LBL logo

Buildings.Examples.ChillerPlant.BaseClasses.Controls

Package with control components for Buildings.Examples.ChillerPlant

Information

This package contains component models that are used to construct the control system in Buildings.Examples.ChillerPlant.

Extends from Modelica.Icons.VariantsPackage (Icon for package containing variants).

Package Content

NameDescription
Buildings.Examples.ChillerPlant.BaseClasses.Controls.ChillerSwitch ChillerSwitch Control unit for enabling/disabling chiller
Buildings.Examples.ChillerPlant.BaseClasses.Controls.KMinusU KMinusU Output y=k-u
Buildings.Examples.ChillerPlant.BaseClasses.Controls.LinearPiecewiseTwo LinearPiecewiseTwo A two-pieces linear piecewise function
Buildings.Examples.ChillerPlant.BaseClasses.Controls.RequestCounter RequestCounter Count the number of actuators that have request
Buildings.Examples.ChillerPlant.BaseClasses.Controls.TrimAndRespond TrimAndRespond Trim and respond logic
Buildings.Examples.ChillerPlant.BaseClasses.Controls.WSEControl WSEControl Control unit for WSE
Buildings.Examples.ChillerPlant.BaseClasses.Controls.ZeroOrderHold ZeroOrderHold Zero order hold for boolean variable
Buildings.Examples.ChillerPlant.BaseClasses.Controls.Examples Examples Test of components


Buildings.Examples.ChillerPlant.BaseClasses.Controls.ChillerSwitch Buildings.Examples.ChillerPlant.BaseClasses.Controls.ChillerSwitch

Control unit for enabling/disabling chiller

Buildings.Examples.ChillerPlant.BaseClasses.Controls.ChillerSwitch

Information

The controls for enabling/disabling chiller are as follows: where TChi_CHWST is chiller chilled water supply temperature, TChiSet is set temperature for chilled water leaving chiller, and TDeaBan is dead band to prevent short cycling.

Extends from Modelica.Blocks.Interfaces.BlockIcon (Basic graphical layout of input/output block).

Parameters

TypeNameDefaultDescription
TemperaturedeaBan Dead band of temperature to prevent chiller short cycling [K]

Connectors

TypeNameDescription
input RealInputchiCHWSTChiller chilled water supply temperature (water entering chiller) [K]
output BooleanOutputyControl signal for chiller. 1: Enable, 0: Disable
input RealInputTSetSet temperature of chiller [K]

Modelica definition

block ChillerSwitch "Control unit for enabling/disabling chiller"
  extends Modelica.Blocks.Interfaces.BlockIcon;
  Modelica.Blocks.Interfaces.RealInput chiCHWST(
    final quantity="Temperature",
    final unit="K",
    displayUnit="deg") 
    "Chiller chilled water supply temperature (water entering chiller)";
  Modelica.Blocks.Interfaces.BooleanOutput y 
    "Control signal for chiller. 1: Enable, 0: Disable";
  Modelica.Blocks.Interfaces.RealInput TSet(
    final quantity="Temperature",
    final unit="K",
    displayUnit="deg") "Set temperature of chiller";
  parameter Modelica.SIunits.Temperature deaBan 
    "Dead band of temperature to prevent chiller short cycling";
  Modelica.Blocks.Logical.Hysteresis hysteresis(uLow=0, uHigh=deaBan);
  Modelica.Blocks.Math.Add add(k1=+1, k2=-1);
equation 
  connect(hysteresis.y, y);

  connect(chiCHWST, add.u1);
  connect(TSet, add.u2);
  connect(add.y, hysteresis.u);

end ChillerSwitch;

Buildings.Examples.ChillerPlant.BaseClasses.Controls.KMinusU Buildings.Examples.ChillerPlant.BaseClasses.Controls.KMinusU

Output y=k-u

Buildings.Examples.ChillerPlant.BaseClasses.Controls.KMinusU

Information

This component computes the value of

y = k - u.

