Performance data for chiller ElectricEIR
Package with performance data for chillers.
Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).
Name | Description |
---|---|
Generic | Generic data record for chiller ElectricEIR |
ElectricEIRChiller_McQuay_WSC_471kW_5_89COP_Vanes | ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes |
ElectricEIRChiller_York_YT_563kW_10_61COP_Vanes | ElectricEIRChiller York YT 563kW/10.61COP/Vanes |
ElectricEIRChiller_McQuay_PEH_703kW_7_03COP_Vanes | ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes |
ElectricEIRChiller_Carrier_23XL_724kW_6_04COP_Vanes | ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes |
ElectricEIRChiller_Carrier_19XR_742kW_5_42COP_VSD | ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD |
ElectricEIRChiller_McQuay_WSC_816kW_6_74COP_Vanes | ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes |
ElectricEIRChiller_McQuay_PEH_819kW_8_11COP_Vanes | ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes |
ElectricEIRChiller_Carrier_19XR_823kW_6_28COP_Vanes | ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes |
ElectricEIRChiller_Carrier_19XR_869kW_5_57COP_VSD | ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD |
ElectricEIRChiller_Carrier_19XR_897kW_7_23COP_VSD | ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD |
ElectricEIRChiller_Carrier_19XR_897kW_6_50COP_Vanes | ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes |
ElectricEIRChiller_York_YT_897kW_7_60COP_VSD | ElectricEIRChiller York YT 897kW/7.60COP/VSD |
ElectricEIRChiller_York_YT_897kW_6_27COP_VSD | ElectricEIRChiller York YT 897kW/6.27COP/VSD |
ElectricEIRChiller_Carrier_19XR_897kW_6_23COP_VSD | ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD |
ElectricEIRChiller_McQuay_PFH_932kW_5_09COP_Vanes | ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes |
ElectricEIRChiller_York_YT_960kW_4_64COP_Vanes | ElectricEIRChiller York YT 960kW/4.64COP/Vanes |
ElectricEIRChiller_York_YT_1023kW_5_81COP_Vanes | ElectricEIRChiller York YT 1023kW/5.81COP/Vanes |
ElectricEIRChiller_McQuay_PEH_1030kW_8_58COP_Vanes | ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes |
ElectricEIRChiller_York_YT_1048kW_6_06COP_Vanes | ElectricEIRChiller York YT 1048kW/6.06COP/Vanes |
ElectricEIRChiller_York_YT_1055kW_5_96COP_Vanes | ElectricEIRChiller York YT 1055kW/5.96COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1076kW_5_52COP_Vanes | ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes |
ElectricEIRChiller_Trane_CVHE_1080kW_7_39COP_Vanes | ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes |
ElectricEIRChiller_York_YT_1090kW_7_57COP_VSD | ElectricEIRChiller York YT 1090kW/7.57COP/VSD |
ElectricEIRChiller_McQuay_PEH_1104kW_8_00COP_Vanes | ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes |
ElectricEIRChiller_Trane_CVHE_1125kW_4_89COP_Vanes | ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes |
ElectricEIRChiller_York_YT_1125kW_7_92COP_VSD | ElectricEIRChiller York YT 1125kW/7.92COP/VSD |
ElectricEIRChiller_Trane_CVHE_1129kW_7_19COP_Vanes | ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1143kW_6_57COP_VSD | ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD |
ElectricEIRChiller_Carrier_19XR_1157kW_5_62COP_VSD | ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD |
ElectricEIRChiller_Carrier_19XR_1196kW_6_50COP_Vanes | ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1213kW_7_78COP_Vanes | ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes |
ElectricEIRChiller_McQuay_PEH_1231kW_6_18COP_Vanes | ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1234kW_5_39COP_VSD | ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD |
ElectricEIRChiller_Carrier_19XR_1259kW_6_26COP_Vanes | ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes |
ElectricEIRChiller_York_YK_1259kW_6_45COP_Vanes | ElectricEIRChiller York YK 1259kW/6.45COP/Vanes |
ElectricEIRChiller_York_YT_1266kW_4_39COP_Vanes | ElectricEIRChiller York YT 1266kW/4.39COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1284kW_6_20COP_Vanes | ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1294kW_7_61COP_Vanes | ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes |
ElectricEIRChiller_Trane_CVHE_1329kW_5_38COP_Vanes | ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1350kW_7_90COP_VSD | ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD |
ElectricEIRChiller_York_YT_1368kW_7_35COP_VSD | ElectricEIRChiller York YT 1368kW/7.35COP/VSD |
ElectricEIRChiller_Trane_CVHE_1372kW_7_49COP_Vanes | ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes |
ElectricEIRChiller_York_YT_1396kW_7_35COP_Vanes | ElectricEIRChiller York YT 1396kW/7.35COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1403kW_7_09COP_VSD | ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD |
ElectricEIRChiller_York_YT_1403kW_6_94COP_VSD | ElectricEIRChiller York YT 1403kW/6.94COP/VSD |
ElectricEIRChiller_Trane_CVHE_1407kW_7_14COP_VSD | ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD |
ElectricEIRChiller_McQuay_PFH_1407kW_6_60COP_Vanes | ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1407kW_6_04COP_VSD | ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD |
ElectricEIRChiller_Carrier_19XR_1410kW_8_54COP_VSD | ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD |
ElectricEIRChiller_Trane_CVHE_1442kW_6_61COP_VSD | ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD |
ElectricEIRChiller_York_YT_1459kW_6_40COP_VSD | ElectricEIRChiller York YT 1459kW/6.40COP/VSD |
ElectricEIRChiller_Trane_CVHE_1484kW_9_96COP_VSD | ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD |
ElectricEIRChiller_York_YT_1495kW_7_51COP_VSD | ElectricEIRChiller York YT 1495kW/7.51COP/VSD |
ElectricEIRChiller_McQuay_WSC_1519kW_7_10COP_Vanes | ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1558kW_5_81COP_VSD | ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD |
ElectricEIRChiller_Carrier_19XR_1586kW_5_53COP_VSD | ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD |
ElectricEIRChiller_McQuay_PEH_1635kW_7_47COP_Vanes | ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1635kW_6_36COP_Vanes | ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1656kW_8_24COP_VSD | ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD |
ElectricEIRChiller_York_YT_1663kW_9_34COP_Vanes | ElectricEIRChiller York YT 1663kW/9.34COP/Vanes |
ElectricEIRChiller_Carrier_19XL_1674kW_7_89COP_Vanes | ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes |
ElectricEIRChiller_Trane_CVHF_1681kW_6_59COP_Vanes | ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1723kW_8_32COP_VSD | ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD |
ElectricEIRChiller_Carrier_19XR_1727kW_9_04COP_Vanes | ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes |
ElectricEIRChiller_McQuay_WSC_1751kW_6_73COP_Vanes | ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes |
ElectricEIRChiller_Trane_CVHF_1758kW_5_96COP_Vanes | ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes |
ElectricEIRChiller_York_YT_1758kW_5_76COP_VSD | ElectricEIRChiller York YT 1758kW/5.76COP/VSD |
ElectricEIRChiller_York_YT_1758kW_6_26COP_Vanes | ElectricEIRChiller York YT 1758kW/6.26COP/Vanes |
ElectricEIRChiller_York_YT_1758kW_5_96COP_Vanes | ElectricEIRChiller York YT 1758kW/5.96COP/Vanes |
ElectricEIRChiller_Trane_CVHE_1758kW_5_96COP_Vanes | ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes |
ElectricEIRChiller_York_YT_1758kW_6_28COP_Vanes | ElectricEIRChiller York YT 1758kW/6.28COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1758kW_5_86COP_VSD | ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD |
ElectricEIRChiller_Trane_CVHF_1758kW_6_46COP_VSD | ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD |
ElectricEIRChiller_Trane_CVHF_1758kW_6_87COP_Vanes | ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1776kW_8_00COP_Vanes | ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes |
ElectricEIRChiller_Carrier_19XL_1779kW_6_18COP_Vanes | ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes |
ElectricEIRChiller_Trane_CVHF_1779kW_6_18COP_Vanes | ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes |
ElectricEIRChiller_York_YT_1794kW_8_11COP_Vanes | ElectricEIRChiller York YT 1794kW/8.11COP/Vanes |
ElectricEIRChiller_York_YT_1794kW_7_90COP_VSD | ElectricEIRChiller York YT 1794kW/7.90COP/VSD |
