LBL logo

Buildings.Fluid.Chillers

Package with chiller models

Information

This package contains components models for chillers.

Extends from Modelica.Icons.VariantsPackage (Icon for package containing variants).

Package Content

Name Description
Buildings.Fluid.Chillers.Carnot_TEva Carnot_TEva Chiller with prescribed evaporator leaving temperature and performance curve adjusted based on Carnot efficiency
Buildings.Fluid.Chillers.Carnot_y Carnot_y Chiller with performance curve adjusted based on Carnot efficiency
Buildings.Fluid.Chillers.ElectricEIR ElectricEIR Electric chiller based on the DOE-2.1 model
Buildings.Fluid.Chillers.ElectricReformulatedEIR ElectricReformulatedEIR Electric chiller based on the DOE-2.1 model, but with performance as a function of condenser leaving instead of entering temperature
Buildings.Fluid.Chillers.Data Data Performance data for electric chillers
Buildings.Fluid.Chillers.Examples Examples Collection of models that illustrate model use and test models
Buildings.Fluid.Chillers.Validation Validation Collection of models that validate the chiller models
Buildings.Fluid.Chillers.BaseClasses BaseClasses Package with base classes for Buildings.Fluid.Chillers

Buildings.Fluid.Chillers.Carnot_TEva Buildings.Fluid.Chillers.Carnot_TEva

Chiller with prescribed evaporator leaving temperature and performance curve adjusted based on Carnot efficiency

Buildings.Fluid.Chillers.Carnot_TEva

Information

This is a model of a chiller whose coefficient of performance COP changes with temperatures in the same way as the Carnot efficiency changes. The control input is the setpoint of the evaporator leaving temperature, which is met exactly at steady state if the chiller has sufficient capacity.

The model allows to either specify the Carnot effectivness ηCarnot,0, or a COP0 at the nominal conditions, together with the evaporator temperature Teva,0 and the condenser temperature Tcon,0, in which case the model computes the Carnot effectivness as

ηCarnot,0 = COP0 ⁄ (Teva,0 ⁄ (Tcon,0-Teva,0)).

On the Advanced tab, a user can specify the temperatures that will be used as the evaporator and condenser temperature.

During the simulation, the chiller COP is computed as the product

COP = ηCarnot,0 COPCarnot ηPL,

where COPCarnot is the Carnot efficiency and ηPL is a polynomial in the cooling part load ratio yPL that can be used to take into account a change in COP at part load conditions. This polynomial has the form

ηPL = a1 + a2 yPL + a3 yPL2 + ...

where the coefficients ai are declared by the parameter a.

On the Dynamics tag, the model can be parametrized to compute a transient or steady-state response. The transient response of the model is computed using a first order differential equation for the evaporator and condenser fluid volumes. The chiller outlet temperatures are equal to the temperatures of these lumped volumes.

Typical use and important parameters

When using this component, make sure that the condenser has sufficient mass flow rate. Based on the evaporator mass flow rate, temperature difference and the efficiencies, the model computes how much heat will be added to the condenser. If the mass flow rate is too small, very high outlet temperatures can result.

The evaporator heat flow rate QEva_flow_nominal is used to assign the default value for the mass flow rates, which are used for the pressure drop calculations. It is also used to compute the part load efficiency. Hence, make sure that QEva_flow_nominal is set to a reasonable value.

The maximum cooling capacity is set by the parameter QEva_flow_min, which is by default set to negative infinity.

By default, the coefficient of performance depends on the evaporator leaving temperature and the condenser entering temperature. This can be changed with the parameters effInpEva and effInpCon.

Notes

For a similar model that can be used as a heat pump, see Buildings.Fluid.HeatPumps.Examples.Carnot_TCon.

Extends from Buildings.Fluid.Chillers.BaseClasses.PartialCarnot_T (Partial model for chiller with performance curve adjusted based on Carnot efficiency).