Extends from Modelica.Blocks.Interfaces.BlockIcon (Basic graphical layout of input/output block).

Parameters

TypeNameDefaultDescription
Realk Sum of u and y

Connectors

TypeNameDescription
input RealInputuInput
output RealOutputyOutput

Modelica definition

block KMinusU "Output y=k-u"
  extends Modelica.Blocks.Interfaces.BlockIcon;
public 
  parameter Real k "Sum of u and y";
  Modelica.Blocks.Interfaces.RealInput u "Input";
  Modelica.Blocks.Interfaces.RealOutput y "Output";
equation 
  y = k - u;
end KMinusU;

Buildings.Examples.ChillerPlant.BaseClasses.Controls.LinearPiecewiseTwo Buildings.Examples.ChillerPlant.BaseClasses.Controls.LinearPiecewiseTwo

A two-pieces linear piecewise function

Buildings.Examples.ChillerPlant.BaseClasses.Controls.LinearPiecewiseTwo

Information

This component calcuates the output according to two piecewise linear function as

u ∈ [x0, x1]: y1 = y10 + u (y11-y10)/(x1-x0)
y2 = y20
u ∈ (x1, x2]: y1 = y11
y2 = y20 + (u-x1) (y21-y20)/(x2-x1)

Extends from Modelica.Blocks.Interfaces.BlockIcon (Basic graphical layout of input/output block).

Parameters

TypeNameDefaultDescription
Realx0 First interval [x0, x1]
Realx1 First interval [x0, x1] and second interval (x1, x2]
Realx2 Second interval (x1, x2]
Realy10 y[1] at u = x0
Realy11 y[1] at u = x1
Realy20 y[2] at u = x1
Realy21 y[2] at u = x2

Connectors

TypeNameDescription
input RealInputuSet point
output RealOutputy[2]Connectors of Real output signal

Modelica definition

block LinearPiecewiseTwo "A two-pieces linear piecewise function"
  extends Modelica.Blocks.Interfaces.BlockIcon;
  parameter Real x0 "First interval [x0, x1]";
  parameter Real x1 "First interval [x0, x1] and second interval (x1, x2]";
  parameter Real x2 "Second interval (x1, x2]";
  parameter Real y10 "y[1] at u = x0";
  parameter Real y11 "y[1] at u = x1";
  parameter Real y20 "y[2] at u = x1";
  parameter Real y21 "y[2] at u = x2";
  Modelica.Blocks.Interfaces.RealInput u "Set point";
  Modelica.Blocks.Interfaces.RealOutput y[2] "Connectors of Real output signal";
  Buildings.Controls.SetPoints.Table y1Tab(table=[x0, y10; x1, y11; x2, y11]) 
    "Tabel for y[1]";
  Buildings.Controls.SetPoints.Table y2Tab(table=[x0, y20; x1, y20; x2, y21]) 
    "Tabel for y[2]";
equation 
  connect(u, y1Tab.u);
  connect(u, y2Tab.u);
  connect(y1Tab.y, y[1]);
  connect(y2Tab.y, y[2]);
end LinearPiecewiseTwo;

Buildings.Examples.ChillerPlant.BaseClasses.Controls.RequestCounter Buildings.Examples.ChillerPlant.BaseClasses.Controls.RequestCounter

Count the number of actuators that have request

Buildings.Examples.ChillerPlant.BaseClasses.Controls.RequestCounter

Information

This model counts the number of requests sent by actuators. A request is triggerred when an input singal uAct[i] is larger than uTri.

Extends from Modelica.Blocks.Interfaces.BlockIcon (Basic graphical layout of input/output block).