ElectricEIRChiller_Carrier_19XL_1797kW_5_69COP_Vanes | ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1801kW_6_34COP_VSD | ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD |
ElectricEIRChiller_York_YT_1867kW_10_09COP_Vanes | ElectricEIRChiller York YT 1867kW/10.09COP/Vanes |
ElectricEIRChiller_Carrier_19XL_1871kW_6_49COP_Vanes | ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes |
ElectricEIRChiller_York_YT_1881kW_6_77COP_VSD | ElectricEIRChiller York YT 1881kW/6.77COP/VSD |
ElectricEIRChiller_York_YK_1881kW_6_53COP_Vanes | ElectricEIRChiller York YK 1881kW/6.53COP/Vanes |
ElectricEIRChiller_McQuay_PEH_1895kW_6_42COP_Vanes | ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes |
ElectricEIRChiller_York_YT_1934kW_7_55COP_Vanes | ElectricEIRChiller York YT 1934kW/7.55COP/Vanes |
ElectricEIRChiller_McQuay_PEH_1934kW_6_01COP_Vanes | ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes |
ElectricEIRChiller_McQuay_WDC_1973kW_6_28COP_Vanes | ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes |
ElectricEIRChiller_York_YK_1997kW_7_24COP_Vanes | ElectricEIRChiller York YK 1997kW/7.24COP/Vanes |
ElectricEIRChiller_McQuay_PFH_2043kW_8_44COP_Vanes | ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes |
ElectricEIRChiller_Trane_CVHF_2043kW_9_08COP_Vanes | ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes |
ElectricEIRChiller_Carrier_19XL_2057kW_6_05COP_Vanes | ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes |
ElectricEIRChiller_York_YT_2110kW_7_15COP_Vanes | ElectricEIRChiller York YT 2110kW/7.15COP/Vanes |
ElectricEIRChiller_McQuay_PFH_2124kW_6_03COP_Vanes | ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes |
ElectricEIRChiller_York_YK_2159kW_6_85COP_Vanes | ElectricEIRChiller York YK 2159kW/6.85COP/Vanes |
ElectricEIRChiller_Trane_CVHF_2184kW_6_78COP_Vanes | ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes |
ElectricEIRChiller_York_YK_2201kW_6_69COP_Vanes | ElectricEIRChiller York YK 2201kW/6.69COP/Vanes |
ElectricEIRChiller_York_YT_2233kW_9_54COP_VSD | ElectricEIRChiller York YT 2233kW/9.54COP/VSD |
ElectricEIRChiller_York_YK_2237kW_6_41COP_Vanes | ElectricEIRChiller York YK 2237kW/6.41COP/Vanes |
ElectricEIRChiller_York_YK_2275kW_6_32COP_Vanes | ElectricEIRChiller York YK 2275kW/6.32COP/Vanes |
ElectricEIRChiller_Trane_CVHF_2300kW_8_10COP_Vanes | ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes |
ElectricEIRChiller_Trane_CVHF_2317kW_6_33COP_VSD | ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD |
ElectricEIRChiller_Carrier_19XR_2391kW_6_77COP_Vanes | ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes |
ElectricEIRChiller_Carrier_19XR_2391kW_6_44COP_VSD | ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD |
ElectricEIRChiller_York_YK_2412kW_5_58COP_Vanes | ElectricEIRChiller York YK 2412kW/5.58COP/Vanes |
ElectricEIRChiller_McQuay_PFH_2462kW_6_67COP_Vanes | ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes |
ElectricEIRChiller_Trane_CVHF_2567kW_11_77COP_VSD | ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD |
ElectricEIRChiller_York_YK_2771kW_6_84COP_VSD | ElectricEIRChiller York YK 2771kW/6.84COP/VSD |
ElectricEIRChiller_Trane_CVHF_2799kW_6_40COP_Vanes | ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes |
ElectricEIRChiller_York_YT_3133kW_9_16COP_Vanes | ElectricEIRChiller York YT 3133kW/9.16COP/Vanes |
ElectricEIRChiller_McQuay_PFH_3165kW_6_48COP_Vanes | ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes |
ElectricEIRChiller_McQuay_PFH_4020kW_7_35COP_Vanes | ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes |
ElectricEIRChiller_York_YK_4396kW_6_63COP_Vanes | ElectricEIRChiller York YK 4396kW/6.63COP/Vanes |
ElectricEIRChiller_York_YK_4477kW_6_64COP_Vanes | ElectricEIRChiller York YK 4477kW/6.64COP/Vanes |
ElectricEIRChiller_York_YK_4515kW_6_22COP_Vanes | ElectricEIRChiller York YK 4515kW/6.22COP/Vanes |
ElectricEIRChiller_York_YK_4537kW_6_28COP_Vanes | ElectricEIRChiller York YK 4537kW/6.28COP/Vanes |
ElectricEIRChiller_Trane_CVHF_4610kW_6_34COP_Vanes | ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes |
ElectricEIRChiller_Carrier_19EX_4667kW_6_16COP_Vanes | ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes |
ElectricEIRChiller_Trane_CVHF_4677kW_6_27COP_Vanes | ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes |
ElectricEIRChiller_York_YK_4966kW_6_05COP_Vanes | ElectricEIRChiller York YK 4966kW/6.05COP/Vanes |
ElectricEIRChiller_York_YK_4969kW_7_14COP_Vanes | ElectricEIRChiller York YK 4969kW/7.14COP/Vanes |
ElectricEIRChiller_York_YK_4969kW_7_07COP_Vanes | ElectricEIRChiller York YK 4969kW/7.07COP/Vanes |
ElectricEIRChiller_Carrier_19EX_4997kW_6_40COP_Vanes | ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes |
ElectricEIRChiller_Carrier_19EX_5148kW_6_34COP_Vanes | ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes |
ElectricEIRChiller_York_YK_5170kW_7_15COP_Vanes | ElectricEIRChiller York YK 5170kW/7.15COP/Vanes |
ElectricEIRChiller_Carrier_19EX_5208kW_6_88COP_Vanes | ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes |
ElectricEIRChiller_York_YK_5465kW_6_94COP_Vanes | ElectricEIRChiller York YK 5465kW/6.94COP/Vanes |
ElectricEIRChiller_York_YK_5549kW_6_50COP_Vanes | ElectricEIRChiller York YK 5549kW/6.50COP/Vanes |
ElectricEIRChiller_Carrier_19FA_5651kW_5_50COP_Vanes | ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes |
DOE_2_Centrifugal_5_50COP | DOE-2 Centrifugal/5.50COP |
ElectricEIRChiller_Multistack_MS_172kW_3_67COP_None | ElectricEIRChiller Multistack MS 172kW/3.67COP/None |
DOE_2_Reciprocating_3_67COP | DOE-2 Reciprocating/3.67COP |
ElectricEIRChiller_Trane_RTWA_383kW_4_17COP_Valve | ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve |
ElectricEIRChiller_Trane_RTHB_531kW_4_83COP_Valve | ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve |
ElectricEIRChiller_Trane_RTHB_538kW_5_12COP_Valve | ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve |
ElectricEIRChiller_Trane_RTHB_542kW_5_26COP_Valve | ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve |
ElectricEIRChiller_York_YS_672kW_7_90COP_Valve | ElectricEIRChiller York YS 672kW/7.90COP/Valve |
ElectricEIRChiller_Carrier_23XL_686kW_5_91COP_Valve | ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve |
ElectricEIRChiller_Trane_RTHC_707kW_7_77COP_Valve | ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve |
ElectricEIRChiller_York_YS_756kW_7_41COP_Valve | ElectricEIRChiller York YS 756kW/7.41COP/Valve |
ElectricEIRChiller_York_YS_781kW_5_42COP_Valve | ElectricEIRChiller York YS 781kW/5.42COP/Valve |
ElectricEIRChiller_Carrier_23XL_830kW_6_97COP_Valve | ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve |
ElectricEIRChiller_Carrier_23XL_862kW_6_11COP_Valve | ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve |
ElectricEIRChiller_Carrier_23XL_862kW_6_84COP_Valve | ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve |
ElectricEIRChiller_Carrier_23XL_865kW_6_05COP_Valve | ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve |
ElectricEIRChiller_York_YS_879kW_5_82COP_Valve | ElectricEIRChiller York YS 879kW/5.82COP/Valve |
ElectricEIRChiller_Trane_RTHC_1009kW_5_37COP_Valve | ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve |
ElectricEIRChiller_Trane_RTHB_1051kW_5_05COP_Valve | ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve |
ElectricEIRChiller_Carrier_23XL_1062kW_5_50COP_Valve | ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve |
ElectricEIRChiller_Trane_RTHC_1066kW_5_73COP_Valve | ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve |
ElectricEIRChiller_Trane_RTHC_1094kW_6_55COP_Valve | ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve |
ElectricEIRChiller_Carrier_23XL_1108kW_6_92COP_Valve | ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve |
ElectricEIRChiller_York_YS_1171kW_9_15COP_Valve | ElectricEIRChiller York YS 1171kW/9.15COP/Valve |
ElectricEIRChiller_Carrier_23XL_1196kW_6_39COP_Valve | ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve |
ElectricEIRChiller_York_YS_1554kW_9_31COP_Valve | ElectricEIRChiller York YS 1554kW/9.31COP/Valve |
ElectricEIRChiller_York_YS_1758kW_5_84COP_Valve | ElectricEIRChiller York YS 1758kW/5.84COP/Valve |
ElectricEIRChiller_Trane_CGWD_207kW_3_99COP_None | ElectricEIRChiller Trane CGWD 207kW/3.99COP/None |
Generic data record for chiller ElectricEIR
This record is used as a template for performance data for the chiller model Buildings.Fluid.Chillers.ElectricEIR.
