Collection of models that illustrate model use and test models
Information
This package contains examples for the use of models that can be found in
Buildings.Fluid.Storage.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
Package Content
Test model for expansion vessel
Information
This model tests a pressure expansion vessel. The medium model that is used in this
example changes its density as a function of temperature.
To see the effect of the expansion vessel, delete the connecting line between
the volume and the expansion vessel and check how much more the pressure increases
as the fluid is heated.
Extends from Modelica.Icons.Example (Icon for runnable examples).
Modelica definition
model ExpansionVessel
"Test model for expansion vessel"
extends Modelica.Icons.Example;
// package Medium = Modelica.Media.Water.WaterIF97OnePhase_ph "Medium model";
package Medium =
Buildings.Media.Water "Medium model";
Buildings.Fluid.Storage.ExpansionVessel expVes(
redeclare package Medium = Medium, V_start=1)
"Expansion vessel";
Buildings.Fluid.MixingVolumes.MixingVolume vol(
redeclare package Medium = Medium,
V=1,
nPorts=1,
m_flow_nominal=0.001,
energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial)
"Volume of water";
Modelica.Blocks.Sources.Pulse pulse(
amplitude=20,
period=3600,
offset=293.15);
Buildings.HeatTransfer.Sources.PrescribedTemperature preTem;
Modelica.Thermal.HeatTransfer.Components.ThermalConductor theCon(G=10000);
equation
connect(pulse.y, preTem.T);
connect(preTem.port, theCon.port_a);
connect(theCon.port_b, vol.heatPort);
connect(vol.ports[1], expVes.port_a);
end ExpansionVessel;
Test model for stratified tank
Information
This test model compares two tank models. The only difference between
the two tank models is that one uses the third order upwind discretization
scheme that reduces numerical diffusion that is induced when connecting
volumes in series.
Extends from Modelica.Icons.Example (Icon for runnable examples).
Modelica definition
model Stratified
"Test model for stratified tank"
extends Modelica.Icons.Example;
package Medium =
Buildings.Media.Water "Medium model";
Buildings.Fluid.Storage.Stratified tanSim(
redeclare package Medium = Medium,
hTan=3,
dIns=0.3,
nSeg=10,
m_flow_nominal=0.1,
VTan=3)
"Tank";
Modelica.Blocks.Sources.TimeTable TWat(table=[0,273.15 + 40; 3600,273.15 +
40; 3600,273.15 + 20; 7200,273.15 + 20])
"Water temperature";
Buildings.Fluid.Sources.Boundary_pT sou_1(
p=300000 + 5000,
T=273.15 + 50,
redeclare package Medium = Medium,
use_T_in=true,
nPorts=2);
Buildings.Fluid.Sources.Boundary_pT sin_1(
redeclare package Medium = Medium,
T=273.15 + 20,
use_p_in=true,
p=300000,
nPorts=2);
FixedResistances.FixedResistanceDpM res_1(
from_dp=true,
redeclare package Medium = Medium,
dp_nominal=5000,
m_flow_nominal=0.1);
Buildings.Fluid.Storage.StratifiedEnhanced tanEnh(
redeclare package Medium = Medium,
hTan=3,
dIns=0.3,
nSeg=10,
m_flow_nominal=0.1,
VTan=3)
"Tank";
FixedResistances.FixedResistanceDpM res_2(
from_dp=true,
redeclare package Medium = Medium,
dp_nominal=5000,
m_flow_nominal=0.1);
Buildings.Fluid.Sensors.EnthalpyFlowRate HOut_flow(
redeclare package Medium
= Medium, m_flow_nominal=0.1)
"Enthalpy flow rate";
Buildings.Fluid.Sensors.EnthalpyFlowRate HOut_flow1(
redeclare package Medium
= Medium, m_flow_nominal=0.1)
"Enthalpy flow rate";
Modelica.Blocks.Continuous.Integrator dH
"Differenz in enthalpy (should be zero at steady-state)";
Modelica.Blocks.Math.Add add(k2=-1);
Modelica.Blocks.Sources.TimeTable P(table=[0,300000; 4200,300000; 4200,
