Buildings.Fluid.DataCenters.Racks.Hybrid.BaseClasses
Package with base classes for Buildings.Fluid.DataCenters.Racks.Hybrid
Information
This package contains base classes that are used to construct the models in Buildings.Fluid.DataCenters.Racks.Hybrid.
Extends from Modelica.Icons.BasesPackage (Icon for packages containing base classes).
Package Content
| Name | Description |
|---|---|
| Partial rack model for air-cooled components | |
| Partial hybrid rack model combining liquid-cooled and air-cooled components | |
| Partial model for hybrid rack combining liquid-cooled and air-cooled components with a rear door heat exchanger | |
| Partial model for air-cooled rack with a rear door heat exchanger |
Buildings.Fluid.DataCenters.Racks.Hybrid.BaseClasses.Air
Partial rack model for air-cooled components
Information
This is a partial model of an IT rack with air-cooled components. The air cooling component with integrated fans is based on Buildings.Fluid.DataCenters.Racks.Air.Rack_P.
The model has fluid ports for the air cooling loop.
For air cooling, portAir_a and portAir_b serve as the inlet and outlet ports.
The input PAir specifies the power consumption for the air-cooled IT equipment.
Note that PAir does not include the power to operate the fan, as this is an output of the model.
The model provides two power consumption outputs.
The output PAirTot is the total electric power consumed by air-cooled IT, including fan energy.
The output PAirFan is the electric power consumed by the fan for air-cooled IT.
This is a partial model because it does not connect the outlet port air.port_b
of the air-cooled component to the model output portAir_b.
This connection must be made by the model that extends this partial model.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Modelica.Media.Interfaces.Pa... | Medium for air cooling loop | |
| Performance data | |||
| Generic | dat | redeclare parameter Building... | Performance data |
| Fan controller | |||
| Strategy | fanControl | Buildings.Fluid.DataCenters.... | Type of fan control strategy |
| Real | fanSpeed[:, :] | [0.0, 0.0; 1.0, 1.0] | Load and fan speed matrix (1st column normalized IT load, 2nd fan speed), e.g., fanSpeed=[0, 0; 0.5, 0.7; 1, 1]) |
| Temperature | TAirOut_set | dat.air.TOut_nominal | Set point temperature for rack outlet air [K] |
| Real | k | 1 | Gain of fan PI controller |
| Time | Ti | 60 | Integrator time constant of fan PI controller [s] |
| Dynamics | |||
| Air cooling | |||
| Dynamics | energyDynamicsAir | Modelica.Fluid.Types.Dynamic... | Type of energy balance for air-cooled component: dynamic (3 initialization options) or steady state |
| Time | tauAir | 2 | Time constant of air outlet temperature at nominal flow [s] |
| Initialization | |||
| Air cooling | |||
| Temperature | TAir_start | 293.15 | Start value of air temperature [K] |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal |
Connectors
| Type | Name | Description |
|---|---|---|
| replaceable package MediumAir | Medium for air cooling loop | |
| FluidPort_a | portAir_a | Air cooling inlet port |
| FluidPort_b | portAir_b | Air cooling outlet port |
| input RealInput | PAir | Power consumed by air-cooled IT [W] |
| output RealOutput | PAirTot | Electric power consumed by air-cooled IT, including fan energy [W] |
| output RealOutput | PAirFan | Electric power consumed by fan for air-cooled IT [W] |
Modelica definition
Buildings.Fluid.DataCenters.Racks.Hybrid.BaseClasses.AirLiquid
Partial hybrid rack model combining liquid-cooled and air-cooled components
Information
This is a partial model of a hybrid IT rack that combines liquid-cooled and air-cooled components. This model integrates two separate cooling technologies in a single rack. The liquid cooling component uses cold plates and is based on Buildings.Fluid.DataCenters.Racks.Liquid.ColdPlateR_P, while the air cooling component with integrated fans is based on Buildings.Fluid.DataCenters.Racks.Air.Rack_P.