Extends from Buildings.Fluid.Chillers.Data.BaseClasses.Chiller (Base classes for chiller models).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | Maximum part load ratio | |
Real | PLRMinUnl | Minimum part unload ratio | |
Real | PLRMin | Minimum part load ratio | |
Real | etaMotor | Fraction of compressor motor heat entering refrigerant | |
Temperature | TConEnt_nominal | Temperature of fluid entering condenser at nominal condition [K] | |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | Reference capacity (negative number) [W] | |
Real | COP_nominal | Reference coefficient of performance | |
MassFlowRate | mEva_flow_nominal | Nominal mass flow at evaporator [kg/s] | |
MassFlowRate | mCon_flow_nominal | Nominal mass flow at condenser [kg/s] | |
Temperature | TEvaLvg_nominal | Temperature of fluid leaving evaporator at nominal condition [K] | |
Performance curves | |||
Integer | nCapFunT | 6 | Number of coefficients for capFunT |
Integer | nEIRFunT | 6 | Number of coefficients for capFunT |
Integer | nEIRFunPLR | 3 | Number of coefficients for capFunT |
Real | capFunT[nCapFunT] | Biquadratic coefficients for capFunT | |
Real | EIRFunT[nEIRFunT] | Biquadratic coefficients for EIRFunT | |
Real | EIRFunPLR[nEIRFunPLR] | Coefficients for EIRFunPLR | |
Temperature | TEvaLvgMin | Minimum value for leaving evaporator temperature [K] | |
Temperature | TEvaLvgMax | Maximum value for leaving evaporator temperature [K] | |
Temperature | TConEntMin | Minimum value for entering condenser temperature [K] | |
Temperature | TConEntMax | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes, !- Name 471200, !- Reference Capacity {W} 5.89, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.01035, !- Reference Chilled Water Flow Rate {m3/s} 0.01924, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.15, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.15 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -471200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.89 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01035 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01924 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.521130E-01,1.324053E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.475238E-01,-2.588210E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.778889E-01,2.338363E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 563kW/10.61COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 563kW/10.61COP/Vanes, !- Name 562600, !- Reference Capacity {W} 10.61, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.01514, !- Reference Chilled Water Flow Rate {m3/s} 0.0241, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 563kW/10.61COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 563kW/10.61COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 563kW/10.61COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -562600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 10.61 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01514 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0241 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.288612E-01,-8.919540E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-5.781003E-01,-1.169130E-01... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.203969E-01,-7.775900E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes, !- Name 703300, !- Reference Capacity {W} 7.03, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.02019, !- Reference Chilled Water Flow Rate {m3/s} 0.02902, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -703300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.03 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02019 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02902 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.779439E-01,1.073486E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.234029E-01,-1.171542E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.864389E-01,-2.522595E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes, !- Name 724400, !- Reference Capacity {W} 6.04, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 21.11, !- Reference Entering Condenser Fluid Temperature {C} 0.01779, !- Reference Chilled Water Flow Rate {m3/s} 0.01956, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -724400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.04 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01779 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.418712E-01,-8.384251E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.059102E-01,-1.621557E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.879418E-01,3.562862E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 13.75 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD, !- Name 742000, !- Reference Capacity {W} 5.42, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 21.11, !- Reference Entering Condenser Fluid Temperature {C} 0.01779, !- Reference Chilled Water Flow Rate {m3/s} 0.01956, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -742000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.42 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01779 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.797101E-01,-2.895701E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.946139E-01,-4.829399E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.202277E-01,1.396384E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 11.25 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes, !- Name 815800, !- Reference Capacity {W} 6.74, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.01748, !- Reference Chilled Water Flow Rate {m3/s} 0.04164, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -815800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.74 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01748 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04164 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.862590E-01,5.799373E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.335321E-01,4.465107E-04,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.070136E-01,8.654874E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes, !- Name 819300, !- Reference Capacity {W} 8.11, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.02524, !- Reference Chilled Water Flow Rate {m3/s} 0.03785, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -819300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.11 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02524 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03785 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.392673E-01,4.328784E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.925176E-01,-1.908391E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.830681E-01,2.254147E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes, !- Name 822900, !- Reference Capacity {W} 6.28, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.04744, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -822900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.573150E-01,8.714616E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.029134E-01,2.171359E-02,2... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.965419E-01,4.689744E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD, !- Name 868600, !- Reference Capacity {W} 5.57, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.01754, !- Reference Chilled Water Flow Rate {m3/s} 0.02593, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -868600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.57 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01754 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02593 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.406799E-01,1.253709E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.943721E-01,1.079147E-01,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.501042E-01,-6.804336E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD, !- Name 896700, !- Reference Capacity {W} 7.23, !- Reference COP {W/W} 9.82, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.0436, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.23 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0436 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.82 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.559679E-01,7.630860E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.511011E-01,4.948557E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.036380E-01,-3.913200E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes, !- Name 896700, !- Reference Capacity {W} 6.50, !- Reference COP {W/W} 9.82, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.04423, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04423 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.82 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.009156E-01,2.151274E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.527749E-01,-4.336881E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.323416E-01,2.561103E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 897kW/7.60COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YT 897kW/7.60COP/VSD, !- Name 896700, !- Reference Capacity {W} 7.60, !- Reference COP {W/W} 9.83, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 897kW/7.60COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 897kW/7.60COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 897kW/7.60COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.60 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.83 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.699948E-01,2.961470E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.526128E-01,3.299472E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.708628E-02,7.070062E-02,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 897kW/6.27COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YT 897kW/6.27COP/VSD, !- Name 896700, !- Reference Capacity {W} 6.27, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 897kW/6.27COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 897kW/6.27COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 897kW/6.27COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.27 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.197991E-01,1.568955E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.530767E-01,-5.683068E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.836320E-02,-1.638320E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD, !- Name 896700, !- Reference Capacity {W} 6.23, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.04442, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.23 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04442 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.862185E-01,3.144947E-02,2... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.606461E-01,-1.202294E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.075556E-01,-2.126466E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes, !- Name 931900, !- Reference Capacity {W} 5.09, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.03785, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -931900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.09 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.182278E+00,3.259490E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.053491E-01,-1.089778E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.823245E-02,6.672421E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 960kW/4.64COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 960kW/4.64COP/Vanes, !- Name 960000, !- Reference Capacity {W} 4.64, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.03785, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 960kW/4.64COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 960kW/4.64COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 960kW/4.64COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.09, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.09 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -960000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.64 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-2.278537E-01,4.055945E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.735924E-01,2.270414E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.737941E-01,3.141127E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1023kW/5.81COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 1023kW/5.81COP/Vanes, !- Name 1023300, !- Reference Capacity {W} 5.81, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.02366, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1023kW/5.81COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1023kW/5.81COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1023kW/5.81COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1023300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.81 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02366 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.571195E-01,-1.571421E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.254964E-01,-1.972389E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.368399E-01,3.286421E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes, !- Name 1030300, !- Reference Capacity {W} 8.58, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.02378, !- Reference Chilled Water Flow Rate {m3/s} 0.03407, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.08, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.08, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1030300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.58 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02378 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03407 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.736028E-01,5.571395E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.125878E-01,1.388940E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.215320E-01,-9.188416E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1048kW/6.06COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 1048kW/6.06COP/Vanes, !- Name 1047900, !- Reference Capacity {W} 6.06, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.04542, !- Reference Chilled Water Flow Rate {m3/s} 0.05678, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1048kW/6.06COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1048kW/6.06COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1048kW/6.06COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1047900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.06 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04542 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05678 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.238221E-01,1.747548E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.255594E-01,-3.502968E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.543796E-01,7.276121E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1055kW/5.96COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 1055kW/5.96COP/Vanes, !- Name 1055000, !- Reference Capacity {W} 5.96, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.02839, !- Reference Chilled Water Flow Rate {m3/s} 0.05678, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1055kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1055kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1055kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1055000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02839 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05678 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.785912E-01,-5.900023E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.245110E-01,-2.850126E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.619878E-01,2.393605E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes, !- Name 1076100, !- Reference Capacity {W} 5.52, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.89, !- Reference Entering Condenser Fluid Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.04744, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1076100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.52 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.187704E-01,4.509452E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.511044E-01,2.415573E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.315760E-01,-3.004087E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes, !- Name 1079600, !- Reference Capacity {W} 7.39, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.61, !- Reference Entering Condenser Fluid Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.06416, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.61 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1079600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06416 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.365583E-01,-3.677215E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.608716E-01,-5.637178E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.789841E-01,2.976513E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 16.24 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.61 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1090kW/7.57COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YT 1090kW/7.57COP/VSD, !- Name 1090100, !- Reference Capacity {W} 7.57, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1090kW/7.57COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1090kW/7.57COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1090kW/7.57COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1090100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.57 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.769028E-01,5.711844E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.241019E-01,-4.961574E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.431969E-01,-4.920686E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes, !- Name 1104200, !- Reference Capacity {W} 8.00, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.02423, !- Reference Chilled Water Flow Rate {m3/s} 0.03028, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.08, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.08, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1104200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.00 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02423 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03028 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.210185E-01,4.386152E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.655242E-01,-3.808337E-04,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.091150E-01,-1.089639E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes, !- Name 1125300, !- Reference Capacity {W} 4.89, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.02776, !- Reference Chilled Water Flow Rate {m3/s} 0.02618, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1125300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.89 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02776 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02618 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.151549E-01,-1.181250E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.810580E-01,-4.344257E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.807198E-01,-1.469686E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1125kW/7.92COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YT 1125kW/7.92COP/VSD, !- Name 1125300, !- Reference Capacity {W} 7.92, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03243, !- Reference Chilled Water Flow Rate {m3/s} 0.05173, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1125kW/7.92COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1125kW/7.92COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1125kW/7.92COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1125300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.92 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05173 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.034212E-01,2.327078E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.542286E-01,-2.451604E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.147453E-01,4.231235E-02,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes, !- Name 1128800, !- Reference Capacity {W} 7.19, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.02776, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.15, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.15, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.15 | Minimum part unload ratio |