305000; 7200,305000; 7200,310000; 10800,310000; 10800,305000])
"Pressure boundary condition";
Modelica.Blocks.Sources.Sine sine(
freqHz=1/86400,
amplitude=10,
offset=273.15 + 20);
Buildings.HeatTransfer.Sources.PrescribedTemperature TBCSid2
"Boundary condition for tank";
Buildings.HeatTransfer.Sources.PrescribedTemperature TBCSid1
"Boundary condition for tank";
Buildings.HeatTransfer.Sources.PrescribedTemperature TBCTop1
"Boundary condition for tank";
Buildings.HeatTransfer.Sources.PrescribedTemperature TBCTop2
"Boundary condition for tank";
equation
connect(TWat.y, sou_1.T_in);
connect(tanSim.port_b, HOut_flow.port_a);
connect(HOut_flow.port_b, res_1.port_a);
connect(tanEnh.port_b, HOut_flow1.port_a);
connect(HOut_flow1.port_b, res_2.port_a);
connect(add.y, dH.u);
connect(HOut_flow.H_flow, add.u1);
connect(HOut_flow1.H_flow, add.u2);
connect(P.y, sin_1.p_in);
connect(sine.y, TBCSid1.T);
connect(sine.y, TBCTop1.T);
connect(sine.y, TBCSid2.T);
connect(sine.y, TBCTop2.T);
connect(TBCSid2.port, tanEnh.heaPorSid);
connect(TBCTop2.port, tanEnh.heaPorTop);
connect(sin_1.ports[1], res_1.port_b);
connect(sin_1.ports[2], res_2.port_b);
connect(sou_1.ports[1], tanSim.port_a);
connect(sou_1.ports[2], tanEnh.port_a);
connect(TBCSid1.port, tanSim.heaPorSid);
connect(TBCTop1.port, tanSim.heaPorTop);
end Stratified;
Example showing the use of StratifiedEnhancedInternalHex
Information
This model provides an example of how the
Buildings.Fluid.Storage.StratifiedEnhancedInternalHex model can be used.
A constant water draw is taken from the tank while a constant flow of hot water
is passed through the heat exchanger to heat the water in the tank.
Extends from Modelica.Icons.Example (Icon for runnable examples).
Modelica definition
model StratifiedEnhancedInternalHex
"Example showing the use of StratifiedEnhancedInternalHex"
extends Modelica.Icons.Example;
package MediumTan =
Buildings.Media.Water "Medium in the tank";
package MediumHex =
Modelica.Media.Incompressible.Examples.Glycol47
"Medium in the heat exchanger";
Buildings.Fluid.Sources.Boundary_pT hotWatOut(
redeclare package Medium = MediumTan,
nPorts=1)
"Hot water outlet";
Buildings.Fluid.Sources.MassFlowSource_T solColSup(
redeclare package Medium = MediumHex,
nPorts=1,
m_flow=0.278,
T=353.15)
"Water from solar collector";
Buildings.Fluid.Sources.Boundary_pT toSolCol(
redeclare package Medium = MediumHex,
nPorts=1,
T=283.15)
"Water to solar collector";
Buildings.Fluid.Sources.MassFlowSource_T bouCol(
redeclare package Medium = MediumTan,
use_T_in=false,
nPorts=1,
m_flow=0.1,
T=283.15)
"Cold water boundary";
Buildings.Fluid.Storage.StratifiedEnhancedInternalHex tan(
redeclare package Medium = MediumTan,
m_flow_nominal=0.001,
VTan=0.151416,
dIns=0.0762,
redeclare package MediumHex = MediumHex,
CHex=40,
Q_flow_nominal=0.278*4200*20,
mHex_flow_nominal=0.278,
hTan=1.746,
hHex_a=0.995,
energyDynamicsHex=Modelica.Fluid.Types.Dynamics.FixedInitial,
hHex_b=0.1,
energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial,
TTan_nominal=293.15,
THex_nominal=323.15)
"Tank with heat exchanger";
equation
connect(solColSup.ports[1], tan.portHex_a);
connect(tan.portHex_b, toSolCol.ports[1]);
connect(bouCol.ports[1], tan.port_b);
connect(hotWatOut.ports[1], tan.port_a);
end StratifiedEnhancedInternalHex;
Test model for stratified tank
Information
This test model compares two tank models. The only difference between
the two tank models is that one uses the third order upwind discretization
scheme that reduces numerical diffusion that is induced when connecting
volumes in series.