Parameters

TypeNameDefaultDescription
replaceable package Medium1PartialMediumMedium 1 in the component
replaceable package Medium2PartialMediumMedium 2 in the component
HeatFlowRateQEva_flow_min-Modelica.Constants.infMaximum heat flow rate for cooling (negative) [W]
Nominal condition
MassFlowRatem1_flow_nominalQCon_flow_nominal/cp1_defaul...Nominal mass flow rate [kg/s]
MassFlowRatem2_flow_nominalQEva_flow_nominal/cp2_defaul...Nominal mass flow rate [kg/s]
HeatFlowRateQEva_flow_nominal Nominal cooling heat flow rate (QEva_flow_nominal < 0) [W]
HeatFlowRateQCon_flow_nominal-QEva_flow_nominal*(1 + COP_...Nominal heating flow rate [W]
TemperatureDifferencedTEva_nominal-10Temperature difference evaporator outlet-inlet [K]
TemperatureDifferencedTCon_nominal10Temperature difference condenser outlet-inlet [K]
Pressuredp1_nominal Pressure difference over condenser [Pa]
Pressuredp2_nominal Pressure difference over evaporator [Pa]
Initialization
MassFlowRatem1_flow.start0Mass flow rate from port_a1 to port_b1 (m1_flow > 0 is design flow direction) [kg/s]
PressureDifferencedp1.start0Pressure difference between port_a1 and port_b1 [Pa]
MassFlowRatem2_flow.start0Mass flow rate from port_a2 to port_b2 (m2_flow > 0 is design flow direction) [kg/s]
PressureDifferencedp2.start0Pressure difference between port_a2 and port_b2 [Pa]
Efficiency
Booleanuse_eta_Carnot_nominaltrueSet to true to use Carnot effectiveness etaCarnot_nominal rather than COP_nominal
RealetaCarnot_nominalCOP_nominal/(TUse_nominal/(T...Carnot effectiveness (=COP/COP_Carnot) used if use_eta_Carnot_nominal = true [1]
RealCOP_nominaletaCarnot_nominal*TUse_nomin...Coefficient of performance at TEva_nominal and TCon_nominal, used if use_eta_Carnot_nominal = false [1]
TemperatureTCon_nominal303.15Condenser temperature used to compute COP_nominal if use_eta_Carnot_nominal=false [K]
TemperatureTEva_nominal278.15Evaporator temperature used to compute COP_nominal if use_eta_Carnot_nominal=false [K]
Reala[:]{1}Coefficients for efficiency curve (need p(a=a, yPL=1)=1)
Assumptions
BooleanallowFlowReversal1true= true to allow flow reversal in medium 1, false restricts to design direction (port_a -> port_b)
BooleanallowFlowReversal2true= true to allow flow reversal in medium 2, false restricts to design direction (port_a -> port_b)
Advanced
MassFlowRatem1_flow_small1E-4*abs(m1_flow_nominal)Small mass flow rate for regularization of zero flow [kg/s]
MassFlowRatem2_flow_small1E-4*abs(m2_flow_nominal)Small mass flow rate for regularization of zero flow [kg/s]
BooleanhomotopyInitializationtrue= true, use homotopy method
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at port is computed
Temperature dependence
EfficiencyInputeffInpEvaBuildings.Fluid.Types.Effici...Temperatures of evaporator fluid used to compute Carnot efficiency
EfficiencyInputeffInpConBuildings.Fluid.Types.Effici...Temperatures of condenser fluid used to compute Carnot efficiency
Flow resistance
Condenser
Booleanfrom_dp1false= true, use m_flow = f(dp) else dp = f(m_flow)
BooleanlinearizeFlowResistance1false= true, use linear relation between m_flow and dp for any flow rate
RealdeltaM10.1Fraction of nominal flow rate where flow transitions to laminar [1]
Evaporator
Booleanfrom_dp2false= true, use m_flow = f(dp) else dp = f(m_flow)
BooleanlinearizeFlowResistance2false= true, use linear relation between m_flow and dp for any flow rate
RealdeltaM20.1Fraction of nominal flow rate where flow transitions to laminar [1]
Dynamics
Condenser
Timetau160Time constant at nominal flow rate (used if energyDynamics1 <> Modelica.Fluid.Types.Dynamics.SteadyState) [s]
TemperatureT1_startMedium1.T_defaultInitial or guess value of set point [K]
Evaporator
Timetau260Time constant at nominal flow rate (used if energyDynamics2 <> Modelica.Fluid.Types.Dynamics.SteadyState) [s]
TemperatureT2_startMedium2.T_defaultInitial or guess value of set point [K]
Evaporator and condenser
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state

Connectors

TypeNameDescription
FluidPort_aport_a1Fluid connector a1 (positive design flow direction is from port_a1 to port_b1)
FluidPort_bport_b1Fluid connector b1 (positive design flow direction is from port_a1 to port_b1)
FluidPort_aport_a2Fluid connector a2 (positive design flow direction is from port_a2 to port_b2)
FluidPort_bport_b2Fluid connector b2 (positive design flow direction is from port_a2 to port_b2)
output RealOutputQCon_flowActual heating heat flow rate added to fluid 1 [W]
output RealOutputPElectric power consumed by compressor [W]
output RealOutputQEva_flowActual cooling heat flow rate removed from fluid 2 [W]
input RealInputTSetEvaporator leaving water temperature [K]