Real | PLRMin | 0.15 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1128800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.19 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02776 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.922479E-01,-4.388411E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.742142E-01,-5.536709E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.693841E-01,2.475201E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD, !- Name 1142900, !- Reference Capacity {W} 6.57, !- Reference COP {W/W} 10.00, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.02593, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1142900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.57 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 10.00 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.939538E-01,4.096493E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.475580E-01,-1.187942E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.408822E-01,-1.578153E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD, !- Name 1156900, !- Reference Capacity {W} 5.62, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 21.11, !- Reference Entering Condenser Fluid Temperature {C} 0.02801, !- Reference Chilled Water Flow Rate {m3/s} 0.03186, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1156900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.62 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02801 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03186 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.076248E+00,5.436724E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.075567E+00,-3.893571E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.608589E-01,-2.058215E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 11.25 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes, !- Name 1195600, !- Reference Capacity {W} 6.50, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.03426, !- Reference Chilled Water Flow Rate {m3/s} 0.04252, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1195600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03426 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04252 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.126801E+00,-4.220591E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.514432E-01,-2.252147E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.724491E-01,2.710369E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes, !- Name 1213200, !- Reference Capacity {W} 7.78, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03243, !- Reference Chilled Water Flow Rate {m3/s} 0.04782, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1213200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.78 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04782 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.070437E-01,-7.437456E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.002142E+00,-2.505239E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.847744E-01,4.027863E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes, !- Name 1230800, !- Reference Capacity {W} 6.18, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03533, !- Reference Chilled Water Flow Rate {m3/s} 0.0511, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1230800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.18 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03533 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0511 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.152795E+00,9.770474E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.067591E-01,1.868314E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.117054E-01,4.263662E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD, !- Name 1234300, !- Reference Capacity {W} 5.39, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.02593, !- Reference Chilled Water Flow Rate {m3/s} 0.03861, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1234300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03861 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.905815E-01,1.190927E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.771659E-01,1.144965E-01,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.495681E-01,-1.449639E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes, !- Name 1258900, !- Reference Capacity {W} 6.26, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.02593, !- Reference Chilled Water Flow Rate {m3/s} 0.03823, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1258900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.26 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03823 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.082071E+00,3.200888E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.582035E-01,6.896017E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.226232E-01,5.199282E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 1259kW/6.45COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 1259kW/6.45COP/Vanes, !- Name 1258900, !- Reference Capacity {W} 6.45, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.02631, !- Reference Chilled Water Flow Rate {m3/s} 0.06246, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 1259kW/6.45COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 1259kW/6.45COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 1259kW/6.45COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1258900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.45 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02631 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06246 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.609200E-01,7.223733E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.991536E-01,6.305932E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.014593E-01,6.216537E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1266kW/4.39COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 1266kW/4.39COP/Vanes, !- Name 1266000, !- Reference Capacity {W} 4.39, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 35.00, !- Reference Entering Condenser Fluid Temperature {C} 0.03533, !- Reference Chilled Water Flow Rate {m3/s} 0.05773, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1266kW/4.39COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1266kW/4.39COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1266kW/4.39COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.11, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.11, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 35.00 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1266000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03533 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05773 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.285663E-01,-2.860032E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.284925E-02,4.206167E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.326942E-01,-7.962527E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes, !- Name 1283500, !- Reference Capacity {W} 6.20, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03684, !- Reference Chilled Water Flow Rate {m3/s} 0.05337, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1283500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.20 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03684 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.119245E+00,-1.524417E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.815645E-01,-2.448971E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.324812E-01,7.690691E-01,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes, !- Name 1294100, !- Reference Capacity {W} 7.61, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03243, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.16, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.16, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.16 | Minimum part unload ratio |
Real | PLRMin | 0.16 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1294100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.61 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.274222E-01,1.278683E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.085249E+00,-9.441252E-04,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.344563E-02,3.993002E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes, !- Name 1329300, !- Reference Capacity {W} 5.38, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.04732, !- Reference Chilled Water Flow Rate {m3/s} 0.07098, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.29, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.29, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.29 | Minimum part unload ratio |
Real | PLRMin | 0.29 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1329300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.38 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04732 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07098 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.339754E-01,1.016009E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.074052E-01,3.355495E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.079777E-02,1.174456E+00,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 21.11 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD, !- Name 1350400, !- Reference Capacity {W} 7.90, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03684, !- Reference Chilled Water Flow Rate {m3/s} 0.05337, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1350400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.90 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03684 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.063866E+00,-1.448990E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.953536E-01,-3.118863E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.336374E-01,-4.098166E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1368kW/7.35COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YT 1368kW/7.35COP/VSD, !- Name 1367900, !- Reference Capacity {W} 7.35, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1368kW/7.35COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1368kW/7.35COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1368kW/7.35COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1367900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.35 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.832184E-01,-3.265439E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.227543E-01,-1.415418E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.483562E-02,1.521114E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes, !- Name 1371500, !- Reference Capacity {W} 7.49, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.41, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.41, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1371500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.49 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.993784E-01,6.523380E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.123765E-01,1.616509E-02,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.154478E-02,9.635713E-01,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1396kW/7.35COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 1396kW/7.35COP/Vanes, !- Name 1396100, !- Reference Capacity {W} 7.35, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1396kW/7.35COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1396kW/7.35COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1396kW/7.35COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1396100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.35 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.167863E-01,-2.788454E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.207500E-01,-9.073869E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.043032E-01,3.720107E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD, !- Name 1403100, !- Reference Capacity {W} 7.09, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03426, !- Reference Chilled Water Flow Rate {m3/s} 0.04252, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1403100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.09 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03426 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04252 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.601814E-01,-3.596494E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.098641E+00,-2.485880E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.788698E-02,2.678891E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1403kW/6.94COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YT 1403kW/6.94COP/VSD, !- Name 1403100, !- Reference Capacity {W} 6.94, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.05047, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1403kW/6.94COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1403kW/6.94COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1403kW/6.94COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.1, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.1 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1403100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.94 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-3.447077E-02,1.273138E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.983846E-01,2.396665E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.272242E-02,3.873540E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD, !- Name 1406600, !- Reference Capacity {W} 7.14, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.14 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.521342E-01,5.248142E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.674858E-01,4.461513E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.963988E-02,3.503067E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes, !- Name 1406600, !- Reference Capacity {W} 6.60, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04038, !- Reference Chilled Water Flow Rate {m3/s} 0.05804, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.60 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04038 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05804 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.191784E+00,2.070584E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.929709E-01,3.424884E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.700603E-02,5.414789E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD, !- Name 1406600, !- Reference Capacity {W} 6.04, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06057, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.04 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06057 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.042261E+00,2.644821E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.026340E+00,-1.612819E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.188880E-01,6.723542E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 32.22 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD, !- Name 1410100, !- Reference Capacity {W} 8.54, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04, !- Reference Chilled Water Flow Rate {m3/s} 0.05861, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1410100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.54 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05861 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.597856E-01,-6.247187E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.131014E+00,-6.735406E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.662908E-02,7.475978E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD, !- Name 1441800, !- Reference Capacity {W} 6.61, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.05047, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1441800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.61 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.007341E-01,1.148568E-03,1... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.287646E-01,-3.024605E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.299787E-02,3.244475E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1459kW/6.40COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YT 1459kW/6.40COP/VSD, !- Name 1459400, !- Reference Capacity {W} 6.40, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.05047, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1459kW/6.40COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1459kW/6.40COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1459kW/6.40COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.13, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.13 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1459400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.40 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.665585E-01,2.211580E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.438935E-01,9.821191E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.999642E-02,2.509430E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD, !- Name 1484000, !- Reference Capacity {W} 9.96, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.24, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.24, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.24 | Minimum part unload ratio |
