Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans
Air handlers and fans
Information
This package contains models used for validation purposes.
Extends from Modelica.Icons.Package (Icon for standard packages).
Package Content
| Name | Description |
|---|---|
| Configuration of multiple-zone VAV | |
| Configuration of multiple-zone VAV | |
| Configuration of multiple-zone VAV | |
| Configuration of multiple-zone VAV | |
| Configuration of multiple-zone VAV | |
| Configuration of multiple-zone VAV | |
| Configuration of multiple-zone VAV | |
| Configuration of multiple-zone VAV | |
| Configuration of multiple-zone VAV | |
| Configuration of multiple-zone VAV |
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZBase
Configuration of multiple-zone VAV
Information
This is a configuration model with the same default options as
Buildings.Templates.AirHandlersFans.VAVMultiZone
except for the following options.
| Component | Configuration |
|---|---|
| Outdoor air section | No economizer |
| Relief/return air section | No economizer |
Extends from VAVMultiZone (Multiple-zone VAV).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| replaceable package MediumChiWat | Water | CHW medium | |
| replaceable package MediumHeaWat | Water | HHW medium | |
| VAVMultiZone | dat | redeclare Buildings.Template... | Design and operating parameters |
| Configuration | |||
| Integer | nZon | 2 | Number of served zones |
| MixedAirWithDamper | secOutRel | Outdoor/relief/return air section | |
| None | fanSupBlo | redeclare inner Buildings.Te... | Supply fan - Blow through |
| SingleVariable | fanSupDra | redeclare inner Buildings.Te... | Supply fan - Draw through |
| WaterBasedHeating | coiHeaPre | redeclare inner Buildings.Te... | Heating coil in preheat position |
| WaterBasedCooling | coiCoo | redeclare inner Buildings.Te... | Cooling coil |
| None | coiHeaReh | redeclare inner Buildings.Te... | Heating coil in reheat position |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversalLiq | true | = true to allow flow reversal, false restricts to design direction - CHW and HW side |
| Advanced | |||
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at ports of subcomponents is computed |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_Out | Outdoor air intake |
| FluidPort_b | port_Sup | Supply air |
| FluidPort_b | port_SupCol | Dual duct cold deck air supply |
| FluidPort_b | port_SupHot | Dual duct hot deck air supply |
| FluidPort_a | port_Ret | Return air |
| FluidPort_b | port_Rel | Relief (exhaust) air |
| FluidPort_b | port_bChiWat | CHW return port |
| FluidPort_a | port_aChiWat | CHW supply port |
| FluidPort_b | port_bHeaWat | HHW return port |
| FluidPort_a | port_aHeaWat | HHW supply port |
| Bus | bus | AHU control bus |
| Bus | busWea | Weather bus |
| Bus | busTer[nZon] | Terminal unit control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilElectricHeating
Configuration of multiple-zone VAV
Information
This is a configuration model with the same default options as
Buildings.Templates.AirHandlersFans.VAVMultiZone
except for the following options.
| Component | Configuration |
|---|---|
| Heating coil | Modulating electric heating coil - Preheat position |
Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| replaceable package MediumChiWat | Water | CHW medium | |
| replaceable package MediumHeaWat | Water | HHW medium | |
| VAVMultiZone | dat | redeclare Buildings.Template... | Design and operating parameters |
| Configuration | |||
| Integer | nZon | 2 | Number of served zones |
| MixedAirWithDamper | secOutRel | Outdoor/relief/return air section | |
| None | fanSupBlo | redeclare inner Buildings.Te... | Supply fan - Blow through |
| SingleVariable | fanSupDra | redeclare inner Buildings.Te... | Supply fan - Draw through |
| WaterBasedCooling | coiCoo | redeclare inner Buildings.Te... | Cooling coil |
| None | coiHeaReh | redeclare inner Buildings.Te... | Heating coil in reheat position |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversalLiq | true | = true to allow flow reversal, false restricts to design direction - CHW and HW side |
| Advanced | |||
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at ports of subcomponents is computed |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_Out | Outdoor air intake |
| FluidPort_b | port_Sup | Supply air |
| FluidPort_b | port_SupCol | Dual duct cold deck air supply |
| FluidPort_b | port_SupHot | Dual duct hot deck air supply |
| FluidPort_a | port_Ret | Return air |
| FluidPort_b | port_Rel | Relief (exhaust) air |
| FluidPort_b | port_bChiWat | CHW return port |
| FluidPort_a | port_aChiWat | CHW supply port |
| FluidPort_b | port_bHeaWat | HHW return port |
| FluidPort_a | port_aHeaWat | HHW supply port |
| Bus | bus | AHU control bus |
| Bus | busWea | Weather bus |
| Bus | busTer[nZon] | Terminal unit control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilEvaporatorMultiStage
Configuration of multiple-zone VAV
Information
This is a configuration model with the same default options as
Buildings.Templates.AirHandlersFans.VAVMultiZone
except for the following options.
| Component | Configuration |
|---|---|
| Cooling coil | Evaporator coil with multi-stage compressor |
Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| replaceable package MediumChiWat | Water | CHW medium | |
| replaceable package MediumHeaWat | Water | HHW medium | |
| VAVMultiZone | dat | redeclare Buildings.Template... | Design and operating parameters |
| Configuration | |||
| Integer | nZon | 2 | Number of served zones |
| MixedAirWithDamper | secOutRel | Outdoor/relief/return air section | |
| None | fanSupBlo | redeclare inner Buildings.Te... | Supply fan - Blow through |
| SingleVariable | fanSupDra | redeclare inner Buildings.Te... | Supply fan - Draw through |
| WaterBasedHeating | coiHeaPre | redeclare inner Buildings.Te... | Heating coil in preheat position |
| None | coiHeaReh | redeclare inner Buildings.Te... | Heating coil in reheat position |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversalLiq | true | = true to allow flow reversal, false restricts to design direction - CHW and HW side |
| Advanced | |||
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at ports of subcomponents is computed |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_Out | Outdoor air intake |
| FluidPort_b | port_Sup | Supply air |
| FluidPort_b | port_SupCol | Dual duct cold deck air supply |
| FluidPort_b | port_SupHot | Dual duct hot deck air supply |
| FluidPort_a | port_Ret | Return air |
| FluidPort_b | port_Rel | Relief (exhaust) air |
| FluidPort_b | port_bChiWat | CHW return port |
| FluidPort_a | port_aChiWat | CHW supply port |
| FluidPort_b | port_bHeaWat | HHW return port |
| FluidPort_a | port_aHeaWat | HHW supply port |
| Bus | bus | AHU control bus |
| Bus | busWea | Weather bus |
| Bus | busTer[nZon] | Terminal unit control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilEvaporatorVariable
Configuration of multiple-zone VAV
Information
This is a configuration model with the same default options as
Buildings.Templates.AirHandlersFans.VAVMultiZone
except for the following options.
| Component | Configuration |
|---|---|
| Cooling coil | Evaporator coil with variable speed compressor |
Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| replaceable package MediumChiWat | Water | CHW medium | |
| replaceable package MediumHeaWat | Water | HHW medium | |
| VAVMultiZone | dat | redeclare Buildings.Template... | Design and operating parameters |
| Configuration | |||
| Integer | nZon | 2 | Number of served zones |
| MixedAirWithDamper | secOutRel | Outdoor/relief/return air section | |
| None | fanSupBlo | redeclare inner Buildings.Te... | Supply fan - Blow through |
| SingleVariable | fanSupDra | redeclare inner Buildings.Te... | Supply fan - Draw through |
| WaterBasedHeating | coiHeaPre | redeclare inner Buildings.Te... | Heating coil in preheat position |
| None | coiHeaReh | redeclare inner Buildings.Te... | Heating coil in reheat position |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversalLiq | true | = true to allow flow reversal, false restricts to design direction - CHW and HW side |
| Advanced | |||
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at ports of subcomponents is computed |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_Out | Outdoor air intake |
| FluidPort_b | port_Sup | Supply air |
| FluidPort_b | port_SupCol | Dual duct cold deck air supply |
| FluidPort_b | port_SupHot | Dual duct hot deck air supply |
| FluidPort_a | port_Ret | Return air |
| FluidPort_b | port_Rel | Relief (exhaust) air |
| FluidPort_b | port_bChiWat | CHW return port |
| FluidPort_a | port_aChiWat | CHW supply port |
| FluidPort_b | port_bHeaWat | HHW return port |
| FluidPort_a | port_aHeaWat | HHW supply port |
| Bus | bus | AHU control bus |
| Bus | busWea | Weather bus |
| Bus | busTer[nZon] | Terminal unit control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZCoilWaterHeating3WVReheat
Configuration of multiple-zone VAV
Information
This is a configuration model with the same default options as
Buildings.Templates.AirHandlersFans.VAVMultiZone
except for the following options.
| Component | Configuration |
|---|---|
| Heating coil | Hot water coil - Three-way modulating valve - Reheat position |
Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| replaceable package MediumChiWat | Water | CHW medium | |
| replaceable package MediumHeaWat | Water | HHW medium | |
| VAVMultiZone | dat | redeclare Buildings.Template... | Design and operating parameters |
| Configuration | |||
| Integer | nZon | 2 | Number of served zones |
| MixedAirWithDamper | secOutRel | Outdoor/relief/return air section | |
| None | fanSupBlo | redeclare inner Buildings.Te... | Supply fan - Blow through |
| SingleVariable | fanSupDra | redeclare inner Buildings.Te... | Supply fan - Draw through |
| WaterBasedCooling | coiCoo | redeclare inner Buildings.Te... | Cooling coil |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversalLiq | true | = true to allow flow reversal, false restricts to design direction - CHW and HW side |
| Advanced | |||
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at ports of subcomponents is computed |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_Out | Outdoor air intake |
| FluidPort_b | port_Sup | Supply air |
| FluidPort_b | port_SupCol | Dual duct cold deck air supply |
| FluidPort_b | port_SupHot | Dual duct hot deck air supply |
| FluidPort_a | port_Ret | Return air |
| FluidPort_b | port_Rel | Relief (exhaust) air |
| FluidPort_b | port_bChiWat | CHW return port |
| FluidPort_a | port_aChiWat | CHW supply port |
| FluidPort_b | port_bHeaWat | HHW return port |
| FluidPort_a | port_aHeaWat | HHW supply port |
| Bus | bus | AHU control bus |
| Bus | busWea | Weather bus |
| Bus | busTer[nZon] | Terminal unit control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZControlG36Airflow
Configuration of multiple-zone VAV
Information
This is a configuration model with the same default options as
Buildings.Templates.AirHandlersFans.VAVMultiZone
except for the following options.
| Component | Configuration |
|---|---|
| Heating coil | Hot water coil - Two-way modulating valve - Preheat position |
| Cooling coil | Chilled water coil - Two-way modulating valve |
| Controller | Guideline 36 controller - Return fan with airflow tracking control |
Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| replaceable package MediumChiWat | Water | CHW medium | |
| replaceable package MediumHeaWat | Water | HHW medium | |
| VAVMultiZone | dat | redeclare Buildings.Template... | Design and operating parameters |
| Configuration | |||
| Integer | nZon | 2 | Number of served zones |
| MixedAirWithDamper | secOutRel | Outdoor/relief/return air section | |
| None | fanSupBlo | redeclare inner Buildings.Te... | Supply fan - Blow through |
| SingleVariable | fanSupDra | redeclare inner Buildings.Te... | Supply fan - Draw through |
| None | coiHeaReh | redeclare inner Buildings.Te... | Heating coil in reheat position |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversalLiq | true | = true to allow flow reversal, false restricts to design direction - CHW and HW side |
| Advanced | |||
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at ports of subcomponents is computed |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_Out | Outdoor air intake |
| FluidPort_b | port_Sup | Supply air |
| FluidPort_b | port_SupCol | Dual duct cold deck air supply |
| FluidPort_b | port_SupHot | Dual duct hot deck air supply |
| FluidPort_a | port_Ret | Return air |
| FluidPort_b | port_Rel | Relief (exhaust) air |
| FluidPort_b | port_bChiWat | CHW return port |
| FluidPort_a | port_aChiWat | CHW supply port |
| FluidPort_b | port_bHeaWat | HHW return port |
| FluidPort_a | port_aHeaWat | HHW supply port |
| Bus | bus | AHU control bus |
| Bus | busWea | Weather bus |
| Bus | busTer[nZon] | Terminal unit control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZControlG36Pressure
Configuration of multiple-zone VAV
Information
This is a configuration model with the same default options as
Buildings.Templates.AirHandlersFans.VAVMultiZone
except for the following options.
| Component | Configuration |
|---|---|
| Heating coil | Hot water coil - Two-way modulating valve - Preheat position |
| Cooling coil | Chilled water coil - Two-way modulating valve |
| Controller | Guideline 36 controller - Return fan with building pressure control |
Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| replaceable package MediumChiWat | Water | CHW medium | |
| replaceable package MediumHeaWat | Water | HHW medium | |
| VAVMultiZone | dat | redeclare Buildings.Template... | Design and operating parameters |
| Configuration | |||
| Integer | nZon | 2 | Number of served zones |
| MixedAirWithDamper | secOutRel | Outdoor/relief/return air section | |
| None | fanSupBlo | redeclare inner Buildings.Te... | Supply fan - Blow through |
| SingleVariable | fanSupDra | redeclare inner Buildings.Te... | Supply fan - Draw through |
| None | coiHeaReh | redeclare inner Buildings.Te... | Heating coil in reheat position |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversalLiq | true | = true to allow flow reversal, false restricts to design direction - CHW and HW side |
| Advanced | |||
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at ports of subcomponents is computed |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_Out | Outdoor air intake |
| FluidPort_b | port_Sup | Supply air |
| FluidPort_b | port_SupCol | Dual duct cold deck air supply |
| FluidPort_b | port_SupHot | Dual duct hot deck air supply |
| FluidPort_a | port_Ret | Return air |
| FluidPort_b | port_Rel | Relief (exhaust) air |
| FluidPort_b | port_bChiWat | CHW return port |
| FluidPort_a | port_aChiWat | CHW supply port |
| FluidPort_b | port_bHeaWat | HHW return port |
| FluidPort_a | port_aHeaWat | HHW supply port |
| Bus | bus | AHU control bus |
| Bus | busWea | Weather bus |
| Bus | busTer[nZon] | Terminal unit control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZDedicatedDampersPressure
Configuration of multiple-zone VAV
Information
This is a configuration model with the same default options as
Buildings.Templates.AirHandlersFans.VAVMultiZone
except for the following options.
| Component | Configuration |
|---|---|
| Outdoor air section | Separate dedicated OA dampers with differential pressure sensor |
Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| replaceable package MediumChiWat | Water | CHW medium | |
| replaceable package MediumHeaWat | Water | HHW medium | |
| VAVMultiZone | dat | redeclare Buildings.Template... | Design and operating parameters |
| Configuration | |||
| Integer | nZon | 2 | Number of served zones |
| None | fanSupBlo | redeclare inner Buildings.Te... | Supply fan - Blow through |
| SingleVariable | fanSupDra | redeclare inner Buildings.Te... | Supply fan - Draw through |
| WaterBasedHeating | coiHeaPre | redeclare inner Buildings.Te... | Heating coil in preheat position |
| WaterBasedCooling | coiCoo | redeclare inner Buildings.Te... | Cooling coil |
| None | coiHeaReh | redeclare inner Buildings.Te... | Heating coil in reheat position |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversalLiq | true | = true to allow flow reversal, false restricts to design direction - CHW and HW side |
| Advanced | |||
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at ports of subcomponents is computed |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_Out | Outdoor air intake |
| FluidPort_b | port_Sup | Supply air |
| FluidPort_b | port_SupCol | Dual duct cold deck air supply |
| FluidPort_b | port_SupHot | Dual duct hot deck air supply |
| FluidPort_a | port_Ret | Return air |
| FluidPort_b | port_Rel | Relief (exhaust) air |
| FluidPort_b | port_bChiWat | CHW return port |
| FluidPort_a | port_aChiWat | CHW supply port |
| FluidPort_b | port_bHeaWat | HHW return port |
| FluidPort_a | port_aHeaWat | HHW supply port |
| Bus | bus | AHU control bus |
| Bus | busWea | Weather bus |
| Bus | busTer[nZon] | Terminal unit control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZFanRelief
Configuration of multiple-zone VAV
Information
This is a configuration model with the same default options as
Buildings.Templates.AirHandlersFans.VAVMultiZone
except for the following options.