Modelica definition

model Carnot_TEva "Chiller with prescribed evaporator leaving temperature and performance curve adjusted based on Carnot efficiency" extends Buildings.Fluid.Chillers.BaseClasses.PartialCarnot_T( final COP_is_for_cooling = true, final QCon_flow_nominal = -QEva_flow_nominal*(1 + COP_nominal)/COP_nominal, effInpEva=Buildings.Fluid.Types.EfficiencyInput.port_b, effInpCon=Buildings.Fluid.Types.EfficiencyInput.port_a, PEle(y=-QEva_flow/COP), redeclare HeatExchangers.HeaterCooler_u con( final from_dp=from_dp1, final dp_nominal=dp1_nominal, final linearizeFlowResistance=linearizeFlowResistance1, final deltaM=deltaM1, final tau=tau1, final T_start=T1_start, final energyDynamics=energyDynamics, final homotopyInitialization=homotopyInitialization, final Q_flow_nominal=QCon_flow_nominal), redeclare HeatExchangers.HeaterCooler_T eva( final from_dp=from_dp2, final dp_nominal=dp2_nominal, final linearizeFlowResistance=linearizeFlowResistance2, final deltaM=deltaM2, final Q_flow_maxHeat=0, final Q_flow_maxCool=QEva_flow_min, final tau=tau2, final T_start=T2_start, final energyDynamics=energyDynamics, final homotopyInitialization=homotopyInitialization)); parameter Modelica.SIunits.HeatFlowRate QEva_flow_min( max=0) = -Modelica.Constants.inf "Maximum heat flow rate for cooling (negative)"; Modelica.Blocks.Interfaces.RealInput TSet(unit="K") "Evaporator leaving water temperature"; protected Modelica.Blocks.Math.Gain yCon(final k=1/QCon_flow_nominal) "Normalized condenser heat flow rate"; Modelica.Blocks.Math.Add QCon_flow_internal(final k1=-1) "Heat added to condenser"; initial equation assert(QEva_flow_nominal < 0, "Parameter QEva_flow_nominal must be negative."); equation connect(TSet, eva.TSet); connect(eva.Q_flow, QEva_flow); connect(QCon_flow_internal.y, yCon.u); connect(yCon.y, con.u); connect(QCon_flow_internal.y, QCon_flow); connect(QCon_flow_internal.u1, eva.Q_flow); connect(QCon_flow_internal.u2, PEle.y); end Carnot_TEva;

Buildings.Fluid.Chillers.Carnot_y Buildings.Fluid.Chillers.Carnot_y

Chiller with performance curve adjusted based on Carnot efficiency

Buildings.Fluid.Chillers.Carnot_y

Information

This is model of a chiller whose coefficient of performance COP changes with temperatures in the same way as the Carnot efficiency changes. The input signal y is the control signal for the compressor.

The model allows to either specify the Carnot effectivness ηCarnot,0, or a COP0 at the nominal conditions, together with the evaporator temperature Teva,0 and the condenser temperature Tcon,0, in which case the model computes the Carnot effectivness as

ηCarnot,0 = COP0 ⁄ (Teva,0 ⁄ (Tcon,0-Teva,0)).

The chiller COP is computed as the product

COP = ηCarnot,0 COPCarnot ηPL,

where COPCarnot is the Carnot efficiency and ηPL is a polynomial in the cooling part load ratio yPL that can be used to take into account a change in COP at part load conditions. This polynomial has the form

ηPL = a1 + a2 yPL + a3 yPL2 + ...

where the coefficients ai are declared by the parameter a.

On the Dynamics tag, the model can be parametrized to compute a transient or steady-state response. The transient response of the model is computed using a first order differential equation for the evaporator and condenser fluid volumes. The chiller outlet temperatures are equal to the temperatures of these lumped volumes.

Typical use and important parameters

When using this component, make sure that the evaporator and the condenser have sufficient mass flow rate. Based on the mass flow rates, the compressor power, temperature difference and the efficiencies, the model computes how much heat will be added to the condenser and removed at the evaporator. If the mass flow rates are too small, very high temperature differences can result.

The evaporator heat flow rate QEva_flow_nominal is used to assign the default value for the mass flow rates, which are used for the pressure drop calculations. It is also used to compute the part load efficiency. Hence, make sure that QEva_flow_nominal is set to a reasonable value.

The maximum cooling capacity is set by the parameter QEva_flow_min, which is by default set to negative infinity.

By default, the coefficient of performance depends on the evaporator leaving temperature and the condenser entering temperature. This can be changed with the parameters effInpEva and effInpCon.

Notes

For a similar model that can be used as a heat pump, see Buildings.Fluid.HeatPumps.Carnot_y.

Extends from Buildings.Fluid.Chillers.BaseClasses.PartialCarnot_y (Partial chiller model with performance curve adjusted based on Carnot efficiency).