Parameters

TypeNameDefaultDescription
IntegernAct Number of actuators
RealuTri Value to trigger a request from actuator

Connectors

TypeNameDescription
output IntegerOutputnIncNumber of actuators requesting control signal increase
input RealInputuAct[nAct]Input signal from actuators

Modelica definition

block RequestCounter 
  "Count the number of actuators that have request"
  extends Modelica.Blocks.Interfaces.BlockIcon;
  parameter Integer nAct "Number of actuators";
  parameter Real uTri "Value to trigger a request from actuator";
  Modelica.Blocks.Interfaces.IntegerOutput nInc 
    "Number of actuators requesting control signal increase";
  Modelica.Blocks.Interfaces.RealInput uAct[nAct] "Input signal from actuators";
algorithm 
  nInc := 0;
  for i in 1:nAct loop
    if uAct[i] > uTri then
      nInc := nInc + 1;
    end if;
  end for;
end RequestCounter;

Buildings.Examples.ChillerPlant.BaseClasses.Controls.TrimAndRespond Buildings.Examples.ChillerPlant.BaseClasses.Controls.TrimAndRespond

Trim and respond logic

Buildings.Examples.ChillerPlant.BaseClasses.Controls.TrimAndRespond

Information

This model implements the trim and respond logic. The model samples the outputs of actuators every tSam. The control sequence is as follows:

Extends from Modelica.Blocks.Interfaces.DiscreteBlockIcon (Graphical layout of discrete block component icon).

Parameters

TypeNameDefaultDescription
Integern Number of input singals
RealuTri Value to triggering the request for actuator
RealyEqu0 y setpoint when equipment starts
RealyMax Upper limit for y
RealyMin Lower limit for y
RealyDec y decrement (must be negative)
RealyInc y increment (must be positive)
IntegernActDec Number of actuators that can violate setpoints and y is still decreased
IntegernActInc Number of actuators requests needed to increase y
TimetSam Sample period of component [s]

Connectors

TypeNameDescription
input RealInputu[n]Input singal
output RealOutputyConnector of Real output signal
input BooleanInputstaStatus indicator, true if equipment is on

Modelica definition

block TrimAndRespond "Trim and respond logic"
  extends Modelica.Blocks.Interfaces.DiscreteBlockIcon;
  parameter Integer n "Number of input singals";
  parameter Real uTri "Value to triggering the request for actuator";
  parameter Real yEqu0 "y setpoint when equipment starts";
  parameter Real yMax "Upper limit for y";
  parameter Real yMin "Lower limit for y";
  parameter Real yDec "y decrement (must be negative)";
  parameter Real yInc "y increment (must be positive)";
  parameter Integer nActDec 
    "Number of actuators that can violate setpoints and y is still decreased";
  parameter Integer nActInc "Number of actuators requests needed to increase y";
  Modelica.Blocks.Interfaces.RealInput u[n] "Input singal";
  Modelica.Blocks.Logical.GreaterThreshold incY(threshold=nActInc - 0.5) 
    "Outputs true if y needs to be increased";
  Modelica.Blocks.Logical.Switch swi;
  Modelica.Blocks.Discrete.Sampler sam(samplePeriod=tSam) "Sampler";
  parameter Modelica.SIunits.Time tSam "Sample period of component";
  Modelica.Blocks.Sources.Constant conYDec(k=yDec) "y decrease";
  Modelica.Blocks.Math.IntegerToReal intToRea "Convert Integer to Real";
  Modelica.Blocks.Sources.Constant conYInc(k=yInc) "y increase";
  Modelica.Blocks.Discrete.UnitDelay uniDel1(
    samplePeriod=tSam,
    startTime=tSam,
    y_start=yEqu0);
  Modelica.Blocks.Math.Add add;
  Modelica.Blocks.Nonlinear.Limiter lim(uMax=yMax, uMin=yMin) "State limiter";
  Modelica.Blocks.Logical.Switch onSetPoi 
    "Set point selecter when equipment switches on";
  Modelica.Blocks.Sources.Constant equSta(k=yEqu0) "equipment start signal";
  Modelica.Blocks.Interfaces.RealOutput y "Connector of Real output signal";
  Modelica.Blocks.Logical.LessThreshold decY(threshold=nActDec + 0.5) 
    "Outputs true if y needs to be decreased";
  Modelica.Blocks.Logical.Switch swi1;
  Modelica.Blocks.Sources.Constant zer1(k=0) "Set point when equipment is off";
  Modelica.Blocks.Interfaces.BooleanInput sta 
    "Status indicator, true if equipment is on";
  ZeroOrderHold zerOrdHol(samplePeriod=tSam) "Zero order hold";
  Buildings.Examples.ChillerPlant.BaseClasses.Controls.RequestCounter req(uTri=
        uTri, nAct=n) "Count the number of request";
equation 
  connect(incY.y, swi.u2);
  connect(sam.y, incY.u);
  connect(uniDel1.y, add.u2);
  connect(add.y, lim.u);
  connect(onSetPoi.y, y);
  connect(zer1.y, swi1.u3);
  connect(swi1.y, swi.u3);
  connect(onSetPoi.y, uniDel1.u);
  connect(sta, zerOrdHol.u);
  connect(req.nInc, intToRea.u);
  connect(intToRea.y, sam.u);
  connect(conYInc.y, swi.u1);
  connect(sam.y, decY.u);
  connect(decY.y, swi1.u2);
  connect(conYDec.y, swi1.u1);
  connect(u, req.uAct);
  connect(equSta.y, onSetPoi.u3);
  connect(lim.y, onSetPoi.u1);
  connect(onSetPoi.u2, zerOrdHol.y);
  connect(swi.y, add.u1);
end TrimAndRespond;