Real | PLRMin | 0.24 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1484000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-4.544480E-01,-3.615933E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-3.693940E-01,-6.387787E-02... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.353827E-01,1.385983E-02,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1495kW/7.51COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YT 1495kW/7.51COP/VSD, !- Name 1494500, !- Reference Capacity {W} 7.51, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.0429, !- Reference Chilled Water Flow Rate {m3/s} 0.06719, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1495kW/7.51COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1495kW/7.51COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1495kW/7.51COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.11, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.11, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1494500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.51 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0429 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06719 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.051921E+00,-1.632255E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.106985E-01,-2.087623E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.517470E-01,-1.577252E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes, !- Name 1519200, !- Reference Capacity {W} 7.10, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.08139, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1519200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.10 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.08139 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.265889E+00,3.401563E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.981236E-01,-1.060763E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.563837E-01,4.894381E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD, !- Name 1557800, !- Reference Capacity {W} 5.81, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 21.11, !- Reference Entering Condenser Fluid Temperature {C} 0.03785, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1557800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.81 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.034307E+00,2.390635E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.099343E+00,-3.132676E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.620909E-01,-2.553890E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 11.94 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD, !- Name 1586000, !- Reference Capacity {W} 5.53, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.03388, !- Reference Chilled Water Flow Rate {m3/s} 0.04669, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1586000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.53 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03388 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04669 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.119233E+00,1.130501E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.110611E+00,-3.795765E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.996379E-01,-1.612021E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes, !- Name 1635200, !- Reference Capacity {W} 7.47, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04416, !- Reference Chilled Water Flow Rate {m3/s} 0.06624, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.08, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.08, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1635200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.47 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04416 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06624 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.894188E-01,2.983148E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.040733E+00,-7.118888E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.836695E-01,5.781685E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes, !- Name 1635200, !- Reference Capacity {W} 6.36, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.03432, !- Reference Chilled Water Flow Rate {m3/s} 0.05035, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1635200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.36 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03432 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05035 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.639212E-01,1.160405E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.355981E-01,-1.083354E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.581595E-01,2.707154E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD, !- Name 1656300, !- Reference Capacity {W} 8.24, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04322, !- Reference Chilled Water Flow Rate {m3/s} 0.06296, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1656300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.24 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04322 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06296 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.611706E-01,-2.867067E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.730916E-01,-8.073559E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.982584E-01,4.414042E-02,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1663kW/9.34COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 1663kW/9.34COP/Vanes, !- Name 1663300, !- Reference Capacity {W} 9.34, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04139, !- Reference Chilled Water Flow Rate {m3/s} 0.0776, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1663kW/9.34COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1663kW/9.34COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1663kW/9.34COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1663300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04139 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0776 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.112226E-01,-4.546497E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.028094E+00,-6.127553E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.127966E-01,3.131004E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes, !- Name 1673900, !- Reference Capacity {W} 7.89, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.32, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.32, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.32 | Minimum part unload ratio |
Real | PLRMin | 0.32 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1673900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.89 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.925408E-01,-4.406182E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.868510E-01,-6.325526E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.386410E-01,2.621224E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes, !- Name 1680900, !- Reference Capacity {W} 6.59, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.04366, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1680900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.59 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04366 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.792987E-01,-5.291217E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.344630E-01,-5.781149E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.619116E-01,2.362420E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD, !- Name 1723100, !- Reference Capacity {W} 8.32, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04757, !- Reference Chilled Water Flow Rate {m3/s} 0.06934, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1723100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.32 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06934 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.742518E-01,-5.109937E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.950574E-01,-1.036684E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.374010E-01,-1.796745E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes, !- Name 1726600, !- Reference Capacity {W} 9.04, !- Reference COP {W/W} 7.78, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03912, !- Reference Chilled Water Flow Rate {m3/s} 0.07192, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1726600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.04 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03912 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07192 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.509915E-01,2.567642E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.072553E+00,-8.058631E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.465824E-01,4.494453E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes, !- Name 1751300, !- Reference Capacity {W} 6.73, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.04145, !- Reference Chilled Water Flow Rate {m3/s} 0.09337, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1751300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.73 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04145 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.923045E-01,1.003672E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.089395E-01,2.628482E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.250725E-01,2.648297E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 5.96, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.074211E+00,7.710761E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.910329E-01,-9.895115E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.694797E-01,9.551656E-02,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1758kW/5.76COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YT 1758kW/5.76COP/VSD, !- Name 1758300, !- Reference Capacity {W} 5.76, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1758kW/5.76COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/5.76COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/5.76COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.76 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.575085E-01,1.313508E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.794525E-01,6.694756E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.859908E-02,1.950291E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.51 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1758kW/6.26COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 1758kW/6.26COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 6.26, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1758kW/6.26COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/6.26COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/6.26COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.14, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.14 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.26 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.975936E-01,-1.459740E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.311197E-01,9.581517E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.720545E-01,5.598164E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1758kW/5.96COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 1758kW/5.96COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 5.96, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1758kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.492365E-01,5.551947E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.949320E-01,9.099785E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.236154E-01,2.590053E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 5.96, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.566057E-02,-2.457943E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.243313E+00,-3.031784E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.871377E-01,5.849639E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1758kW/6.28COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 1758kW/6.28COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 6.28, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1758kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.079149E-01,-2.006276E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.605391E-01,-1.377994E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.861223E-01,5.482049E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD, !- Name 1758300, !- Reference Capacity {W} 5.86, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06303, !- Reference Chilled Water Flow Rate {m3/s} 0.07337, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.86 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.677279E-01,-3.175504E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.743365E-01,-5.054806E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.784580E-01,-5.498632E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD, !- Name 1758300, !- Reference Capacity {W} 6.46, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.46 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.066671E+00,5.889240E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.989434E-02,2.062907E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.268954E-01,3.297771E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 6.87, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.87 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.085529E-01,3.412026E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.329473E-01,5.521802E-03,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.401900E-01,5.090345E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes, !- Name 1775900, !- Reference Capacity {W} 8.00, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04757, !- Reference Chilled Water Flow Rate {m3/s} 0.07003, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1775900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.00 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07003 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.841535E-01,-3.584260E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.006719E-01,-3.137026E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.276235E-01,2.787167E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes, !- Name 1779400, !- Reference Capacity {W} 6.18, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.06303, !- Reference Chilled Water Flow Rate {m3/s} 0.08858, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1779400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.18 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.08858 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.703515E-01,-4.051337E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.872331E-01,-3.907248E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.090532E-01,2.641442E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.11 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes, !- Name 1779400, !- Reference Capacity {W} 6.18, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.04454, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1779400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.18 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04454 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.331346E-01,-5.678656E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.137523E-01,-1.879556E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.699409E-01,1.874304E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1794kW/8.11COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 1794kW/8.11COP/Vanes, !- Name 1793500, !- Reference Capacity {W} 8.11, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05148, !- Reference Chilled Water Flow Rate {m3/s} 0.09653, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1794kW/8.11COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1794kW/8.11COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1794kW/8.11COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.08, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.08 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1793500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.11 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05148 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09653 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.536140E+00,-1.630760E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.546274E-01,2.456473E-01,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.187543E-02,8.272483E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1794kW/7.90COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YT 1794kW/7.90COP/VSD, !- Name 1793500, !- Reference Capacity {W} 7.90, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05148, !- Reference Chilled Water Flow Rate {m3/s} 0.09653, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1794kW/7.90COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1794kW/7.90COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1794kW/7.90COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1793500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.90 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05148 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09653 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.552268E-01,-1.553435E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.984829E-01,-1.552700E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.445880E-01,1.059293E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes, !- Name 1797000, !- Reference Capacity {W} 5.69, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.07737, !- Reference Chilled Water Flow Rate {m3/s} 0.09672, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.39, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.39, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.39 | Minimum part unload ratio |
Real | PLRMin | 0.39 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1797000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.69 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07737 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09672 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.084596E-01,4.671596E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.084290E+00,-4.318103E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.926251E-01,-2.657314E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 21.11 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD, !- Name 1800500, !- Reference Capacity {W} 6.34, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05161, !- Reference Chilled Water Flow Rate {m3/s} 0.06385, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1800500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05161 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06385 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.174861E-01,-7.299051E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.931082E-01,-1.885558E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.040764E-01,2.818752E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1867kW/10.09COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 1867kW/10.09COP/Vanes, !- Name 1867300, !- Reference Capacity {W} 10.09, !- Reference COP {W/W} 7.78, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1867kW/10.09COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1867kW/10.09COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1867kW/10.09COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1867300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 10.09 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.451516E-01,-1.252382E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.668391E-01,1.506485E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.157002E-01,2.251016E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes, !- Name 1870800, !- Reference Capacity {W} 6.49, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.06303, !- Reference Chilled Water Flow Rate {m3/s} 0.0877, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1870800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.49 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0877 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.658630E-03,-3.836575E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.029608E+00,-7.149045E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.984908E-01,2.906868E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1881kW/6.77COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YT 1881kW/6.77COP/VSD, !- Name 1881400, !- Reference Capacity {W} 6.77, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1881kW/6.77COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1881kW/6.77COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1881kW/6.77COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1881400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.065247E-01,-4.158206E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.175311E-01,-3.913241E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.087656E-02,4.842164E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 1881kW/6.53COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 1881kW/6.53COP/Vanes, !- Name 1881400, !- Reference Capacity {W} 6.53, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.04397, !- Reference Chilled Water Flow Rate {m3/s} 0.1041, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 1881kW/6.53COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 1881kW/6.53COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 1881kW/6.53COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1881400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.53 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04397 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.1041 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.561286E-01,4.130164E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.434989E-01,4.361264E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.272116E-02,4.176382E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 9.44 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes, !