Package of medium voltage electricity cables used in distribution grid
This package contains records of physical properties of medium voltage commercial cables. New cables can be added by extending the base record Buildings.Electrical.Transmission.MediumVoltageCables.Generic.
Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).
Name | Description |
---|---|
Annealed_Al_10 | Annealed Al cable - AWG 1/0 |
Annealed_Al_1000 | Annealed Al cable - AWG 1000 |
Annealed_Al_1500 | Annealed Al cable - AWG 1500 |
Annealed_Al_30 | Annealed Al cable - AWG 3/0 |
Annealed_Al_350 | Annealed Al cable - kcmil 350 |
Annealed_Al_40 | Annealed Al cable - AWG 4/0 |
Annealed_Al_500 | Annealed Al cable - AWG 500 |
Generic | Data record for a generic medium voltage cable |
Annealed Al cable - AWG 1/0
Annealed aluminium cable with a cross-sectional AWG 1/0 (American Wire Gauge). This type of cable has the following properties
Rdc = 0.551181e-3 // Characteristic DC resistance at T = T_ref[Ohm/m] T_ref= 298.15 // Reference temperature of the material [K] d = 9.195e-3 // Inner diameter [m] D = 26.543e-3 // Outer diameter [m] Amp = 195 // Ampacity [A]
Extends from Buildings.Electrical.Transmission.MediumVoltageCables.Generic (Data record for a generic medium voltage cable).
Type | Name | Default | Description |
---|---|---|---|
Material | material | Types.Material.Al | Material of the cable |
Current | Amp | 195 | Ampacitance of the cable [A] |
Temperature | T_ref | 298.15 | Reference cable temperature [K] |
Temperature | M | 228.1 + 273.15 | Temperature constant of the material [K] |
replaceable function lineResistance | Function that computes the resistance of a cable | ||
replaceable function lineInductance | Function that computes the inductance of a cable | ||
replaceable function lineCapacitance | Function that computes the capacitance of a cable | ||
String | size | "1/0" | AWG or kcmil code representing the conductor size |
CharacteristicResistance | Rdc | 0.551181e-3 | Characteristic DC resistance of the cable @ T_ref [Ohm/m] |
Length | d | 9.195e-3 | Inner diameter [m] |
Length | D | 26.543e-3 | Outer diameter [m] |
Length | GMR | Buildings.Electrical.Transmi... | Geometrical Mean Radius of the cable [m] |
Length | GMD | Buildings.Electrical.Transmi... | Geometrical Mean Diameter of the cable [m] |
Annealed Al cable - AWG 1000
Annealed aluminium cable with a cross-sectional kcmil 1000 (thousand of Circular Mils). This type of cable has the following properties
Rdc = 5.80709e-5 // Characteristic DC resistance at T = T_ref[Ohm/m] T_ref= 298.15 // Reference temperature of the material [K] d = 28.372e-3 // Inner diameter [m] D = 46.101e-3 // Outer diameter [m] Amp = 640 // Ampacity [A]
Extends from Buildings.Electrical.Transmission.MediumVoltageCables.Generic (Data record for a generic medium voltage cable).
Type | Name | Default | Description |
---|---|---|---|
Material | material | Types.Material.Al | Material of the cable |
Current | Amp | 640 | Ampacitance of the cable [A] |
Temperature | T_ref | 298.15 | Reference cable temperature [K] |
Temperature | M | 228.1 + 273.15 | Temperature constant of the material [K] |
replaceable function lineResistance | Function that computes the resistance of a cable | ||
replaceable function lineInductance | Function that computes the inductance of a cable | ||
replaceable function lineCapacitance | Function that computes the capacitance of a cable | ||
String | size | "1000" | AWG or kcmil code representing the conductor size |
CharacteristicResistance | Rdc | 5.80709e-5 | Characteristic DC resistance of the cable @ T_ref [Ohm/m] |
Length | d | 28.372e-3 | Inner diameter [m] |
Length | D | 46.101e-3 | Outer diameter [m] |
Length | GMR | Buildings.Electrical.Transmi... | Geometrical Mean Radius of the cable [m] |
Length | GMD | Buildings.Electrical.Transmi... | Geometrical Mean Diameter of the cable [m] |
Annealed Al cable - AWG 1500
Annealed aluminium cable with a cross-sectional kcmil 1500 (thousand of Circular Mils). This type of cable has the following properties
Rdc = 3.87139e-5 // Characteristic DC resistance at T = T_ref[Ohm/m] T_ref= 298.15 // Reference temperature of the material [K] d = 34.798e-3 // Inner diameter [m] D = 53.34e-3 // Outer diameter [m] Amp = 800 // Ampacity [A]
Extends from Buildings.Electrical.Transmission.MediumVoltageCables.Generic (Data record for a generic medium voltage cable).