Parameters

TypeNameDefaultDescription
replaceable package Medium1PartialMediumMedium 1 in the component
replaceable package Medium2PartialMediumMedium 2 in the component
Nominal condition
MassFlowRatem1_flow_nominalQCon_flow_nominal/cp1_defaul...Nominal mass flow rate [kg/s]
MassFlowRatem2_flow_nominalQEva_flow_nominal/cp2_defaul...Nominal mass flow rate [kg/s]
TemperatureDifferencedTEva_nominal-10Temperature difference evaporator outlet-inlet [K]
TemperatureDifferencedTCon_nominal10Temperature difference condenser outlet-inlet [K]
Pressuredp1_nominal Pressure difference over condenser [Pa]
Pressuredp2_nominal Pressure difference over evaporator [Pa]
PowerP_nominal Nominal compressor power (at y=1) [W]
Initialization
MassFlowRatem1_flow.start0Mass flow rate from port_a1 to port_b1 (m1_flow > 0 is design flow direction) [kg/s]
PressureDifferencedp1.start0Pressure difference between port_a1 and port_b1 [Pa]
MassFlowRatem2_flow.start0Mass flow rate from port_a2 to port_b2 (m2_flow > 0 is design flow direction) [kg/s]
PressureDifferencedp2.start0Pressure difference between port_a2 and port_b2 [Pa]
Efficiency
Booleanuse_eta_Carnot_nominaltrueSet to true to use Carnot effectiveness etaCarnot_nominal rather than COP_nominal
RealetaCarnot_nominalCOP_nominal/(TUse_nominal/(T...Carnot effectiveness (=COP/COP_Carnot) used if use_eta_Carnot_nominal = true [1]
RealCOP_nominaletaCarnot_nominal*TUse_nomin...Coefficient of performance at TEva_nominal and TCon_nominal, used if use_eta_Carnot_nominal = false [1]
TemperatureTCon_nominal303.15Condenser temperature used to compute COP_nominal if use_eta_Carnot_nominal=false [K]
TemperatureTEva_nominal278.15Evaporator temperature used to compute COP_nominal if use_eta_Carnot_nominal=false [K]
Reala[:]{1}Coefficients for efficiency curve (need p(a=a, yPL=1)=1)
Assumptions
BooleanallowFlowReversal1true= true to allow flow reversal in medium 1, false restricts to design direction (port_a -> port_b)
BooleanallowFlowReversal2true= true to allow flow reversal in medium 2, false restricts to design direction (port_a -> port_b)
Advanced
MassFlowRatem1_flow_small1E-4*abs(m1_flow_nominal)Small mass flow rate for regularization of zero flow [kg/s]
MassFlowRatem2_flow_small1E-4*abs(m2_flow_nominal)Small mass flow rate for regularization of zero flow [kg/s]
BooleanhomotopyInitializationtrue= true, use homotopy method
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at port is computed
Temperature dependence
EfficiencyInputeffInpEvaBuildings.Fluid.Types.Effici...Temperatures of evaporator fluid used to compute Carnot efficiency
EfficiencyInputeffInpConBuildings.Fluid.Types.Effici...Temperatures of condenser fluid used to compute Carnot efficiency
Flow resistance
Condenser
Booleanfrom_dp1false= true, use m_flow = f(dp) else dp = f(m_flow)
BooleanlinearizeFlowResistance1false= true, use linear relation between m_flow and dp for any flow rate
RealdeltaM10.1Fraction of nominal flow rate where flow transitions to laminar [1]
Evaporator
Booleanfrom_dp2false= true, use m_flow = f(dp) else dp = f(m_flow)
BooleanlinearizeFlowResistance2false= true, use linear relation between m_flow and dp for any flow rate
RealdeltaM20.1Fraction of nominal flow rate where flow transitions to laminar [1]
Dynamics
Condenser
Timetau160Time constant at nominal flow rate (used if energyDynamics1 <> Modelica.Fluid.Types.Dynamics.SteadyState) [s]
TemperatureT1_startMedium1.T_defaultInitial or guess value of set point [K]
Evaporator
Timetau260Time constant at nominal flow rate (used if energyDynamics2 <> Modelica.Fluid.Types.Dynamics.SteadyState) [s]
TemperatureT2_startMedium2.T_defaultInitial or guess value of set point [K]
Evaporator and condenser
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state

Connectors

TypeNameDescription
FluidPort_aport_a1Fluid connector a1 (positive design flow direction is from port_a1 to port_b1)
FluidPort_bport_b1Fluid connector b1 (positive design flow direction is from port_a1 to port_b1)
FluidPort_aport_a2Fluid connector a2 (positive design flow direction is from port_a2 to port_b2)
FluidPort_bport_b2Fluid connector b2 (positive design flow direction is from port_a2 to port_b2)
output RealOutputQCon_flowActual heating heat flow rate added to fluid 1 [W]
output RealOutputPElectric power consumed by compressor [W]
output RealOutputQEva_flowActual cooling heat flow rate removed from fluid 2 [W]
input RealInputyPart load ratio of compressor [1]

Modelica definition

model Carnot_y "Chiller with performance curve adjusted based on Carnot efficiency" extends Buildings.Fluid.Chillers.BaseClasses.PartialCarnot_y( final COP_is_for_cooling = true, effInpEva=Buildings.Fluid.Types.EfficiencyInput.port_b, effInpCon=Buildings.Fluid.Types.EfficiencyInput.port_a); end Carnot_y;

Buildings.Fluid.Chillers.ElectricEIR Buildings.Fluid.Chillers.ElectricEIR

Electric chiller based on the DOE-2.1 model

Buildings.Fluid.Chillers.ElectricEIR

Information

Model of an electric chiller, based on the DOE-2.1 chiller model and the EnergyPlus chiller model Chiller:Electric:EIR.

This model uses three functions to predict capacity and power consumption:

These curves are stored in the data record per and are available from Buildings.Fluid.Chillers.Data.ElectricEIR. Additional performance curves can be developed using two available techniques (Hydeman and Gillespie, 2002). The first technique is called the Least-squares Linear Regression method and is used when sufficient performance data exist to employ standard least-square linear regression techniques. The second technique is called Reference Curve Method and is used when insufficient performance data exist to apply linear regression techniques. A detailed description of both techniques can be found in Hydeman and Gillespie (2002).

