Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Trox
Performance data for Trox
Information
Package with performance data for active beams from Trox.
Package Content
Name | Description |
---|---|
DID632A_nozzleH_length6ft_cooling | Performance data for Trox DID 632A for cooling mode |
DID632A_nozzleH_length6ft_heating | Performance data for Trox DID 632A for heating mode |
Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_length6ft_cooling
Performance data for Trox DID 632A for cooling mode
Information
Performance data for Trox active beam for cooling mode.
Extends from Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Generic (Generic data record for active beam).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Nominal condition | |||
MassFlowRate | mAir_flow_nominal | 0.0792 | Nominal air mass flow rate per beam [kg/s] |
MassFlowRate | mWat_flow_nominal | 0.094 | Nominal water mass flow rate per beam [kg/s] |
PressureDifference | dpWat_nominal | 10000 | Water-side nominal pressure drop per beam [Pa] |
PressureDifference | dpAir_nominal | 100 | Air-side nominal pressure drop [Pa] |
TemperatureDifference | dT_nominal | -10 | Nominal temperature difference water inlet minus room air [K] |
HeatFlowRate | Q_flow_nominal | -1092 | Nominal capacity per beam [W] |
Modelica definition
record DID632A_nozzleH_length6ft_cooling = Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Generic
(
primaryAir(r_V={0,0.714286,1,1.2857}, f={0,0.823403,1,1.1256}),
dT(f={0,0.5,1}, r_dT={0,0.5,1}),
water(r_V={0,0.33333,0.5,0.666667,0.833333,1,1.333333}, f={0,0.71,0.85,0.92,
0.97,1,1.04}),
mAir_flow_nominal=0.0792,
mWat_flow_nominal=0.094,
dpWat_nominal=10000,
dpAir_nominal=100,
dT_nominal=-10,
Q_flow_nominal=-1092) "Performance data for Trox DID 632A for cooling mode";
Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Trox.DID632A_nozzleH_length6ft_heating
Performance data for Trox DID 632A for heating mode
Information
Performance data for Trox active beam for heating mode.
Extends from Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Generic (Generic data record for active beam).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Nominal condition | |||
MassFlowRate | mAir_flow_nominal | 0.0792 | Nominal air mass flow rate per beam [kg/s] |
MassFlowRate | mWat_flow_nominal | 0.094 | Nominal water mass flow rate per beam [kg/s] |
PressureDifference | dpWat_nominal | 10000 | Water-side nominal pressure drop per beam [Pa] |
PressureDifference | dpAir_nominal | 100 | Air-side nominal pressure drop [Pa] |
TemperatureDifference | dT_nominal | 27.8 | Nominal temperature difference water inlet minus room air [K] |
HeatFlowRate | Q_flow_nominal | 2832 | Nominal capacity per beam [W] |
Modelica definition
record DID632A_nozzleH_length6ft_heating = Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Generic
(
dT(f={0,0.5,1}, r_dT={0,0.5,1}),
primaryAir(r_V={0,0.714286,1,1.2857}, f={0,0.8554,1,1.0778}),
water(r_V={0,0.33333,0.5,0.666667,0.833333,1,1.333333}, f={0,0.71,0.85,0.92,
0.97,1,1.04}),
mAir_flow_nominal=0.0792,
mWat_flow_nominal=0.094,
dpWat_nominal=10000,
dpAir_nominal=100,
dT_nominal=27.8,
Q_flow_nominal=2832) "Performance data for Trox DID 632A for heating mode";