Type | Name | Default | Description |
---|---|---|---|
Material | material | Types.Material.Al | Material of the cable |
Current | Amp | 800 | Ampacitance of the cable [A] |
Temperature | T_ref | 298.15 | Reference cable temperature [K] |
Temperature | M | 228.1 + 273.15 | Temperature constant of the material [K] |
replaceable function lineResistance | Function that computes the resistance of a cable | ||
replaceable function lineInductance | Function that computes the inductance of a cable | ||
replaceable function lineCapacitance | Function that computes the capacitance of a cable | ||
String | size | "1500" | AWG or kcmil code representing the conductor size |
CharacteristicResistance | Rdc | 3.87139e-5 | Characteristic DC resistance of the cable @ T_ref [Ohm/m] |
Length | d | 34.798e-3 | Inner diameter [m] |
Length | D | 53.34e-3 | Outer diameter [m] |
Length | GMR | Buildings.Electrical.Transmi... | Geometrical Mean Radius of the cable [m] |
Length | GMD | Buildings.Electrical.Transmi... | Geometrical Mean Diameter of the cable [m] |
Annealed Al cable - AWG 3/0
Annealed aluminium cable with a cross-sectional AWG 2/0 (American Wire Gauge). This type of cable has the following properties
Rdc = 0.344488e-3 // Characteristic DC resistance at T = T_ref[Ohm/m] T_ref= 298.15 // Reference temperature of the material [K] d = 11.582e-3 // Inner diameter [m] D = 28.956e-3 // Outer diameter [m] Amp = 250 // Ampacity [A]
Extends from Buildings.Electrical.Transmission.MediumVoltageCables.Generic (Data record for a generic medium voltage cable).
Type | Name | Default | Description |
---|---|---|---|
Material | material | Types.Material.Al | Material of the cable |
Current | Amp | 250 | Ampacitance of the cable [A] |
Temperature | T_ref | 298.15 | Reference cable temperature [K] |
Temperature | M | 228.1 + 273.15 | Temperature constant of the material [K] |
replaceable function lineResistance | Function that computes the resistance of a cable | ||
replaceable function lineInductance | Function that computes the inductance of a cable | ||
replaceable function lineCapacitance | Function that computes the capacitance of a cable | ||
String | size | "3/0" | AWG or kcmil code representing the conductor size |
CharacteristicResistance | Rdc | 0.344488e-3 | Characteristic DC resistance of the cable @ T_ref [Ohm/m] |
Length | d | 11.582e-3 | Inner diameter [m] |
Length | D | 28.956e-3 | Outer diameter [m] |
Length | GMR | Buildings.Electrical.Transmi... | Geometrical Mean Radius of the cable [m] |
Length | GMD | Buildings.Electrical.Transmi... | Geometrical Mean Diameter of the cable [m] |
Annealed Al cable - kcmil 350
Annealed aluminium cable with a cross-sectional kcmil 350 (thousand of Circular Mils). This type of cable has the following properties
Rdc = 0.165682e-3 // Characteristic DC resistance at T = T_ref[Ohm/m] T_ref= 298.15 // Reference temperature of the material [K] d = 16.789e-3 // Inner diameter [m] D = 34.417e-3 // Outer diameter [m] Amp = 375 // Ampacity [A]
Extends from Buildings.Electrical.Transmission.MediumVoltageCables.Generic (Data record for a generic medium voltage cable).
Type | Name | Default | Description |
---|---|---|---|
Material | material | Types.Material.Al | Material of the cable |
Current | Amp | 375 | Ampacitance of the cable [A] |
Temperature | T_ref | 298.15 | Reference cable temperature [K] |
Temperature | M | 228.1 + 273.15 | Temperature constant of the material [K] |
replaceable function lineResistance | Function that computes the resistance of a cable | ||
replaceable function lineInductance | Function that computes the inductance of a cable | ||
replaceable function lineCapacitance | Function that computes the capacitance of a cable | ||
String | size | "350" | AWG or kcmil code representing the conductor size |
CharacteristicResistance | Rdc | 0.165682e-3 | Characteristic DC resistance of the cable @ T_ref [Ohm/m] |
Length | d | 16.789e-3 | Inner diameter [m] |
Length | D | 34.417e-3 | Outer diameter [m] |
Length | GMR | Buildings.Electrical.Transmi... | Geometrical Mean Radius of the cable [m] |
Length | GMD | Buildings.Electrical.Transmi... | Geometrical Mean Diameter of the cable [m] |
Annealed Al cable - AWG 4/0
Annealed aluminium cable with a cross-sectional AWG 4/0 (American Wire Gauge). This type of cable has the following properties
Rdc = 0.274278e-3 // Characteristic DC resistance at T = T_ref[Ohm/m] T_ref= 298.15 // Reference temperature of the material [K] d = 13.005e-3 // Inner diameter [m] D = 30.353e-3 // Outer diameter [m] Amp = 285 // Ampacity [A]
Extends from Buildings.Electrical.Transmission.MediumVoltageCables.Generic (Data record for a generic medium voltage cable).