| Component | Configuration |
|---|---|
| Relief/return air section | Relief fan with two-position relief damper |
| Return fan | No fan |
| Relief fan | Single fan - Variable speed |
Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| replaceable package MediumChiWat | Water | CHW medium | |
| replaceable package MediumHeaWat | Water | HHW medium | |
| VAVMultiZone | dat | redeclare Buildings.Template... | Design and operating parameters |
| Configuration | |||
| Integer | nZon | 2 | Number of served zones |
| None | fanSupBlo | redeclare inner Buildings.Te... | Supply fan - Blow through |
| SingleVariable | fanSupDra | redeclare inner Buildings.Te... | Supply fan - Draw through |
| WaterBasedHeating | coiHeaPre | redeclare inner Buildings.Te... | Heating coil in preheat position |
| WaterBasedCooling | coiCoo | redeclare inner Buildings.Te... | Cooling coil |
| None | coiHeaReh | redeclare inner Buildings.Te... | Heating coil in reheat position |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversalLiq | true | = true to allow flow reversal, false restricts to design direction - CHW and HW side |
| Advanced | |||
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at ports of subcomponents is computed |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_Out | Outdoor air intake |
| FluidPort_b | port_Sup | Supply air |
| FluidPort_b | port_SupCol | Dual duct cold deck air supply |
| FluidPort_b | port_SupHot | Dual duct hot deck air supply |
| FluidPort_a | port_Ret | Return air |
| FluidPort_b | port_Rel | Relief (exhaust) air |
| FluidPort_b | port_bChiWat | CHW return port |
| FluidPort_a | port_aChiWat | CHW supply port |
| FluidPort_b | port_bHeaWat | HHW return port |
| FluidPort_a | port_aHeaWat | HHW supply port |
| Bus | bus | AHU control bus |
| Bus | busWea | Weather bus |
| Bus | busTer[nZon] | Terminal unit control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Validation.UserProject.AirHandlersFans.VAVMZFanSupplyBlowThrough
Configuration of multiple-zone VAV
Information
This is a configuration model with the same default options as
Buildings.Templates.AirHandlersFans.VAVMultiZone
except for the following options.
| Component | Configuration |
|---|---|
| Supply fan | Single fan - Variable speed - Blow-through position |
Extends from Buildings.Templates.AirHandlersFans.VAVMultiZone (Multiple-zone VAV).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| replaceable package MediumChiWat | Water | CHW medium | |
| replaceable package MediumHeaWat | Water | HHW medium | |
| VAVMultiZone | dat | redeclare Buildings.Template... | Design and operating parameters |
| Configuration | |||
| Integer | nZon | 2 | Number of served zones |
| MixedAirWithDamper | secOutRel | Outdoor/relief/return air section | |
| WaterBasedHeating | coiHeaPre | redeclare inner Buildings.Te... | Heating coil in preheat position |
| WaterBasedCooling | coiCoo | redeclare inner Buildings.Te... | Cooling coil |
| None | coiHeaReh | redeclare inner Buildings.Te... | Heating coil in reheat position |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversalLiq | true | = true to allow flow reversal, false restricts to design direction - CHW and HW side |
| Advanced | |||
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at ports of subcomponents is computed |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_Out | Outdoor air intake |
| FluidPort_b | port_Sup | Supply air |
| FluidPort_b | port_SupCol | Dual duct cold deck air supply |
| FluidPort_b | port_SupHot | Dual duct hot deck air supply |
| FluidPort_a | port_Ret | Return air |
| FluidPort_b | port_Rel | Relief (exhaust) air |
| FluidPort_b | port_bChiWat | CHW return port |
| FluidPort_a | port_aChiWat | CHW supply port |
| FluidPort_b | port_bHeaWat | HHW return port |
| FluidPort_a | port_aHeaWat | HHW supply port |
| Bus | bus | AHU control bus |
| Bus | busWea | Weather bus |
| Bus | busTer[nZon] | Terminal unit control bus |