- Name 1895400, !- Reference Capacity {W} 6.42, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.09, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.09 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1895400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.42 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.573195E-01,-1.131937E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.915073E-01,-4.399727E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.592598E-01,1.425462E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 1934kW/7.55COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 1934kW/7.55COP/Vanes, !- Name 1934100, !- Reference Capacity {W} 7.55, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 13.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05552, !- Reference Chilled Water Flow Rate {m3/s} 0.08675, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1934kW/7.55COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1934kW/7.55COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1934kW/7.55COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 13.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1934100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.55 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.08675 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.420318E-02,1.103599E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.173674E+00,-1.301647E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.706237E-01,6.063362E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes, !- Name 1934100, !- Reference Capacity {W} 6.01, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.05552, !- Reference Chilled Water Flow Rate {m3/s} 0.07981, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.08, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.08 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1934100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.01 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07981 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.893111E-01,-3.834949E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.885371E-01,-5.877829E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.849256E-01,-2.369152E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes, !- Name 1972800, !- Reference Capacity {W} 6.28, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.04145, !- Reference Chilled Water Flow Rate {m3/s} 0.09337, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1972800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04145 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.110884E+00,7.376077E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.097378E+00,-3.018324E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.282891E-01,2.722981E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 1997kW/7.24COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 1997kW/7.24COP/Vanes, !- Name 1997400, !- Reference Capacity {W} 7.24, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.04397, !- Reference Chilled Water Flow Rate {m3/s} 0.1041, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 1997kW/7.24COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 1997kW/7.24COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 1997kW/7.24COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1997400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.24 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04397 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.1041 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.058272E-01,1.309175E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.188194E-01,8.769791E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.359332E-02,5.873752E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes, !- Name 2043100, !- Reference Capacity {W} 8.44, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04757, !- Reference Chilled Water Flow Rate {m3/s} 0.06814, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.08, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.08, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2043100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.44 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06814 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.383569E-01,4.716323E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.891693E-01,1.168677E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.225600E-01,3.070007E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes, !- Name 2043100, !- Reference Capacity {W} 9.08, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 18.33, !- Reference Entering Condenser Fluid Temperature {C} 0.09085, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.28, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.28, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.28 | Minimum part unload ratio |
Real | PLRMin | 0.28 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 18.33 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2043100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.08 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.340241E+00,7.634284E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.065177E-01,1.178669E-02,2... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.173752E-01,4.394720E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes, !- Name 2057200, !- Reference Capacity {W} 6.05, !- Reference COP {W/W} 7.78, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.08322, !- Reference Chilled Water Flow Rate {m3/s} 0.09722, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.28, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.28, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.28 | Minimum part unload ratio |
Real | PLRMin | 0.28 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2057200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.08322 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09722 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.737452E-01,-1.249478E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.623086E-01,-5.844490E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.041274E-01,-3.861525E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 2110kW/7.15COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 2110kW/7.15COP/Vanes, !- Name 2110000, !- Reference Capacity {W} 7.15, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06057, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 2110kW/7.15COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 2110kW/7.15COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 2110kW/7.15COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2110000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.15 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06057 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.359238E-01,1.785857E-02,1... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.270855E-01,-4.119654E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.469187E-01,1.862690E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes, !- Name 2124000, !- Reference Capacity {W} 6.03, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05552, !- Reference Chilled Water Flow Rate {m3/s} 0.07981, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2124000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.03 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07981 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.040134E+00,-1.745650E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.157799E+00,-3.621524E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.051419E-01,2.033679E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 2159kW/6.85COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 2159kW/6.85COP/Vanes, !- Name 2159200, !- Reference Capacity {W} 6.85, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 2159kW/6.85COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 2159kW/6.85COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 2159kW/6.85COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2159200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.85 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.322235E-01,1.553954E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.106730E-01,-3.786410E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.595694E-01,1.889684E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes, !- Name 2183800, !- Reference Capacity {W} 6.78, !- Reference COP {W/W} 7.78, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.04883, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2183800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.78 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04883 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.235680E+00,2.213527E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.877947E-01,-1.334886E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.942647E-02,5.249540E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 2201kW/6.69COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 2201kW/6.69COP/Vanes, !- Name 2201400, !- Reference Capacity {W} 6.69, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 2201kW/6.69COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 2201kW/6.69COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 2201kW/6.69COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2201400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.69 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.474968E-01,-4.800356E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.234137E-01,1.308264E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.653493E-01,1.444620E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 2233kW/9.54COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YT 2233kW/9.54COP/VSD, !- Name 2233000, !- Reference Capacity {W} 9.54, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.06107, !- Reference Chilled Water Flow Rate {m3/s} 0.11451, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 2233kW/9.54COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 2233kW/9.54COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 2233kW/9.54COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2233000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.54 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06107 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11451 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.585741E-01,-5.127829E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.563409E-01,-1.966623E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.917141E-02,1.743339E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 2237kW/6.41COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 2237kW/6.41COP/Vanes, !- Name 2236600, !- Reference Capacity {W} 6.41, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 2237kW/6.41COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 2237kW/6.41COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 2237kW/6.41COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.13, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.13, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.13 | Minimum part unload ratio |
Real | PLRMin | 0.13 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2236600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.41 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.899710E-01,-1.413334E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.567950E-01,3.354557E-03,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.605354E-01,2.125571E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 2275kW/6.32COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 2275kW/6.32COP/Vanes, !- Name 2275200, !- Reference Capacity {W} 6.32, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 2275kW/6.32COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 2275kW/6.32COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 2275kW/6.32COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.13, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.13, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.13 | Minimum part unload ratio |
Real | PLRMin | 0.13 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2275200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.32 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.034673E+00,-1.091064E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.326094E-01,-6.056615E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.735485E-01,2.163041E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes, !- Name 2299900, !- Reference Capacity {W} 8.10, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.23, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.23, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.23 | Minimum part unload ratio |
Real | PLRMin | 0.23 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2299900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.10 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.268137E-01,3.920902E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.178121E-01,6.561784E-03,8... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.161399E-01,4.347344E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD, !- Name 2317400, !- Reference Capacity {W} 6.33, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.09085, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2317400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.33 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.277716E-01,1.018101E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.502330E-01,-2.301510E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.861441E-02,5.297727E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes, !- Name 2391300, !- Reference Capacity {W} 6.77, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06858, !- Reference Chilled Water Flow Rate {m3/s} 0.0846, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2391300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06858 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0846 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.676388E-01,-5.087680E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.266646E-01,-2.367443E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.036386E-01,2.524850E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD, !- Name 2391300, !- Reference Capacity {W} 6.44, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06858, !- Reference Chilled Water Flow Rate {m3/s} 0.0846, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2391300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.44 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06858 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0846 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.676388E-01,-5.087680E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.230142E-01,-2.371649E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.774812E-02,2.490111E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 2412kW/5.58COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 2412kW/5.58COP/Vanes, !- Name 2412400, !- Reference Capacity {W} 5.58, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.09085, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 2412kW/5.58COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 2412kW/5.58COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 2412kW/5.58COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.12, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.12, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.12 | Minimum part unload ratio |
Real | PLRMin | 0.12 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2412400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.58 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.473817E-01,8.069214E-03,8... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.626807E-01,-2.305674E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.472427E-01,7.531481E-01,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes, !- Name 2461600, !- Reference Capacity {W} 6.67, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.07066, !- Reference Chilled Water Flow Rate {m3/s} 0.10157, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2461600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.67 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07066 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.10157 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.561527E-01,5.742999E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.462893E-01,2.854651E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.222135E-02,5.830980E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD, !- Name 2567100, !- Reference Capacity {W} 11.77, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.12113, !- Reference Chilled Water Flow Rate {m3/s} 0.15142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.11, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.11, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2567100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 11.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.12113 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.15142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.549428E-01,2.748161E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.561990E-01,-3.333063E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.039419E-01,4.184975E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 2771kW/6.84COP/VSD
Chiller:Electric:EIR, ElectricEIRChiller York YK 2771kW/6.84COP/VSD, !- Name 2771100, !- Reference Capacity {W} 6.84, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.10094, !- Reference Chilled Water Flow Rate {m3/s} 0.15142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 2771kW/6.84COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 2771kW/6.84COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 2771kW/6.84COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2771100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.84 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.10094 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.15142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.734286E-01,4.848829E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.203736E-01,1.030460E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.653354E-02,1.737382E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes, !- Name 2799200, !- Reference Capacity {W} 6.40, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.09893, !- Reference Chilled Water Flow Rate {m3/s} 0.13761, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2799200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.40 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09893 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.13761 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.210324E-01,-2.752320E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.267558E-01,-7.615857E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.023576E-01,-2.893592E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YT 3133kW/9.16COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YT 3133kW/9.16COP/Vanes, !- Name 3133300, !- Reference Capacity {W} 9.16, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.08076, !- Reference Chilled Water Flow Rate {m3/s} 0.12618, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 3133kW/9.16COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 3133kW/9.16COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 3133kW/9.16COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.07, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.07, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.07 | Minimum part unload ratio |