The model takes as an input the set point for the leaving chilled water temperature, which is met if the chiller has sufficient capacity. Thus, the model has a built-in, ideal temperature control. The model has three tests on the part load ratio and the cycling ratio:

  1. The test
      PLR1 =min(QEva_flow_set/QEva_flow_ava, per.PLRMax);
    
    ensures that the chiller capacity does not exceed the chiller capacity specified by the parameter per.PLRMax.
  2. The test
      CR = min(PLR1/per.PRLMin, 1.0);
    
    computes a cycling ratio. This ratio expresses the fraction of time that a chiller would run if it were to cycle because its load is smaller than the minimal load at which it can operate. Note that this model continuously operates even if the part load ratio is below the minimum part load ratio. Its leaving evaporator and condenser temperature can therefore be considered as an average temperature between the modes where the compressor is off and on.
  3. The test
      PLR2 = max(per.PLRMinUnl, PLR1);
    
    computes the part load ratio of the compressor. The assumption is that for a part load ratio below per.PLRMinUnl, the chiller uses hot gas bypass to reduce the capacity, while the compressor power draw does not change.

The electric power only contains the power for the compressor, but not any power for pumps or fans.

The model can be parametrized to compute a transient or steady-state response. The transient response of the boiler is computed using a first order differential equation for the evaporator and condenser fluid volumes. The chiller outlet temperatures are equal to the temperatures of these lumped volumes.

References

Extends from Buildings.Fluid.Chillers.BaseClasses.PartialElectric (Partial model for electric chiller based on the model in DOE-2, CoolTools and EnergyPlus).

Parameters

TypeNameDefaultDescription
replaceable package Medium1PartialMediumMedium 1 in the component
replaceable package Medium2PartialMediumMedium 2 in the component
Genericper Performance data
Nominal condition
MassFlowRatem1_flow_nominalmCon_flow_nominalNominal mass flow rate [kg/s]
MassFlowRatem2_flow_nominalmEva_flow_nominalNominal mass flow rate [kg/s]
PressureDifferencedp1_nominal Pressure difference [Pa]
PressureDifferencedp2_nominal Pressure difference [Pa]
Initialization
MassFlowRatem1_flow.start0Mass flow rate from port_a1 to port_b1 (m1_flow > 0 is design flow direction) [kg/s]
PressureDifferencedp1.start0Pressure difference between port_a1 and port_b1 [Pa]
MassFlowRatem2_flow.start0Mass flow rate from port_a2 to port_b2 (m2_flow > 0 is design flow direction) [kg/s]
PressureDifferencedp2.start0Pressure difference between port_a2 and port_b2 [Pa]
RealcapFunT.start1Cooling capacity factor function of temperature curve [1]
EfficiencyEIRFunT.start1Power input to cooling capacity ratio function of temperature curve [1]
EfficiencyEIRFunPLR.start1Power input to cooling capacity ratio function of part load ratio [1]
RealPLR1.start1Part load ratio [1]
RealPLR2.start1Part load ratio [1]
RealCR.start1Cycling ratio [1]
Assumptions
BooleanallowFlowReversal1true= true to allow flow reversal in medium 1, false restricts to design direction (port_a -> port_b)
BooleanallowFlowReversal2true= true to allow flow reversal in medium 2, false restricts to design direction (port_a -> port_b)
Advanced
MassFlowRatem1_flow_small1E-4*abs(m1_flow_nominal)Small mass flow rate for regularization of zero flow [kg/s]
MassFlowRatem2_flow_small1E-4*abs(m2_flow_nominal)Small mass flow rate for regularization of zero flow [kg/s]
BooleanhomotopyInitializationtrue= true, use homotopy method
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at port is computed
Flow resistance
Medium 1
Booleanfrom_dp1false= true, use m_flow = f(dp) else dp = f(m_flow)
BooleanlinearizeFlowResistance1false= true, use linear relation between m_flow and dp for any flow rate
RealdeltaM10.1Fraction of nominal flow rate where flow transitions to laminar
Medium 2
Booleanfrom_dp2false= true, use m_flow = f(dp) else dp = f(m_flow)
BooleanlinearizeFlowResistance2false= true, use linear relation between m_flow and dp for any flow rate
RealdeltaM20.1Fraction of nominal flow rate where flow transitions to laminar
Dynamics
Nominal condition
Timetau130Time constant at nominal flow [s]
Timetau230Time constant at nominal flow [s]
Equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
DynamicsmassDynamicsenergyDynamicsType of mass balance: dynamic (3 initialization options) or steady state
Initialization
Medium 1
AbsolutePressurep1_startMedium1.p_defaultStart value of pressure [Pa]
TemperatureT1_start273.15 + 25Start value of temperature [K]
MassFractionX1_start[Medium1.nX]Medium1.X_defaultStart value of mass fractions m_i/m [kg/kg]
ExtraPropertyC1_start[Medium1.nC]fill(0, Medium1.nC)Start value of trace substances
ExtraPropertyC1_nominal[Medium1.nC]fill(1E-2, Medium1.nC)Nominal value of trace substances. (Set to typical order of magnitude.)
Medium 2
AbsolutePressurep2_startMedium2.p_defaultStart value of pressure [Pa]
TemperatureT2_start273.15 + 5Start value of temperature [K]
MassFractionX2_start[Medium2.nX]Medium2.X_defaultStart value of mass fractions m_i/m [kg/kg]
ExtraPropertyC2_start[Medium2.nC]fill(0, Medium2.nC)Start value of trace substances
ExtraPropertyC2_nominal[Medium2.nC]fill(1E-2, Medium2.nC)Nominal value of trace substances. (Set to typical order of magnitude.)

Connectors

TypeNameDescription
FluidPort_aport_a1Fluid connector a1 (positive design flow direction is from port_a1 to port_b1)
FluidPort_bport_b1Fluid connector b1 (positive design flow direction is from port_a1 to port_b1)
FluidPort_aport_a2Fluid connector a2 (positive design flow direction is from port_a2 to port_b2)
FluidPort_bport_b2Fluid connector b2 (positive design flow direction is from port_a2 to port_b2)
input BooleanInputonSet to true to enable compressor, or false to disable compressor
input RealInputTSetSet point for leaving chilled water temperature [K]
output RealOutputPElectric power consumed by compressor [W]

Modelica definition

model ElectricEIR "Electric chiller based on the DOE-2.1 model" extends Buildings.Fluid.Chillers.BaseClasses.PartialElectric( final QEva_flow_nominal = per.QEva_flow_nominal, final COP_nominal= per.COP_nominal, final PLRMax= per.PLRMax, final PLRMinUnl= per.PLRMinUnl, final PLRMin= per.PLRMin, final etaMotor= per.etaMotor, final mEva_flow_nominal= per.mEva_flow_nominal, final mCon_flow_nominal= per.mCon_flow_nominal, final TEvaLvg_nominal= per.TEvaLvg_nominal); parameter Buildings.Fluid.Chillers.Data.ElectricEIR.Generic per "Performance data"; protected final parameter Modelica.SIunits.Conversions.NonSIunits.Temperature_degC TConEnt_nominal_degC= Modelica.SIunits.Conversions.to_degC(per.TConEnt_nominal) "Temperature of fluid entering condenser at nominal condition"; Modelica.SIunits.Conversions.NonSIunits.Temperature_degC TConEnt_degC "Temperature of fluid entering condenser"; initial equation // Verify correctness of performance curves, and write warning if error is bigger than 10% Buildings.Fluid.Chillers.BaseClasses.warnIfPerformanceOutOfBounds( Buildings.Utilities.Math.Functions.biquadratic(a=per.capFunT, x1=TEvaLvg_nominal_degC, x2=TConEnt_nominal_degC), "Capacity as function of temperature ", "per.capFunT"); equation TConEnt_degC=Modelica.SIunits.Conversions.to_degC(TConEnt); if on then // Compute the chiller capacity fraction, using a biquadratic curve. // Since the regression for capacity can have negative values (for unreasonable temperatures), // we constrain its return value to be non-negative. This prevents the solver to pick the // unrealistic solution. capFunT = Buildings.Utilities.Math.Functions.smoothMax( x1= 1E-6, x2= Buildings.Utilities.Math.Functions.biquadratic(a=per.capFunT, x1=TEvaLvg_degC, x2=TConEnt_degC), deltaX= 1E-7); /* assert(capFunT > 0.1, "Error: Received capFunT = " + String(capFunT) + ".\n" + "Coefficient for polynomial seem to be not valid for the encountered temperature range.\n" + "Temperatures are TConEnt_degC = " + String(TConEnt_degC) + " degC\n" + " TEvaLvg_degC = " + String(TEvaLvg_degC) + " degC"); */ // Chiller energy input ratio biquadratic curve. EIRFunT = Buildings.Utilities.Math.Functions.biquadratic(a=per.EIRFunT, x1=TEvaLvg_degC, x2=TConEnt_degC); // Chiller energy input ratio quadratic curve EIRFunPLR = per.EIRFunPLR[1]+per.EIRFunPLR[2]*PLR2+per.EIRFunPLR[3]*PLR2^2; else capFunT = 0; EIRFunT = 0; EIRFunPLR = 0; end if; end ElectricEIR;

Buildings.Fluid.Chillers.ElectricReformulatedEIR Buildings.Fluid.Chillers.ElectricReformulatedEIR

Electric chiller based on the DOE-2.1 model, but with performance as a function of condenser leaving instead of entering temperature

Buildings.Fluid.Chillers.ElectricReformulatedEIR

Information

Model of an electric chiller, based on the model by Hydeman et al. (2002) that has been developed in the CoolTools project and that is implemented in EnergyPlus as the model Chiller:Electric:ReformulatedEIR. This empirical model is similar to Buildings.Fluid.Chillers.ElectricEIR. The difference is that to compute the performance, this model uses the condenser leaving temperature instead of the entering temperature, and it uses a bicubic polynomial to compute the part load performance.