The model has separate fluid ports for each cooling loop.
For liquid cooling, portLiq_a and portLiq_b serve as the inlet and outlet ports.
For air cooling, portAir_a and portAir_b serve as the inlet and outlet ports.
Each cooling system has its own input for the electrical power consumption by the IT equipment.
The input PLiq specifies the power consumption for the liquid-cooled IT equipment,
and the input PAir specifies the power consumption for the air-cooled IT equipment.
Note that PAir does not include the power to operate the fan, as this is an output of the model.
The model provides three power consumption outputs on the right side.
The output PLiqTot is the electric power consumed by liquid-cooled IT.
The output PAirTot is the total electric power consumed by air-cooled IT, including fan energy.
The output PAirFan is the electric power consumed by the fan for air-cooled IT.
This is a partial model because it does not connect the outlet port air.port_b
of the air-cooled component to the model output portAir_b.
This connection must be made by the model that extends this partial model.
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumLiq | Modelica.Media.Interfaces.Pa... | Medium for liquid cooling loop | |
| replaceable package MediumAir | Modelica.Media.Interfaces.Pa... | Medium for air cooling loop | |
| Performance data | |||
| Generic | dat | redeclare parameter Building... | Performance data |
| Liquid cooling | |||
| VolumeFlowRate | VColPla_flow_nominal | sum(dat.liq.theRes.V_flow)/s... | Design flow rate of one cold plate for liquid cooling [m3/s] |
| Real | nColPla | dat.liq.PIT_nominal/(VColPla... | Number of cold plates for liquid cooling |
| Fan controller | |||
| Strategy | fanControl | Buildings.Fluid.DataCenters.... | Type of fan control strategy |
| Real | fanSpeed[:, :] | [0.0, 0.0; 1.0, 1.0] | Load and fan speed matrix (1st column normalized IT load, 2nd fan speed), e.g., fanSpeed=[0, 0; 0.5, 0.7; 1, 1]) |
| Temperature | TAirOut_set | dat.air.TOut_nominal | Set point temperature for rack outlet air [K] |
| Real | k | 1 | Gain of fan PI controller |
| Time | Ti | 60 | Integrator time constant of fan PI controller [s] |
| Dynamics | |||
| Liquid cooling | |||
| Dynamics | energyDynamicsLiq | Modelica.Fluid.Types.Dynamic... | Type of energy balance for liquid-cooled component: dynamic (3 initialization options) or steady state |
| Time | tauLiq | 2 | Time constant of liquid outlet temperature at nominal flow [s] |
| Air cooling | |||
| Dynamics | energyDynamicsAir | Modelica.Fluid.Types.Dynamic... | Type of energy balance for air-cooled component: dynamic (3 initialization options) or steady state |
| Time | tauAir | 2 | Time constant of air outlet temperature at nominal flow [s] |
| Initialization | |||
| Liquid cooling | |||
| Temperature | TLiq_start | 293.15 | Start value of liquid temperature [K] |
| Air cooling | |||
| Temperature | TAir_start | 293.15 | Start value of air temperature [K] |
| Advanced | |||
| Liquid cooling | |||
| Boolean | linearizedLiq | false | = true, use linear relation between m_flow and dp for liquid cooling |
| Assumptions | |||
| Boolean | allowFlowReversalAir | true | = false to simplify equations, assuming, but not enforcing, no flow reversal for air loop |
| Boolean | allowFlowReversalLiq | true | = false to simplify equations, assuming, but not enforcing, no flow reversal for liquid loop |
Connectors
| Type | Name | Description |
|---|---|---|
| replaceable package MediumLiq | Medium for liquid cooling loop | |
| replaceable package MediumAir | Medium for air cooling loop | |
| FluidPort_a | portLiq_a | Liquid cooling inlet port |
| FluidPort_b | portLiq_b | Liquid cooling outlet port |
| FluidPort_a | portAir_a | Air cooling inlet port |
| FluidPort_b | portAir_b | Air cooling outlet port |
| input RealInput | PLiq | Power consumed by for liquid-cooled IT [W] |
| input RealInput | PAir | Power consumed by air-cooled IT [W] |
| output RealOutput | PLiqTot | Electric power consumed by liquid-cooled IT [W] |
| output RealOutput | PAirTot | Electric power consumed by air-cooled IT, including fan energy [W] |
| output RealOutput | PAirFan | Electric power consumed by fan for air-cooled IT [W] |
Modelica definition
Buildings.Fluid.DataCenters.Racks.Hybrid.BaseClasses.PartialAirLiquidRearDoorHex
Partial model for hybrid rack combining liquid-cooled and air-cooled components with a rear door heat exchanger
Information
Partial model of a hybrid IT rack that combines liquid-cooled and air-cooled components with a rear door heat exchanger.
