnostics | |||
Boolean | show_V_flow | false | = true, if volume flow rate at inflowing port is computed |
Boolean | show_T | false | = true, if actual temperature at port is computed (may lead to events) |
Type | Name | Description |
---|---|---|
FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
input RealInput | N_in | Prescribed rotational speed |
model FlowMachinePolynomial "Fan or pump with head and efficiency declared by a non-dimensional polynomial" extends Buildings.Fluid.Interfaces.PartialTwoPortInterface; extends Modelica.Icons.ObsoleteModel;Modelica.Blocks.Interfaces.RealInput N_in "Prescribed rotational speed"; parameter Modelica.SIunits.Length D "Diameter"; parameter Real[:] a "Polynomial coefficients for pressure=p(mNor_flow)"; parameter Real[:] b "Polynomial coefficients for etaSha=p(mNor_flow)"; parameter Real mNorMin_flow "Lowest valid normalized mass flow rate"; parameter Real mNorMax_flow "Highest valid normalized mass flow rate"; parameter Real scaM_flow = 1 "Factor used to scale the mass flow rate of the fan (used for quickly adjusting fan size)"; parameter Real scaDp = 1 "Factor used to scale the pressure increase of the fan (used for quickly adjusting fan size)"; Real pNor(min=0) "Normalized pressure"; Real mNor_flow(start=mNorMax_flow) "Normalized mass flow rate"; Real etaSha(min=0, max=1) "Efficiency, flow work divided by shaft power"; Modelica.SIunits.Power PSha "Power input at shaft"; Medium.Density rho "Medium density"; protected parameter Real pNorMin1(fixed=false) "Normalized pressure, used to test slope of polynomial outside [xMin, xMax]"; parameter Real pNorMin2(fixed=false) "Normalized pressure, used to test slope of polynomial outside [xMin, xMax]"; parameter Real pNorMax1(fixed=false) "Normalized pressure, used to test slope of polynomial outside [xMin, xMax]"; parameter Real pNorMax2(fixed=false) "Normalized pressure, used to test slope of polynomial outside [xMin, xMax]"; initial equation Modelica.Utilities.Streams.print("The model Buildings.Fluid.Movers.FlowMachinePolynomial is deprecated. It will be removed in future releases. You should use Buildings.Fluid.Movers.FlowMachine_y instead of Buildings.Fluid.Movers.FlowMachinePolynomial."); // check slope of polynomial outside the domain [mNorMin_flow, mNorMax_flow] pNorMin1 = Buildings.Fluid.Utilities.extendedPolynomial( c=a, x=mNorMin_flow/2, xMin=mNorMin_flow, xMax=mNorMax_flow); pNorMin2 = Buildings.Fluid.Utilities.extendedPolynomial( c=a, x=mNorMin_flow, xMin=mNorMin_flow, xMax=mNorMax_flow); pNorMax1 = Buildings.Fluid.Utilities.extendedPolynomial( c=a, x=mNorMax_flow, xMin=mNorMin_flow, xMax=mNorMax_flow); pNorMax2 = Buildings.Fluid.Utilities.extendedPolynomial( c=a, x=mNorMax_flow*2, xMin=mNorMin_flow, xMax=mNorMax_flow); assert(pNorMin1>pNorMin2, "Slope of pump pressure polynomial is non-negative for mNor_flow < mNorMin_flow. Check parameter a."); assert(pNorMax1>pNorMax2, "Slope of pump pressure polynomial is non-negative for mNorMax_flow < mNor_flow. Check parameter a."); equation // For computing the density, we assume that the fan operates in the design flow direction. rho = Medium.density( Medium.setState_phX(port_a.p, inStream(port_a.h_outflow), inStream(port_a.Xi_outflow))); -dp = scaDp * pNor * rho * D*D * N_in * N_in; m_flow = scaM_flow * mNor_flow * rho * D*D*D * N_in; pNor = Buildings.Fluid.Utilities.extendedPolynomial( c=a, x=mNor_flow, xMin=mNorMin_flow, xMax=mNorMax_flow); etaSha = max(0.1, Buildings.Fluid.Utilities.polynomial( c=b, x=mNor_flow)); etaSha * PSha = -dp * m_flow / rho; // dp<0 and m_flow>0 for normal operation // Energy balance (no storage, no heat loss/gain) PSha = -m_flow*(port_a.h_outflow-inStream(port_b.h_outflow)); PSha = m_flow*(port_b.h_outflow-inStream(port_a.h_outflow)); // Mass balance (no storage) port_a.m_flow + port_b.m_flow = 0; // Transport of substances port_a.Xi_outflow = inStream(port_b.Xi_outflow); port_b.Xi_outflow = inStream(port_a.Xi_outflow); port_a.C_outflow = inStream(port_b.C_outflow); port_b.C_outflow = inStream(port_a.C_outflow);end FlowMachinePolynomial;