This model uses three functions to predict capacity and power consumption:

These curves are stored in the data record per and are available from Buildings.Fluid.Chillers.Data.ElectricReformulatedEIRChiller. Additional performance curves can be developed using two available techniques (Hydeman and Gillespie, 2002). The first technique is called the Least-squares Linear Regression method and is used when sufficient performance data exist to employ standard least-square linear regression techniques. The second technique is called Reference Curve Method and is used when insufficient performance data exist to apply linear regression techniques. A detailed description of both techniques can be found in Hydeman and Gillespie (2002).

The model takes as an input the set point for the leaving chilled water temperature, which is met if the chiller has sufficient capacity. Thus, the model has a built-in, ideal temperature control. The model has three tests on the part load ratio and the cycling ratio:

  1. The test
      PLR1 =min(QEva_flow_set/QEva_flow_ava, per.PLRMax);
    
    ensures that the chiller capacity does not exceed the chiller capacity specified by the parameter per.PLRMax.
  2. The test
      CR = min(PLR1/per.PRLMin, 1.0);
    
    computes a cycling ratio. This ratio expresses the fraction of time that a chiller would run if it were to cycle because its load is smaller than the minimal load at which it can operate. Note that this model continuously operates even if the part load ratio is below the minimum part load ratio. Its leaving evaporator and condenser temperature can therefore be considered as an average temperature between the modes where the compressor is off and on.
  3. The test
      PLR2 = max(per.PLRMinUnl, PLR1);
    
    computes the part load ratio of the compressor. The assumption is that for a part load ratio below per.PLRMinUnl, the chiller uses hot gas bypass to reduce the capacity, while the compressor power draw does not change.

The electric power only contains the power for the compressor, but not any power for pumps or fans.

The model can be parametrized to compute a transient or steady-state response. The transient response of the boiler is computed using a first order differential equation for the evaporator and condenser fluid volumes. The chiller outlet temperatures are equal to the temperatures of these lumped volumes.

References

Extends from Buildings.Fluid.Chillers.BaseClasses.PartialElectric (Partial model for electric chiller based on the model in DOE-2, CoolTools and EnergyPlus).

Parameters

TypeNameDefaultDescription
replaceable package Medium1PartialMediumMedium 1 in the component
replaceable package Medium2PartialMediumMedium 2 in the component
Genericper Performance data
Nominal condition
MassFlowRatem1_flow_nominalmCon_flow_nominalNominal mass flow rate [kg/s]
MassFlowRatem2_flow_nominalmEva_flow_nominalNominal mass flow rate [kg/s]
PressureDifferencedp1_nominal Pressure difference [Pa]
PressureDifferencedp2_nominal Pressure difference [Pa]
Initialization
MassFlowRatem1_flow.start0Mass flow rate from port_a1 to port_b1 (m1_flow > 0 is design flow direction) [kg/s]
PressureDifferencedp1.start0Pressure difference between port_a1 and port_b1 [Pa]
MassFlowRatem2_flow.start0Mass flow rate from port_a2 to port_b2 (m2_flow > 0 is design flow direction) [kg/s]
PressureDifferencedp2.start0Pressure difference between port_a2 and port_b2 [Pa]
RealcapFunT.start1Cooling capacity factor function of temperature curve [1]
EfficiencyEIRFunT.start1Power input to cooling capacity ratio function of temperature curve [1]
EfficiencyEIRFunPLR.start1Power input to cooling capacity ratio function of part load ratio [1]
RealPLR1.start1Part load ratio [1]
RealPLR2.start1Part load ratio [1]
RealCR.start1Cycling ratio [1]
Assumptions
BooleanallowFlowReversal1true= true to allow flow reversal in medium 1, false restricts to design direction (port_a -> port_b)
BooleanallowFlowReversal2true= true to allow flow reversal in medium 2, false restricts to design direction (port_a -> port_b)
Advanced
MassFlowRatem1_flow_small1E-4*abs(m1_flow_nominal)Small mass flow rate for regularization of zero flow [kg/s]
MassFlowRatem2_flow_small1E-4*abs(m2_flow_nominal)Small mass flow rate for regularization of zero flow [kg/s]
BooleanhomotopyInitializationtrue= true, use homotopy method
Diagnostics
Booleanshow_Tfalse= true, if actual temperature at port is computed
Flow resistance
Medium 1
Booleanfrom_dp1false= true, use m_flow = f(dp) else dp = f(m_flow)
BooleanlinearizeFlowResistance1false= true, use linear relation between m_flow and dp for any flow rate
RealdeltaM10.1Fraction of nominal flow rate where flow transitions to laminar
Medium 2
Booleanfrom_dp2false= true, use m_flow = f(dp) else dp = f(m_flow)
BooleanlinearizeFlowResistance2false= true, use linear relation between m_flow and dp for any flow rate
RealdeltaM20.1Fraction of nominal flow rate where flow transitions to laminar
Dynamics
Nominal condition
Timetau130Time constant at nominal flow [s]
Timetau230Time constant at nominal flow [s]
Equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
DynamicsmassDynamicsenergyDynamicsType of mass balance: dynamic (3 initialization options) or steady state
Initialization
Medium 1
AbsolutePressurep1_startMedium1.p_defaultStart value of pressure [Pa]
TemperatureT1_start273.15 + 25Start value of temperature [K]
MassFractionX1_start[Medium1.nX]Medium1.X_defaultStart value of mass fractions m_i/m [kg/kg]
ExtraPropertyC1_start[Medium1.nC]fill(0, Medium1.nC)Start value of trace substances
ExtraPropertyC1_nominal[Medium1.nC]fill(1E-2, Medium1.nC)Nominal value of trace substances. (Set to typical order of magnitude.)
Medium 2
AbsolutePressurep2_startMedium2.p_defaultStart value of pressure [Pa]
TemperatureT2_start273.15 + 5Start value of temperature [K]
MassFractionX2_start[Medium2.nX]Medium2.X_defaultStart value of mass fractions m_i/m [kg/kg]
ExtraPropertyC2_start[Medium2.nC]fill(0, Medium2.nC)Start value of trace substances
ExtraPropertyC2_nominal[Medium2.nC]fill(1E-2, Medium2.nC)Nominal value of trace substances. (Set to typical order of magnitude.)

Connectors

TypeNameDescription
FluidPort_aport_a1Fluid connector a1 (positive design flow direction is from port_a1 to port_b1)
FluidPort_bport_b1Fluid connector b1 (positive design flow direction is from port_a1 to port_b1)
FluidPort_aport_a2Fluid connector a2 (positive design flow direction is from port_a2 to port_b2)
FluidPort_bport_b2Fluid connector b2 (positive design flow direction is from port_a2 to port_b2)
input BooleanInputonSet to true to enable compressor, or false to disable compressor
input RealInputTSetSet point for leaving chilled water temperature [K]
output RealOutputPElectric power consumed by compressor [W]

Modelica definition

model ElectricReformulatedEIR "Electric chiller based on the DOE-2.1 model, but with performance as a function of condenser leaving instead of entering temperature" extends Buildings.Fluid.Chillers.BaseClasses.PartialElectric( final QEva_flow_nominal = per.QEva_flow_nominal, final COP_nominal= per.COP_nominal, final PLRMax= per.PLRMax, final PLRMinUnl= per.PLRMinUnl, final PLRMin= per.PLRMin, final etaMotor= per.etaMotor, final mEva_flow_nominal= per.mEva_flow_nominal, final mCon_flow_nominal= per.mCon_flow_nominal, final TEvaLvg_nominal= per.TEvaLvg_nominal); parameter Buildings.Fluid.Chillers.Data.ElectricReformulatedEIR.Generic per "Performance data"; protected final parameter Modelica.SIunits.Conversions.NonSIunits.Temperature_degC TConLvg_nominal_degC= Modelica.SIunits.Conversions.to_degC(per.TConLvg_nominal) "Temperature of fluid leaving condenser at nominal condition"; Modelica.SIunits.Conversions.NonSIunits.Temperature_degC TConLvg_degC "Temperature of fluid leaving condenser"; initial equation // Verify correctness of performance curves, and write warning if error is bigger than 10% Buildings.Fluid.Chillers.BaseClasses.warnIfPerformanceOutOfBounds( Buildings.Utilities.Math.Functions.biquadratic(a=per.capFunT, x1=TEvaLvg_nominal_degC, x2=TConLvg_nominal_degC), "Capacity as a function of temperature ", "per.capFunT"); equation TConLvg_degC=Modelica.SIunits.Conversions.to_degC(TConLvg); if on then // Compute the chiller capacity fraction, using a biquadratic curve. // Since the regression for capacity can have negative values (for unreasonable temperatures), // we constrain its return value to be non-negative. This prevents the solver to pick the // unrealistic solution. capFunT = Buildings.Utilities.Math.Functions.smoothMax( x1= 1E-6, x2= Buildings.Utilities.Math.Functions.biquadratic(a=per.capFunT, x1=TEvaLvg_degC, x2=TConLvg_degC), deltaX= 1E-7); /* assert(capFunT > 0.1, "Error: Received capFunT = " + String(capFunT) + ".\n" + "Coefficient for polynomial seem to be not valid for the encountered temperature range.\n" + "Temperatures are TConLvg_degC = " + String(TConLvg_degC) + " degC\n" + " TEvaLvg_degC = " + String(TEvaLvg_degC) + " degC"); */ // Chiller energy input ratio biquadratic curve. EIRFunT = Buildings.Utilities.Math.Functions.biquadratic(a=per.EIRFunT, x1=TEvaLvg_degC, x2=TConLvg_degC); // Chiller energy input ratio bicubic curve EIRFunPLR = Buildings.Utilities.Math.Functions.bicubic(a=per.EIRFunPLR, x1=TConLvg_degC, x2=PLR2); else capFunT = 0; EIRFunT = 0; EIRFunPLR = 0; end if; end ElectricReformulatedEIR;

http://simulationresearch.lbl.gov/modelica