Type | Name | Default | Description |
---|---|---|---|
Material | material | Types.Material.Al | Material of the cable |
Current | Amp | 285 | Ampacitance of the cable [A] |
Temperature | T_ref | 298.15 | Reference cable temperature [K] |
Temperature | M | 228.1 + 273.15 | Temperature constant of the material [K] |
replaceable function lineResistance | Function that computes the resistance of a cable | ||
replaceable function lineInductance | Function that computes the inductance of a cable | ||
replaceable function lineCapacitance | Function that computes the capacitance of a cable | ||
String | size | "4/0" | AWG or kcmil code representing the conductor size |
CharacteristicResistance | Rdc | 0.274278e-3 | Characteristic DC resistance of the cable @ T_ref [Ohm/m] |
Length | d | 13.005e-3 | Inner diameter [m] |
Length | D | 30.353e-3 | Outer diameter [m] |
Length | GMR | Buildings.Electrical.Transmi... | Geometrical Mean Radius of the cable [m] |
Length | GMD | Buildings.Electrical.Transmi... | Geometrical Mean Diameter of the cable [m] |
Annealed Al cable - AWG 500
Annealed aluminium cable with a cross-sectional kcmil 500 (thousand of Circular Mils). This type of cable has the following properties
Rdc = 0.116142e-3 // Characteristic DC resistance at T = T_ref[Ohm/m] T_ref= 298.15 // Reference temperature of the material [K] d = 20.066e-3 // Inner diameter [m] D = 37.592e-3 // Outer diameter [m] Amp = 450 // Ampacity [A]
Extends from Buildings.Electrical.Transmission.MediumVoltageCables.Generic (Data record for a generic medium voltage cable).
Type | Name | Default | Description |
---|---|---|---|
Material | material | Types.Material.Al | Material of the cable |
Current | Amp | 450 | Ampacitance of the cable [A] |
Temperature | T_ref | 298.15 | Reference cable temperature [K] |
Temperature | M | 228.1 + 273.15 | Temperature constant of the material [K] |
replaceable function lineResistance | Function that computes the resistance of a cable | ||
replaceable function lineInductance | Function that computes the inductance of a cable | ||
replaceable function lineCapacitance | Function that computes the capacitance of a cable | ||
String | size | "500" | AWG or kcmil code representing the conductor size |
CharacteristicResistance | Rdc | 0.116142e-3 | Characteristic DC resistance of the cable @ T_ref [Ohm/m] |
Length | d | 20.066e-3 | Inner diameter [m] |
Length | D | 37.592e-3 | Outer diameter [m] |
Length | GMR | Buildings.Electrical.Transmi... | Geometrical Mean Radius of the cable [m] |
Length | GMD | Buildings.Electrical.Transmi... | Geometrical Mean Diameter of the cable [m] |
Data record for a generic medium voltage cable
This is a base record for specifying physical properties for medium voltage commercial cables. New cables can be added by extending it.
For medium voltage cables, the geometric properties of the cable and the material are specified. For example some of the properties that are specified are:
Rdc : Characteristic DC resistance at T = T_ref[Ohm/m] T_ref : Reference temperature of the material [K] d : Inner diameter [m] D : Outer diameter [m] Amp : Ampacity [A]
other properties such as the geometric mean diameter GMD and the geometric mean radius GMR are by default computed using functions, but this can be overriden.
Extends from Modelica.Icons.MaterialProperty (Icon for property classes), Buildings.Electrical.Transmission.BaseClasses.BaseCable (Record that contains the properties of a generic cable).
Type | Name | Default | Description |
---|---|---|---|
Material | material | Buildings.Electrical.Transmi... | Material of the cable |
Current | Amp | 0.0 | Ampacitance of the cable [A] |
Temperature | T_ref | 298.15 | Reference cable temperature [K] |
Temperature | M | 228.1 + 273.15 | Temperature constant of the material [K] |
replaceable function lineResistance | Function that computes the resistance of a cable | ||
replaceable function lineInductance | Function that computes the inductance of a cable | ||
replaceable function lineCapacitance | Function that computes the capacitance of a cable | ||
String | size | AWG or kcmil code representing the conductor size | |
CharacteristicResistance | Rdc | Characteristic DC resistance of the cable @ T_ref [Ohm/m] | |
Length | d | Inner diameter [m] | |
Length | D | Outer diameter [m] | |
Length | GMR | Geometrical Mean Radius of the cable [m] | |
Length | GMD | Geometrical Mean Diameter of the cable [m] |