Real | PLRMin | 0.07 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -3133300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.16 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.08076 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.12618 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.607419E-01,1.323998E-02,6... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.150153E-01,-3.956395E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.387579E-01,6.435208E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes, !- Name 3165000, !- Reference Capacity {W} 6.48, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.09085, !- Reference Chilled Water Flow Rate {m3/s} 0.13627, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -3165000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.48 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.13627 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.342558E+00,7.520735E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.347904E-01,6.551597E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.054110E-01,4.090646E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes, !- Name 4019500, !- Reference Capacity {W} 7.35, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.07874, !- Reference Chilled Water Flow Rate {m3/s} 0.09842, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4019500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.35 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07874 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09842 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.958422E-01,3.762768E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.322623E-01,-2.157964E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.763566E-02,5.964012E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 4396kW/6.63COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 4396kW/6.63COP/Vanes, !- Name 4395800, !- Reference Capacity {W} 6.63, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4396kW/6.63COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4396kW/6.63COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4396kW/6.63COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.41, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.41, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4395800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.63 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.693621E-01,-7.284715E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.913358E-01,-5.974145E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.021070E-01,3.103971E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 4477kW/6.64COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 4477kW/6.64COP/Vanes, !- Name 4476700, !- Reference Capacity {W} 6.64, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4477kW/6.64COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4477kW/6.64COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4477kW/6.64COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.41, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.41, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4476700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.64 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.844230E-01,-9.879643E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.264570E-01,-3.391606E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.767206E-01,1.074393E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 4515kW/6.22COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 4515kW/6.22COP/Vanes, !- Name 4515400, !- Reference Capacity {W} 6.22, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4515kW/6.22COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4515kW/6.22COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4515kW/6.22COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4515400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.22 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.732405E-01,-7.176618E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.908290E-01,1.028668E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.870815E-01,3.951784E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 4537kW/6.28COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 4537kW/6.28COP/Vanes, !- Name 4536500, !- Reference Capacity {W} 6.28, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4537kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4537kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4537kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4536500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.418253E-01,8.142292E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.709829E-01,-2.257680E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.528426E-01,2.920280E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes, !- Name 4610300, !- Reference Capacity {W} 6.34, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.19129, !- Reference Chilled Water Flow Rate {m3/s} 0.24757, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4610300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19129 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24757 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.614836E-01,-3.988130E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.415078E-01,-4.779029E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.026691E-01,2.922585E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes, !- Name 4666600, !- Reference Capacity {W} 6.16, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4666600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.16 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.084496E-01,-4.396326E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.214788E-01,-8.218594E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.771252E-01,2.854188E-02,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes, !- Name 4677100, !- Reference Capacity {W} 6.27, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.20138, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.41, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.41, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4677100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.27 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.20138 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.449416E-01,-2.116553E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.283132E-01,-3.030491E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.531562E-01,-2.126229E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 4966kW/6.05COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 4966kW/6.05COP/Vanes, !- Name 4965500, !- Reference Capacity {W} 6.05, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.21198, !- Reference Chilled Water Flow Rate {m3/s} 0.26498, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4966kW/6.05COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4966kW/6.05COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4966kW/6.05COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.12, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.12, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.12 | Minimum part unload ratio |
Real | PLRMin | 0.12 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4965500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.21198 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.746486E-01,-3.051134E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.229769E-01,-8.128614E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.416463E-01,1.947185E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 4969kW/7.14COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 4969kW/7.14COP/Vanes, !- Name 4969000, !- Reference Capacity {W} 7.14, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.17665, !- Reference Chilled Water Flow Rate {m3/s} 0.26498, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4969kW/7.14COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4969kW/7.14COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4969kW/7.14COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.16, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.16, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.16 | Minimum part unload ratio |
Real | PLRMin | 0.16 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4969000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.14 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.817577E-01,-1.012013E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.382162E-01,-5.847442E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.259512E-01,2.320151E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 4969kW/7.07COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 4969kW/7.07COP/Vanes, !- Name 4969000, !- Reference Capacity {W} 7.07, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.17665, !- Reference Chilled Water Flow Rate {m3/s} 0.26498, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4969kW/7.07COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4969kW/7.07COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4969kW/7.07COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.16, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.16, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.16 | Minimum part unload ratio |
Real | PLRMin | 0.16 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4969000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.07 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.803605E-01,-9.685535E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.220087E-01,-4.480691E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.308102E-01,1.802734E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes, !- Name 4997200, !- Reference Capacity {W} 6.40, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4997200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.40 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.122762E-02,2.550937E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.685097E-01,-2.541433E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.364887E-01,2.122607E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes, !- Name 5148400, !- Reference Capacity {W} 6.34, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.18283, !- Reference Chilled Water Flow Rate {m3/s} 0.25526, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5148400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18283 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.25526 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.564454E-01,2.020689E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.426449E-01,3.961314E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.883602E-01,5.018646E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 5170kW/7.15COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 5170kW/7.15COP/Vanes, !- Name 5169500, !- Reference Capacity {W} 7.15, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.17665, !- Reference Chilled Water Flow Rate {m3/s} 0.26498, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 5170kW/7.15COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 5170kW/7.15COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 5170kW/7.15COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.15, !- Minimum Part Load Ratio 1.08, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.15, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.08 | Maximum part load ratio |
Real | PLRMinUnl | 0.15 | Minimum part unload ratio |
Real | PLRMin | 0.15 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5169500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.15 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.675697E-01,-1.191228E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.894383E-01,-2.926530E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.497273E-01,1.011288E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes, !- Name 5208200, !- Reference Capacity {W} 6.88, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.18283, !- Reference Chilled Water Flow Rate {m3/s} 0.25293, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5208200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.88 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18283 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.25293 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.563516E-01,-4.106264E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.198204E-01,-1.523340E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.334262E-01,3.926783E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 5465kW/6.94COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 5465kW/6.94COP/Vanes, !- Name 5464900, !- Reference Capacity {W} 6.94, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.18296, !- Reference Chilled Water Flow Rate {m3/s} 0.27444, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 5465kW/6.94COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 5465kW/6.94COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 5465kW/6.94COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5464900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.94 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18296 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.27444 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.092441E-01,-1.225892E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.396022E-01,-5.954060E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.795792E-01,7.872758E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YK 5549kW/6.50COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller York YK 5549kW/6.50COP/Vanes, !- Name 5549300, !- Reference Capacity {W} 6.50, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.18296, !- Reference Chilled Water Flow Rate {m3/s} 0.27444, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 5549kW/6.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 5549kW/6.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 5549kW/6.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5549300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18296 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.27444 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.402079E-01,1.836029E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.989980E-01,-8.246157E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.336623E-01,1.901320E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.11 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes
Chiller:Electric:EIR, ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes, !- Name 5651300, !- Reference Capacity {W} 5.50, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.18927, !- Reference Chilled Water Flow Rate {m3/s} 0.18927, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5651300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18927 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.18927 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.299676E+00,1.790645E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.853207E-01,-1.652255E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.629327E-01,5.709336E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
DOE-2 Centrifugal/5.50COP
Chiller:Electric:EIR, DOE-2 Centrifugal/5.50COP, !- Name Autosize, !- Reference Capacity {W} 5.5, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.4, !- Reference Entering Condenser Fluid Temperature {C} Autosize, !- Reference Chilled Water Flow Rate {m3/s} Autosize, !- Reference Condenser Water Flow Rate {m3/s} DOE-2 Centrifugal/5.50COP CAPFT, !- Cooling Capacity Function of Temperature Curve Name DOE-2 Centrifugal/5.50COP EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name DOE-2 Centrifugal/5.50COP EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.1, !- Minimum Part Load Ratio 1.0, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.2, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow; !- Chiller Flow Mode
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.0 | Maximum part load ratio |
Real | PLRMinUnl | 0.2 | Minimum part unload ratio |
Real | PLRMin | 0.1 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.4 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -100000.0 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.5 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0022 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0041 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {0.257896E+00,0.389016E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {0.933884E+00,-0.582120E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {0.222903,0.313387,0.463710} | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.0 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.0 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 24.0 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.0 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Multistack MS 172kW/3.67COP/None
Chiller:Electric:EIR, ElectricEIRChiller Multistack MS 172kW/3.67COP/None, !- Name 172300, !- Reference Capacity {W} 3.67, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 18.33, !- Reference Entering Condenser Fluid Temperature {C} 0.00738, !- Reference Chilled Water Flow Rate {m3/s} 0.00959, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Multistack MS 172kW/3.67COP/None CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Multistack MS 172kW/3.67COP/None EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Multistack MS 172kW/3.67COP/None EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 18.33 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -172300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 3.67 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.00738 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.00959 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.839419E-01,1.094957E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.396181E-01,-5.754225E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.747786E-03,1.072374E+00,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
DOE-2 Reciprocating/3.67COP
Chiller:Electric:EIR, DOE-2 Reciprocating/3.67COP, !- Name Autosize, !- Reference Capacity {W} 3.67, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.4, !- Reference Entering Condenser Fluid Temperature {C} Autosize, !- Reference Chilled Water Flow Rate {m3/s} Autosize, !- Reference Condenser Water Flow Rate {m3/s} DOE-2 Reciprocating/3.67COP CAPFT, !- Cooling Capacity Function of Temperature Curve Name DOE-2 Reciprocating/3.67COP EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name DOE-2 Reciprocating/3.67COP EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.1, !- Minimum Part Load Ratio 1.0, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.2, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow; !- Chiller Flow Mode
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.0 | Maximum part load ratio |
Real | PLRMinUnl | 0.2 | Minimum part unload ratio |
Real | PLRMin | 0.1 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.4 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -100000.0 | Reference capacity (negative number) [W] |
Real | COP_nominal | 3.67 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0022 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0044 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {0.507883E+00,0.145228E+00,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {0.103076E+01,-0.103536E+00,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {0.088065,1.137742,-0.225806} | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.0 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.0 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 24.0 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.0 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve, !- Name 383300, !- Reference Capacity {W} 4.17, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.0165, !- Reference Chilled Water Flow Rate {m3/s} 0.02063, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.25, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.25, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.25 | Minimum part unload ratio |