Extends from Modelica.Icons.Example (Icon for runnable examples).
Parameters
Type | Name | Default | Description |
MassFlowRate | m_flow_nominal | 1*1000/3600/4 | [kg/s] |
Modelica definition
model StratifiedLoadingUnloading
"Test model for stratified tank"
extends Modelica.Icons.Example;
package Medium =
Buildings.Media.Water "Medium model";
constant Integer nSeg = 7
"Number of segments in tank";
parameter Modelica.SIunits.MassFlowRate m_flow_nominal= 1*1000/3600/4;
Buildings.Fluid.Sources.Boundary_pT sou_1(
p=300000 + 5000,
T=273.15 + 40,
redeclare package Medium = Medium,
use_T_in=false,
nPorts=2);
Sources.MassFlowSource_T sin_1(
redeclare package Medium = Medium,
T=273.15 + 20,
m_flow=-0.028,
use_m_flow_in=true,
nPorts=1);
Buildings.Fluid.Storage.StratifiedEnhanced tanEnh(
redeclare package Medium = Medium,
hTan=3,
dIns=0.3,
VTan=0.1,
nSeg=nSeg,
show_T=true,
m_flow_nominal=m_flow_nominal)
"Tank";
Sources.MassFlowSource_T sin_2(
redeclare package Medium = Medium,
T=273.15 + 20,
m_flow=-0.028,
use_m_flow_in=true,
nPorts=1);
Buildings.Fluid.Storage.Stratified tan(
redeclare package Medium = Medium,
hTan=3,
dIns=0.3,
VTan=0.1,
nSeg=nSeg,
show_T=true,
m_flow_nominal=m_flow_nominal)
"Tank";
Modelica.Blocks.Sources.Pulse pulse(
amplitude=2*m_flow_nominal,
offset=-m_flow_nominal,
period=7200);
Buildings.Fluid.Sensors.EnthalpyFlowRate HIn_flow(
redeclare package Medium =
Medium, m_flow_nominal=m_flow_nominal)
"Enthalpy flow rate";
Buildings.Fluid.Sensors.EnthalpyFlowRate HOut_flow(
redeclare package Medium
= Medium, m_flow_nominal=m_flow_nominal)
"Enthalpy flow rate";
Buildings.Fluid.Sensors.EnthalpyFlowRate HInEnh_flow(
redeclare package Medium
= Medium, m_flow_nominal=m_flow_nominal)
"Enthalpy flow rate";
Buildings.Fluid.Sensors.EnthalpyFlowRate HOutEnh_flow(
redeclare package
Medium = Medium, m_flow_nominal=m_flow_nominal)
"Enthalpy flow rate";
Modelica.Blocks.Math.Add add(k2=-1);
Modelica.Blocks.Continuous.Integrator dHTanEnh
"Difference in enthalpy (should be zero at steady-state)";
Modelica.Blocks.Math.Add add1(
k2=-1);
Modelica.Blocks.Continuous.Integrator dHTan
"Difference in enthalpy (should be zero at steady-state)";
equation
connect(sou_1.ports[1], HIn_flow.port_a);
connect(HIn_flow.port_b, tan.port_a);
connect(tan.port_b, HOut_flow.port_a);
connect(HOut_flow.port_b, sin_2.ports[1]);
connect(sou_1.ports[2], HInEnh_flow.port_a);
connect(HInEnh_flow.port_b, tanEnh.port_a);
connect(tanEnh.port_b, HOutEnh_flow.port_a);
connect(HOutEnh_flow.port_b, sin_1.ports[1]);
connect(HInEnh_flow.H_flow, add.u1);
connect(HOutEnh_flow.H_flow, add.u2);
connect(add.y, dHTanEnh.u);
connect(HIn_flow.H_flow, add1.u1);
connect(HOut_flow.H_flow, add1.u2);
connect(add1.y, dHTan.u);
connect(pulse.y, sin_1.m_flow_in);
connect(pulse.y, sin_2.m_flow_in);
end StratifiedLoadingUnloading;
Automatically generated Mon Jul 13 14:26:11 2015.