Buildings.Applications.DataCenters.LiquidCooled.Validation
Collection of validation models
Information
This package contains validation models for the classes in Buildings.Applications.DataCenters.LiquidCooled.
Note that most validation models contain simple input data which may not be realistic, but for which the correct output can be obtained through an analytic solution. The examples plot various outputs, which have been verified against these solutions. These model outputs are stored as reference data and used for continuous validation whenever models in the library change.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
Package Content
| Name | Description |
|---|---|
| Validation model that tests the component configurations at design conditions | |
| Validation model that tests the component configurations at design conditions, using water in all fluid loops |
Buildings.Applications.DataCenters.LiquidCooled.Validation.ChillerWSEDesignConditionsGlycol
Validation model that tests the component configurations at design conditions
Information
Validation model that simulates Buildings.Applications.DataCenters.LiquidCooled.Examples.ChillerWSE at design conditions.
This model verifies the design conditions if the system is designed for full economizer use, and the IT utilization is 100%.
Extends from Buildings.Applications.DataCenters.LiquidCooled.Examples.ChillerWSE (Example model of a simple liquid-cooled data center with chiller and water-side economizer).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumTow | Buildings.Media.Antifreeze.P... | Medium for tower loop | |
| replaceable package MediumRac | Buildings.Media.Antifreeze.P... | Medium for rack | |
| Power | PRac | 1E6 | Total rack design power [W] |
| Real | fraWSE | 0.999999 | Fraction of peak load covered by water side economizer |
| Real | fraChi | 1 - fraWSE | Fraction of peak load covered by chiller |
| MassFlowRate | mRac_flow_nominal | PRac/(TRacRet_nominal - TRac... | Rack mass flow rate at design conditions [kg/s] |
| MassFlowRate | mPla_flow_nominal | PRac/(TPlaRet_nominal - TPla... | Cooling loop water mass flow rate at design conditions [kg/s] |
| PressureDifference | dpVal_nominal | 20000 | Valve design pressure drop [Pa] |
| PressureDifference | dpHexChi_nominal | 80000 | Heat exchanger design pressure drop on chiller side [Pa] |
| PressureDifference | dPRac_nominal | 60000 | Rack design pressure drop [Pa] |
| OCP_1kW_OAM_PG25 | datRac | Performance data for IT rack | |
| Real | COPc_nominal | 5 | Chiller COP |
| Real | epsWSE_nominal | QWSE_flow_nominal/(min(mWSEP... | Effectiveness of water side economizer |
| Generic_2MW | datCDU | Data record for CDU | |
| Generic | datCooTow | Performance data for cooling tower | |
| replaceable model Pipe | HydraulicDiameter | Pipe model | |
Connectors
| Type | Name | Description |
|---|---|---|
| Bus | weaBus | Weather data bus |
Modelica definition
Buildings.Applications.DataCenters.LiquidCooled.Validation.ChillerWSEDesignConditionsWater
Validation model that tests the component configurations at design conditions, using water in all fluid loops
Information
Validation model that simulates Buildings.Applications.DataCenters.LiquidCooled.Examples.ChillerWSE at design conditions. The model is identical to Buildings.Applications.DataCenters.LiquidCooled.Validation.ChillerWSEDesignConditionsGlycol except that the media is set to water.
This model verifies that the media conversions are implemented correctly.
Extends from Buildings.Applications.DataCenters.LiquidCooled.Validation.ChillerWSEDesignConditionsGlycol (Validation model that tests the component configurations at design conditions).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumTow | Buildings.Media.Water | Medium for tower loop | |
| replaceable package MediumRac | Buildings.Media.Water | Medium for rack | |
| Power | PRac | 1E6 | Total rack design power [W] |
| Real | fraWSE | 0.999999 | Fraction of peak load covered by water side economizer |
| Real | fraChi | 1 - fraWSE | Fraction of peak load covered by chiller |
| MassFlowRate | mRac_flow_nominal | PRac/(TRacRet_nominal - TRac... | Rack mass flow rate at design conditions [kg/s] |
| MassFlowRate | mPla_flow_nominal | PRac/(TPlaRet_nominal - TPla... | Cooling loop water mass flow rate at design conditions [kg/s] |
| PressureDifference | dpVal_nominal | 20000 | Valve design pressure drop [Pa] |
| PressureDifference | dpHexChi_nominal | 80000 | Heat exchanger design pressure drop on chiller side [Pa] |
| PressureDifference | dPRac_nominal | 60000 | Rack design pressure drop [Pa] |
| OCP_1kW_OAM_PG25 | datRac | Performance data for IT rack | |
| Real | COPc_nominal | 5 | Chiller COP |
| Real | epsWSE_nominal | QWSE_flow_nominal/(min(mWSEP... | Effectiveness of water side economizer |
| Generic | datCooTow | Performance data for cooling tower | |
| replaceable model Pipe | HydraulicDiameter | Pipe model | |
Connectors
| Type | Name | Description |
|---|---|---|
| replaceable package MediumTow | Medium for tower loop | |
| replaceable package MediumRac | Medium for rack | |
| Bus | weaBus | Weather data bus |