This model extends Buildings.Fluid.DataCenters.Racks.Hybrid.BaseClasses.AirLiquid and adds a partial model for a rear door heat exchanger.
Extends from Buildings.Fluid.DataCenters.Racks.Hybrid.BaseClasses.AirLiquid (Partial hybrid rack model combining liquid-cooled and air-cooled components).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumLiq | PartialMedium | Medium for liquid cooling loop | |
| replaceable package MediumAir | PartialMedium | Medium for air cooling loop | |
| replaceable package MediumReaDooHex | Modelica.Media.Interfaces.Pa... | Medium for rear door heat exchanger coolant loop | |
| PartialRearDoorHeatExchanger | reaDooHex | redeclare Buildings.Fluid.Da... | Rear door heat exchanger |
| Liquid cooling | |||
| VolumeFlowRate | VColPla_flow_nominal | sum(dat.liq.theRes.V_flow)/s... | Design flow rate of one cold plate for liquid cooling [m3/s] |
| Real | nColPla | dat.liq.PIT_nominal/(VColPla... | Number of cold plates for liquid cooling |
| Fan controller | |||
| Strategy | fanControl | Buildings.Fluid.DataCenters.... | Type of fan control strategy |
| Real | fanSpeed[:, :] | [0.0, 0.0; 1.0, 1.0] | Load and fan speed matrix (1st column normalized IT load, 2nd fan speed), e.g., fanSpeed=[0, 0; 0.5, 0.7; 1, 1]) |
| Temperature | TAirOut_set | dat.air.TOut_nominal | Set point temperature for rack outlet air [K] |
| Real | k | 1 | Gain of fan PI controller |
| Time | Ti | 60 | Integrator time constant of fan PI controller [s] |
| Dynamics | |||
| Liquid cooling | |||
| Dynamics | energyDynamicsLiq | Modelica.Fluid.Types.Dynamic... | Type of energy balance for liquid-cooled component: dynamic (3 initialization options) or steady state |
| Time | tauLiq | 2 | Time constant of liquid outlet temperature at nominal flow [s] |
| Air cooling | |||
| Dynamics | energyDynamicsAir | Modelica.Fluid.Types.Dynamic... | Type of energy balance for air-cooled component: dynamic (3 initialization options) or steady state |
| Time | tauAir | 2 | Time constant of air outlet temperature at nominal flow [s] |
| Initialization | |||
| Liquid cooling | |||
| Temperature | TLiq_start | 293.15 | Start value of liquid temperature [K] |
| Air cooling | |||
| Temperature | TAir_start | 293.15 | Start value of air temperature [K] |
| Advanced | |||
| Liquid cooling | |||
| Boolean | linearizedLiq | false | = true, use linear relation between m_flow and dp for liquid cooling |
| Assumptions | |||
| Boolean | allowFlowReversalAir | true | = false to simplify equations, assuming, but not enforcing, no flow reversal for air loop |
| Boolean | allowFlowReversalLiq | true | = false to simplify equations, assuming, but not enforcing, no flow reversal for liquid loop |
| Boolean | allowFlowReversalCoo | true | = false to simplify equations, assuming, but not enforcing, no flow reversal for rear door heat exchanger coolant |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | portLiq_a | Liquid cooling inlet port |
| FluidPort_b | portLiq_b | Liquid cooling outlet port |
| FluidPort_a | portAir_a | Air cooling inlet port |
| FluidPort_b | portAir_b | Air cooling outlet port |
| input RealInput | PLiq | Power consumed by for liquid-cooled IT [W] |