Real | PLRMin | 0.25 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -383300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.17 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0165 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02063 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.830684E-01,3.676199E-02,5... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.228513E-01,-8.700783E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.295553E-02,9.114398E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve, !- Name 531000, !- Reference Capacity {W} 4.83, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.0135, !- Reference Chilled Water Flow Rate {m3/s} 0.01577, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -531000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.83 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0135 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01577 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.434012E-01,1.630729E-02,8... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.524778E-01,1.045156E-04,6... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.980020E-01,2.733157E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve, !- Name 538000, !- Reference Capacity {W} 5.12, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.01375, !- Reference Chilled Water Flow Rate {m3/s} 0.01956, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -538000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.12 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01375 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.344780E-01,2.760000E-02,3... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.455087E-01,-9.301201E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.816950E-01,3.731838E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve, !- Name 541500, !- Reference Capacity {W} 5.26, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 21.11, !- Reference Entering Condenser Fluid Temperature {C} 0.01363, !- Reference Chilled Water Flow Rate {m3/s} 0.01577, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -541500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.26 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01363 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01577 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.226438E-01,2.878831E-02,3... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.953775E-01,-1.359340E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.057645E-01,-1.548084E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YS 672kW/7.90COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller York YS 672kW/7.90COP/Valve, !- Name 671600, !- Reference Capacity {W} 7.90, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 15.56, !- Reference Entering Condenser Fluid Temperature {C} 0.01514, !- Reference Chilled Water Flow Rate {m3/s} 0.0241, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 672kW/7.90COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 672kW/7.90COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 672kW/7.90COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -671600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.90 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01514 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0241 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.274375E-01,2.846559E-02,4... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.069331E-01,-6.420922E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.936152E-01,3.375574E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve, !- Name 685700, !- Reference Capacity {W} 5.91, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 23.74, !- Reference Entering Condenser Fluid Temperature {C} 0.0571, !- Reference Chilled Water Flow Rate {m3/s} 0.03255, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.74 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -685700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.91 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03255 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.903523E-01,-2.676742E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.014060E-01,1.561000E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.113934E-01,4.190226E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve, !- Name 706800, !- Reference Capacity {W} 7.77, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 15.56, !- Reference Entering Condenser Fluid Temperature {C} 0.04921, !- Reference Chilled Water Flow Rate {m3/s} 0.03268, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.28, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.28, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.28 | Minimum part unload ratio |
Real | PLRMin | 0.28 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -706800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04921 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03268 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.362925E-01,2.940722E-02,5... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.497944E-01,6.883157E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.997099E-01,6.754676E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 11.11 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YS 756kW/7.41COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller York YS 756kW/7.41COP/Valve, !- Name 756000, !- Reference Capacity {W} 7.41, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 16.06, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 756kW/7.41COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 756kW/7.41COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 756kW/7.41COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.11, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.11, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 16.06 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -756000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.41 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.432455E-01,2.794778E-02,2... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.917947E-01,-1.929936E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.929778E-01,1.673799E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 16.06 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YS 781kW/5.42COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller York YS 781kW/5.42COP/Valve, !- Name 780700, !- Reference Capacity {W} 5.42, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.01893, !- Reference Chilled Water Flow Rate {m3/s} 0.03785, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 781kW/5.42COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 781kW/5.42COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 781kW/5.42COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -780700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.42 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01893 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03785 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.002148E+00,3.300191E-02,3... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.475957E-01,-1.054652E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.519108E-01,2.756914E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve, !- Name 829900, !- Reference Capacity {W} 6.97, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.04744, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -829900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.97 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.198506E-01,4.299516E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.610959E-01,-1.560459E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.307464E-01,7.784162E-01,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 14.17 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve, !- Name 861500, !- Reference Capacity {W} 6.11, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.04296, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -861500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.11 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04296 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-3.646458E-02,-6.061334E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.420642E-01,-2.110032E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.292819E-01,3.662723E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve, !- Name 861500, !- Reference Capacity {W} 6.84, !- Reference COP {W/W} 9.69, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.04296, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -861500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.84 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04296 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.69 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-4.535842E-02,-6.253871E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.930611E-01,-2.082914E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.145826E-01,7.340475E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve, !- Name 865100, !- Reference Capacity {W} 6.05, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.03716, !- Reference Chilled Water Flow Rate {m3/s} 0.04366, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -865100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03716 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04366 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.079758E-01,-2.344768E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.437328E-01,7.625344E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.545235E-01,3.104981E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YS 879kW/5.82COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller York YS 879kW/5.82COP/Valve, !- Name 879100, !- Reference Capacity {W} 5.82, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.03785, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 879kW/5.82COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 879kW/5.82COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 879kW/5.82COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -879100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.82 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.031429E+00,3.364723E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.595308E-01,-1.087985E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.029493E-01,3.223124E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve, !- Name 1009200, !- Reference Capacity {W} 5.37, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.86, !- Reference Entering Condenser Fluid Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.04618, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 24.86 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1009200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.37 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04618 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.134633E+00,3.267210E-02,5... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.383883E-01,7.754235E-03,6... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.316727E-01,1.013111E+00,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 19.97 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.86 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve, !- Name 1051400, !- Reference Capacity {W} 5.05, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.04527, !- Reference Chilled Water Flow Rate {m3/s} 0.05659, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1051400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04527 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05659 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.482157E-01,3.306737E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.904181E-01,-5.530317E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.590465E-01,2.148987E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve, !- Name 1062000, !- Reference Capacity {W} 5.50, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.04573, !- Reference Chilled Water Flow Rate {m3/s} 0.05716, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1062000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04573 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05716 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.025695E+00,2.327484E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.634070E-01,-7.025220E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.576261E-01,3.416910E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 21.11 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve, !- Name 1065500, !- Reference Capacity {W} 5.73, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 25.28, !- Reference Entering Condenser Fluid Temperature {C} 0.05142, !- Reference Chilled Water Flow Rate {m3/s} 0.04416, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 25.28 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1065500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.73 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05142 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04416 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.062396E+00,4.575299E-02,2... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.003080E-01,3.783201E-03,9... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.007344E-01,1.119205E+00,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 20.07 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 25.28 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve, !- Name 1093600, !- Reference Capacity {W} 6.55, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.33, !- Reference Entering Condenser Fluid Temperature {C} 0.04921, !- Reference Chilled Water Flow Rate {m3/s} 0.04524, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.25, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.25, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.25 | Minimum part unload ratio |
Real | PLRMin | 0.25 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.33 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1093600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.55 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04921 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04524 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.643756E-01,3.820069E-02,4... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.579136E-01,-1.133448E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.626466E-01,7.903550E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve, !- Name 1107700, !- Reference Capacity {W} 6.92, !- Reference COP {W/W} 8.97, !- Reference Leaving Chilled Water Temperature {C} 23.74, !- Reference Entering Condenser Fluid Temperature {C} 0.0571, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.74 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1107700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.92 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.97 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.631328E-01,-1.027433E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.668296E-01,-2.800906E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.370745E-01,8.374817E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YS 1171kW/9.15COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller York YS 1171kW/9.15COP/Valve, !- Name 1171000, !- Reference Capacity {W} 9.15, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 15.56, !- Reference Entering Condenser Fluid Temperature {C} 0.03249, !- Reference Chilled Water Flow Rate {m3/s} 0.05173, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 1171kW/9.15COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 1171kW/9.15COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 1171kW/9.15COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1171000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.15 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03249 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05173 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.299045E-01,2.350383E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.325834E-01,-2.611733E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.889392E-01,4.684305E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve, !- Name 1195600, !- Reference Capacity {W} 6.39, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.03653, !- Reference Chilled Water Flow Rate {m3/s} 0.04271, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1195600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03653 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04271 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.775948E-01,2.206074E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.077824E-01,-1.608447E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.061065E-01,7.305514E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YS 1554kW/9.31COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller York YS 1554kW/9.31COP/Valve, !- Name 1554300, !- Reference Capacity {W} 9.31, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 15.56, !- Reference Entering Condenser Fluid Temperature {C} 0.0424, !- Reference Chilled Water Flow Rate {m3/s} 0.07949, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 1554kW/9.31COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 1554kW/9.31COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 1554kW/9.31COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1554300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.31 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0424 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07949 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.083027E+00,9.278069E-03,1... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.099117E-01,1.379553E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.720219E-01,5.084848E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller York YS 1758kW/5.84COP/Valve
Chiller:Electric:EIR, ElectricEIRChiller York YS 1758kW/5.84COP/Valve, !- Name 1758300, !- Reference Capacity {W} 5.84, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 1758kW/5.84COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 1758kW/5.84COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 1758kW/5.84COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.84 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.130185E-01,-1.425368E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.381264E-01,6.304193E-03,9... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.149879E-01,3.171267E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
ElectricEIRChiller Trane CGWD 207kW/3.99COP/None
Chiller:Electric:EIR, ElectricEIRChiller Trane CGWD 207kW/3.99COP/None, !- Name 207400, !- Reference Capacity {W} 3.99, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.00898, !- Reference Chilled Water Flow Rate {m3/s} 0.01122, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CGWD 207kW/3.99COP/None CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CGWD 207kW/3.99COP/None EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CGWD 207kW/3.99COP/None EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.25, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.25, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.25 | Minimum part unload ratio |
Real | PLRMin | 0.25 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -207400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 3.99 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.00898 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01122 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.441897E-01,3.371079E-02,9... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.273870E-01,-1.189276E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.146742E-02,6.543795E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |