Buildings.Electrical.AC.OnePhase.Loads.Examples

Package with example models

Information

This package contains examples for the use of models that can be found in Buildings.Electrical.AC.OnePhase.Loads.

Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).

Package Content

Name Description
Buildings.Electrical.AC.OnePhase.Loads.Examples.DynamicLoads DynamicLoads Example that illustrates the use of dynamic loads
Buildings.Electrical.AC.OnePhase.Loads.Examples.ParallelLoads ParallelLoads Example that illustrates the use of the load models at constant voltage
Buildings.Electrical.AC.OnePhase.Loads.Examples.ParallelResistors ParallelResistors Example that illustrates the use of the load models at constant voltage
Buildings.Electrical.AC.OnePhase.Loads.Examples.TestImpedance TestImpedance Example that illustrates the use of the impedances
Buildings.Electrical.AC.OnePhase.Loads.Examples.ThreePhases ThreePhases Examples that illustrates how to replicate a three-phase balanced system
Buildings.Electrical.AC.OnePhase.Loads.Examples.VariableImpedance VariableImpedance Example that illustrates how using variable impedances

Buildings.Electrical.AC.OnePhase.Loads.Examples.DynamicLoads Buildings.Electrical.AC.OnePhase.Loads.Examples.DynamicLoads

Example that illustrates the use of dynamic loads

Buildings.Electrical.AC.OnePhase.Loads.Examples.DynamicLoads

Information

This model compares two dynamic load models that use the dynamic phasors.

The loads at nominal conditions should consume an active power equal to 1.2 kW. Because of the line resistance the voltage at the load is attenuated and they consume less power.

As expected the real part of the current vector drawn by the loads are the same while the complex parts have opposite signs.

Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model DynamicLoads "Example that illustrates the use of dynamic loads" extends Modelica.Icons.Example; Buildings.Electrical.AC.OnePhase.Sources.FixedVoltage source( f=60, V=120) "Voltage source"; Buildings.Electrical.AC.OnePhase.Loads.Capacitive dynRC( pf=0.8, mode=Buildings.Electrical.Types.Load.FixedZ_dynamic, P_nominal=-1200, V_nominal=120) "Dynamic RC load"; Buildings.Electrical.AC.OnePhase.Lines.TwoPortResistance line(R=0.1) "Line resistance"; Buildings.Electrical.AC.OnePhase.Loads.Inductive dynRL( pf=0.8, mode=Buildings.Electrical.Types.Load.FixedZ_dynamic, P_nominal=-1200, V_nominal=120) "Dynamic RL load"; equation connect(source.terminal, line.terminal_n); connect(line.terminal_p, dynRC.terminal); connect(dynRL.terminal, line.terminal_p); end DynamicLoads;

Buildings.Electrical.AC.OnePhase.Loads.Examples.ParallelLoads Buildings.Electrical.AC.OnePhase.Loads.Examples.ParallelLoads

Example that illustrates the use of the load models at constant voltage

Buildings.Electrical.AC.OnePhase.Loads.Examples.ParallelLoads

Information

This model illustrates the use of the load models. The first two lines are inductive loads, followed by two capacitive loads and a resistive load. The inductive load varRL and the capacitive load varRC have a variable load specified by the inputs Pow and y respectively. All the loads have a nominal power of 1kW, and varRL is the only one that at t=0 produces power 1kW and as the time increases it start to consume up to 1kW.

Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model ParallelLoads "Example that illustrates the use of the load models at constant voltage" extends Modelica.Icons.Example; Buildings.Electrical.AC.OnePhase.Loads.Inductive varRL( mode=Buildings.Electrical.Types.Load.VariableZ_P_input, P_nominal=-1e3, linearized=false, V_nominal=120) "Variable inductor and resistor"; Buildings.Electrical.AC.OnePhase.Sources.FixedVoltage source(f=60, V=120) "Voltage source"; Modelica.Blocks.Sources.Ramp load_y(duration=0.5, startTime=0.2) "Input signal for RC load"; Buildings.Electrical.AC.OnePhase.Loads.Inductive RL( P_nominal=-1e3, linearized=false, V_nominal=120) "Constant inductor and resistor"; Buildings.Electrical.AC.OnePhase.Loads.Capacitive varRC(mode=Buildings.Electrical.Types.Load.VariableZ_y_input, P_nominal=-1e3, linearized=false, V_nominal=120) "Variable conductor and resistor"; Buildings.Electrical.AC.OnePhase.Loads.Capacitive RC(mode=Buildings.Electrical.Types.Load.FixedZ_steady_state, P_nominal=-1e3, linearized=false, V_nominal=120) "Constant conductor and resistor"; Buildings.Electrical.AC.OnePhase.Loads.Resistive R( P_nominal=-1e3, mode=Buildings.Electrical.Types.Load.FixedZ_steady_state, linearized=false, V_nominal=120) "Resistive load"; Modelica.Blocks.Sources.Ramp load_P( startTime=0.2, duration=0.5, height=-2000, offset=1000) "Power signal for load varRL"; equation connect(source.terminal, varRL.terminal); connect(source.terminal, RL.terminal); connect(source.terminal, varRC.terminal); connect(source.terminal, R.terminal); connect(RC.terminal, R.terminal); connect(load_y.y, varRC.y); connect(load_P.y, varRL.Pow); end ParallelLoads;

Buildings.Electrical.AC.OnePhase.Loads.Examples.ParallelResistors Buildings.Electrical.AC.OnePhase.Loads.Examples.ParallelResistors

Example that illustrates the use of the load models at constant voltage

Buildings.Electrical.AC.OnePhase.Loads.Examples.ParallelResistors

Information

This model compares two resistive loads. Model R consumes or produces a variable amount of power, while model R1 consumes a fixed power.

At time t=0 R and R1 consumes the same amount of power while at t=1 R produces the same power consumed by R1.

Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model ParallelResistors "Example that illustrates the use of the load models at constant voltage" extends Modelica.Icons.Example; Buildings.Electrical.AC.OnePhase.Sources.FixedVoltage source(f=60, V=120) "Voltage source"; Modelica.Blocks.Sources.Ramp load(duration=0.5, startTime=0.2, height=2400, offset=-1200) "Power signal for load R"; Buildings.Electrical.AC.OnePhase.Loads.Resistive R( mode=Buildings.Electrical.Types.Load.VariableZ_P_input, P_nominal=-1e3, V_nominal=120) "Variable resistive load"; Buildings.Electrical.AC.OnePhase.Loads.Resistive R1( mode=Buildings.Electrical.Types.Load.FixedZ_steady_state, P_nominal=-1.2e3, V_nominal=120) "Fixed resistive load"; equation connect(source.terminal, R.terminal); connect(load.y, R.Pow); connect(source.terminal, R1.terminal); end ParallelResistors;

Buildings.Electrical.AC.OnePhase.Loads.Examples.TestImpedance Buildings.Electrical.AC.OnePhase.Loads.Examples.TestImpedance

Example that illustrates the use of the impedances

Buildings.Electrical.AC.OnePhase.Loads.Examples.TestImpedance

Information

This model shows how to use the impedance model in different configurations:

Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model TestImpedance "Example that illustrates the use of the impedances" extends Modelica.Icons.Example; Buildings.Electrical.AC.OnePhase.Sources.FixedVoltage V(f=60, V=120); Buildings.Electrical.AC.OnePhase.Loads.Impedance Z1(R=0, inductive=true, L=1/(2*Modelica.Constants.pi*60)) "Inductive impedance"; Buildings.Electrical.AC.OnePhase.Loads.Impedance Z2(R=0, inductive=false, C=1/(2*Modelica.Constants.pi*60)) "Capacitive impedance"; Buildings.Electrical.AC.OnePhase.Loads.Impedance Z3(R=1) "Resistive impedance"; Buildings.Electrical.AC.OnePhase.Loads.Impedance Z4( R=1, L=1/(2*Modelica.Constants.pi*60)) "Inductive-resistive impedance"; Buildings.Electrical.AC.OnePhase.Loads.Impedance Z5( R=1, inductive=false, C=1/(2*Modelica.Constants.pi*60)) "Capacitive-resistive impedance"; equation connect(V.terminal, Z1.terminal); connect(V.terminal, Z2.terminal); connect(V.terminal, Z3.terminal); connect(V.terminal, Z4.terminal); connect(V.terminal, Z5.terminal); end TestImpedance;

Buildings.Electrical.AC.OnePhase.Loads.Examples.ThreePhases Buildings.Electrical.AC.OnePhase.Loads.Examples.ThreePhases

Examples that illustrates how to replicate a three-phase balanced system

Buildings.Electrical.AC.OnePhase.Loads.Examples.ThreePhases

Information

This model shows how a balanced three phase system can be represented with three independent single phase circuits.

Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model ThreePhases "Examples that illustrates how to replicate a three-phase balanced system" extends Modelica.Icons.Example; Buildings.Electrical.AC.OnePhase.Sources.FixedVoltage Va( definiteReference=true, f=60, V=120) "Source phase A"; Buildings.Electrical.AC.OnePhase.Loads.Impedance Za( inductive=true, L=1/(2*Modelica.Constants.pi*60), R=12) "Impedance phase A"; Buildings.Electrical.AC.OnePhase.Sources.FixedVoltage Vb( definiteReference=true, phiSou=-2.0943951023932, f=60, V=120) "Source phase B"; Buildings.Electrical.AC.OnePhase.Loads.Impedance Zb( inductive=true, L=1/(2*Modelica.Constants.pi*60), R=12) "Impedance phase B"; Buildings.Electrical.AC.OnePhase.Sources.FixedVoltage Vc( definiteReference=true, phiSou=2.0943951023932, f=60, V=120) "Source phase C"; Buildings.Electrical.AC.OnePhase.Loads.Impedance Zc( inductive=true, L=1/(2*Modelica.Constants.pi*60), R=12) "Impedance phase C"; equation connect(Va.terminal, Za.terminal); connect(Vb.terminal, Zb.terminal); connect(Vc.terminal, Zc.terminal); end ThreePhases;

Buildings.Electrical.AC.OnePhase.Loads.Examples.VariableImpedance Buildings.Electrical.AC.OnePhase.Loads.Examples.VariableImpedance

Example that illustrates how using variable impedances

Buildings.Electrical.AC.OnePhase.Loads.Examples.VariableImpedance

Information

This model shows how to vary the resistance, capacitance or inductance of an impedance model.

Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model VariableImpedance "Example that illustrates how using variable impedances" extends Modelica.Icons.Example; Buildings.Electrical.AC.OnePhase.Sources.FixedVoltage V(f=60, V=120) "Voltage source"; Buildings.Electrical.AC.OnePhase.Loads.Impedance Z_L( R=0, inductive=true, L=1/(2*Modelica.Constants.pi*60), use_L_in=true, LMin=1/(2*Modelica.Constants.pi*60), LMax=2/(2*Modelica.Constants.pi*60)) "Impedance with variable L"; Buildings.Electrical.AC.OnePhase.Loads.Impedance Z_C( R=0, inductive=false, C=1/(2*Modelica.Constants.pi*60), use_C_in=true, CMin=1/(2*Modelica.Constants.pi*60), CMax=2/(2*Modelica.Constants.pi*60)) "Impedance with variable C"; Buildings.Electrical.AC.OnePhase.Loads.Impedance Z_R( R=1, RMin=1, RMax=2, use_R_in=true, L=0) "Impedance with variable R"; Modelica.Blocks.Sources.Ramp load(duration=0.5, startTime=0.2, height=1, offset=0) "Input signal for the loads"; equation connect(V.terminal, Z_L.terminal); connect(V.terminal, Z_C.terminal); connect(V.terminal, Z_R.terminal); connect(load.y, Z_R.y_R); connect(load.y, Z_C.y_C); connect(load.y, Z_L.y_L); end VariableImpedance;

Automatically generated Mon May 4 10:18:44 2015.