Buildings.Examples.ChillerPlant.BaseClasses.Controls.WSEControl Buildings.Examples.ChillerPlant.BaseClasses.Controls.WSEControl

Control unit for WSE

Buildings.Examples.ChillerPlant.BaseClasses.Controls.WSEControl

Information

This component decides if the WSE is set to on or off. The WSE is enabled when

  1. The WSE has been disabled for at least 20 minutes, and
  2. TWSE_CHWST > 0.9 TWetBul + TTowApp + TWSEApp

The WSE is disabled when
  1. The WSE has been enabled for at least 20 minutes, and
  2. TWSE_CHWRT < 1 + TWSE_CWST

where TWSE_CHWST is the chilled water supply temperature for the WSE, TWetBul is the wet bulb temperature, TTowApp is the cooling tower approach, TWSEApp is the approach for the WSE, TWSE_CHWRT is the chilled water return temperature for the WSE, and TWSE_CWST is the condenser water return temperature for the WSE.

Connectors

TypeNameDescription
input RealInputwseCHWSTWSE's chilled water supply temperature (water entering WSE) [K]
output RealOutputy2Control signal for valve in CHW loop of WSE
input RealInputTWetBulWet bulb temperature [K]
input RealInputtowTAppcooling tower approach [K]
input RealInputwseCWSTWSE's condenser water supply temperature (water entering WSE) [K]
output RealOutputy1Control signal for valve in the CW loop of WSE

Modelica definition

block WSEControl "Control unit for WSE"