| input RealInput | PAir | Power consumed by air-cooled IT [W] |
| output RealOutput | PLiqTot | Electric power consumed by liquid-cooled IT [W] |
| output RealOutput | PAirTot | Electric power consumed by air-cooled IT, including fan energy [W] |
| output RealOutput | PAirFan | Electric power consumed by fan for air-cooled IT [W] |
| replaceable package MediumReaDooHex | Medium for rear door heat exchanger coolant loop | |
| FluidPort_a | portReaDooHex_a | Rear door heat exchanger coolant inlet port |
| FluidPort_b | portReaDooHex_b | Rear door heat exchanger coolant outlet port |
Modelica definition
Buildings.Fluid.DataCenters.Racks.Hybrid.BaseClasses.PartialAirRearDoorHex
Partial model for air-cooled rack with a rear door heat exchanger
Information
Partial model of an air-cooled IT rack with a rear door heat exchanger.
This model extends Buildings.Fluid.DataCenters.Racks.Hybrid.BaseClasses.Air and adds a partial model for a rear door heat exchanger.
Extends from Buildings.Fluid.DataCenters.Racks.Hybrid.BaseClasses.Air (Partial rack model for air-cooled components).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | PartialMedium | Medium for air cooling loop | |
| replaceable package MediumReaDooHex | Modelica.Media.Interfaces.Pa... | Medium for rear door heat exchanger coolant loop | |
| PartialRearDoorHeatExchanger | reaDooHex | redeclare Buildings.Fluid.Da... | Rear door heat exchanger |
| Fan controller | |||
| Strategy | fanControl | Buildings.Fluid.DataCenters.... | Type of fan control strategy |
| Real | fanSpeed[:, :] | [0.0, 0.0; 1.0, 1.0] | Load and fan speed matrix (1st column normalized IT load, 2nd fan speed), e.g., fanSpeed=[0, 0; 0.5, 0.7; 1, 1]) |
| Temperature | TAirOut_set | dat.air.TOut_nominal | Set point temperature for rack outlet air [K] |
| Real | k | 1 | Gain of fan PI controller |
| Time | Ti | 60 | Integrator time constant of fan PI controller [s] |
| Dynamics | |||
| Air cooling | |||
| Dynamics | energyDynamicsAir | Modelica.Fluid.Types.Dynamic... | Type of energy balance for air-cooled component: dynamic (3 initialization options) or steady state |
| Time | tauAir | 2 | Time constant of air outlet temperature at nominal flow [s] |
| Initialization | |||
| Air cooling | |||
| Temperature | TAir_start | 293.15 | Start value of air temperature [K] |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal |
| Boolean | allowFlowReversalCoo | true | = false to simplify equations, assuming, but not enforcing, no flow reversal for rear door heat exchanger coolant |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | portAir_a | Air cooling inlet port |
| FluidPort_b | portAir_b | Air cooling outlet port |
| input RealInput | PAir | Power consumed by air-cooled IT [W] |
| output RealOutput | PAirTot | Electric power consumed by air-cooled IT, including fan energy [W] |
| output RealOutput | PAirFan | Electric power consumed by fan for air-cooled IT [W] |
| replaceable package MediumReaDooHex | Medium for rear door heat exchanger coolant loop | |
| FluidPort_a | portReaDooHex_a | Rear door heat exchanger coolant inlet port |
| FluidPort_b | portReaDooHex_b | Rear door heat exchanger coolant outlet port |