  Modelica.Blocks.Interfaces.RealInput wseCHWST(
    final quantity="Temperature",
    final unit="K",
    displayUnit="deg") 
    "WSE's chilled water supply temperature (water entering WSE)";
  Modelica.Blocks.Interfaces.RealOutput y2 
    "Control signal for valve in CHW loop of WSE";
  Modelica.Blocks.Sources.Constant TWSEApp(k=1) "Approach for WSE";
  Modelica.Blocks.Math.Sum sum(nin=3);
  Modelica.Blocks.Logical.Greater greater;
  Modelica.Blocks.Logical.And andOpe;
  Buildings.Controls.Continuous.OffTimer offTim;
  Modelica.Blocks.Sources.Constant minDisTim(k=1200) 
    "minium Disabled time for WSE";
  Modelica.Blocks.Logical.Less less;
  Modelica.Blocks.Interfaces.RealInput TWetBul(
    final quantity="Temperature",
    final unit="K",
    displayUnit="deg") "Wet bulb temperature";
  Modelica.Blocks.Interfaces.RealInput towTApp(
    final quantity="Temperature",
    final unit="K",
    displayUnit="deg") "cooling tower approach";
  Modelica.Blocks.Math.Product pro;
  Modelica.Blocks.Sources.Constant cons(k=0.9);
  Modelica.Blocks.Interfaces.RealInput wseCWST(
    final quantity="Temperature",
    final unit="K",
    displayUnit="deg") 
    "WSE's condenser water supply temperature (water entering WSE)";
  Modelica.Blocks.Logical.Greater less1;
  Modelica.Blocks.Sources.Constant cons1(k=1) "cons";
  Modelica.Blocks.Sources.Constant minEnaTim(k=1200) 
    "minium enabled time for heat exchanger";
  Buildings.Controls.Continuous.OffTimer onTim;
  Modelica.Blocks.Logical.Greater less2;
  Modelica.Blocks.Logical.And dis "true for disable";
  Modelica.Blocks.Math.Add add1(k1=+1);
  Modelica.Blocks.Logical.Not not3;
  Modelica.Blocks.Logical.And and2;
  Modelica.Blocks.Math.BooleanToReal booToRea;
  Modelica.Blocks.Logical.Not not1;
  Modelica.Blocks.Interfaces.RealOutput y1 
    "Control signal for valve in the CW loop of WSE";
  KMinusU kMinU(k=1);
  Modelica.Blocks.Logical.Pre pre1;
equation 
  connect(sum.y, greater.u2);
  connect(greater.y, andOpe.u1);
  connect(minDisTim.y, less.u1);
  connect(offTim.y, less.u2);
  connect(less.y, andOpe.u2);
  connect(TWSEApp.y, sum.u[1]);
  connect(pro.y, sum.u[2]);
  connect(cons.y, pro.u1);
  connect(cons1.y, add1.u1);
  connect(less1.y, dis.u2);
  connect(less2.y, dis.u1);
  connect(minEnaTim.y, less2.u2);
  connect(onTim.y, less2.u1);
  connect(not3.y, offTim.u);
  connect(dis.y, and2.u1);
  connect(andOpe.y, not1.u);
  connect(not1.y, and2.u2);

  connect(kMinU.y, y1);
  connect(and2.y, pre1.u);
  connect(pre1.y, booToRea.u);
  connect(pre1.y, onTim.u);
  connect(pre1.y, not3.u);
  connect(booToRea.y, kMinU.u);
  connect(booToRea.y, y2);
  connect(TWetBul, pro.u2);
  connect(wseCHWST, greater.u1);
  connect(wseCWST, add1.u2);
  connect(add1.y, less1.u1);
  connect(wseCHWST, less1.u2);
  connect(towTApp, sum.u[3]);
end WSEControl;

Buildings.Examples.ChillerPlant.BaseClasses.Controls.ZeroOrderHold Buildings.Examples.ChillerPlant.BaseClasses.Controls.ZeroOrderHold

Zero order hold for boolean variable

Buildings.Examples.ChillerPlant.BaseClasses.Controls.ZeroOrderHold

Information

This model outputs the same value as the input for a given time of period.

Extends from Modelica.Blocks.Interfaces.BooleanSISO (Single Input Single Output control block with signals of type Boolean), Modelica.Blocks.Interfaces.DiscreteBlock (Base class of discrete control blocks).

Parameters

TypeNameDefaultDescription
TimesamplePeriod Sample period of component [s]
TimestartTime0First sample time instant [s]

Connectors

TypeNameDescription
input BooleanInputuConnector of Boolean input signal
output BooleanOutputyConnector of Boolean output signal

Modelica definition

block ZeroOrderHold "Zero order hold for boolean variable"
  extends Modelica.Blocks.Interfaces.BooleanSISO;
  extends Modelica.Blocks.Interfaces.DiscreteBlock;
protected 
  Boolean ySample;
algorithm 
  when {sampleTrigger,initial()} then
    y := ySample;
    ySample := u;
  end when;
end ZeroOrderHold;

Automatically generated Thu Jul 26 10:24:45 2012.