Buildings.Templates.AirHandlersFans.Components.ReliefReturnSection
Models for relief/return air section
Information
Components inside that package represent the relief/return air section of an air handler.
Extends from Modelica.Icons.VariantsPackage (Icon for package containing variants).
Package Content
| Name | Description |
|---|---|
| No relief branch | |
| No return branch | |
| Modulating relief damper without fan | |
| Relief fan with two-position relief damper | |
| Return fan with modulating relief damper |
Buildings.Templates.AirHandlersFans.Components.ReliefReturnSection.NoRelief
No relief branch
Information
This model represents a configuration with an air economizer and no relief branch. The return fan is optional.
Extends from Buildings.Templates.AirHandlersFans.Components.Interfaces.PartialReliefReturnSection (Interface class for relief/return air section).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| OutdoorReliefReturnSection | dat | Design and operating parameters | |
| Configuration | |||
| ReliefReturnSection | typ | Buildings.Templates.AirHandl... | Relief/return air section type |
| Damper | typDamRel | Buildings.Templates.Componen... | Relief damper type |
| Fan | typFanRel | Buildings.Templates.Componen... | Relief fan type |
| Fan | typFanRet | fanRet.typ | Return fan type |
| Exhaust/relief/return section | |||
| None | fanRet | redeclare Buildings.Template... | Return fan |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
| FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
| FluidPort_a | port_aHeaRec | Optional fluid connector for heat recovery |
| FluidPort_b | port_bHeaRec | Optional fluid connector for heat recovery |
| FluidPort_b | port_bRet | Optional fluid connector for return branch |
| FluidPort_b | port_bPre | Fluid connector for differential pressure sensor |
| Bus | bus | Control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Components.ReliefReturnSection.NoReturn
No return branch
Information
This model represents a configuration with no air economizer for 100% outdoor air applications (such as DOAS).
Extends from Buildings.Templates.AirHandlersFans.Components.Interfaces.PartialReliefReturnSection (Interface class for relief/return air section).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| OutdoorReliefReturnSection | dat | Design and operating parameters | |
| SingleVariable | fanRet | redeclare Buildings.Template... | Return fan |
| Configuration | |||
| ReliefReturnSection | typ | Buildings.Templates.AirHandl... | Relief/return air section type |
| Damper | typDamRel | damRel.typ | Relief damper type |
| Fan | typFanRel | Buildings.Templates.Componen... | Relief fan type |
| Fan | typFanRet | fanRet.typ | Return fan type |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
| FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
| FluidPort_a | port_aHeaRec | Optional fluid connector for heat recovery |
| FluidPort_b | port_bHeaRec | Optional fluid connector for heat recovery |
| FluidPort_b | port_bRet | Optional fluid connector for return branch |
| FluidPort_b | port_bPre | Fluid connector for differential pressure sensor |
| Bus | bus | Control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Components.ReliefReturnSection.ReliefDamper
Modulating relief damper without fan
Information
This model represents a configuration with an air economizer and an actuated relief damper (modulating) without fan.
Extends from Buildings.Templates.AirHandlersFans.Components.Interfaces.PartialReliefReturnSection (Interface class for relief/return air section).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| OutdoorReliefReturnSection | dat | Design and operating parameters | |
| Configuration | |||
| ReliefReturnSection | typ | Buildings.Templates.AirHandl... | Relief/return air section type |
| Damper | typDamRel | damRel.typ | Relief damper type |
| Fan | typFanRel | Buildings.Templates.Componen... | Relief fan type |
| Fan | typFanRet | Buildings.Templates.Componen... | Return fan type |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
| FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
| FluidPort_a | port_aHeaRec | Optional fluid connector for heat recovery |
| FluidPort_b | port_bHeaRec | Optional fluid connector for heat recovery |
| FluidPort_b | port_bRet | Optional fluid connector for return branch |
| FluidPort_b | port_bPre | Fluid connector for differential pressure sensor |
| Bus | bus | Control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Components.ReliefReturnSection.ReliefFan
Relief fan with two-position relief damper
Information
This model represents a configuration with an air economizer and a relief fan with an actuated relief damper (two-position).
Extends from Buildings.Templates.AirHandlersFans.Components.Interfaces.PartialReliefReturnSection (Interface class for relief/return air section).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| OutdoorReliefReturnSection | dat | Design and operating parameters | |
| SingleVariable | fanRel | redeclare Buildings.Template... | Relief fan |
| Configuration | |||
| ReliefReturnSection | typ | Buildings.Templates.AirHandl... | Relief/return air section type |
| Damper | typDamRel | damRel.typ | Relief damper type |
| Fan | typFanRel | fanRel.typ | Relief fan type |
| Fan | typFanRet | Buildings.Templates.Componen... | Return fan type |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
| FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
| FluidPort_a | port_aHeaRec | Optional fluid connector for heat recovery |
| FluidPort_b | port_bHeaRec | Optional fluid connector for heat recovery |
| FluidPort_b | port_bRet | Optional fluid connector for return branch |
| FluidPort_b | port_bPre | Fluid connector for differential pressure sensor |
| Bus | bus | Control bus |
Modelica definition
Buildings.Templates.AirHandlersFans.Components.ReliefReturnSection.ReturnFan
Return fan with modulating relief damper
Information
This model represents a configuration with an air economizer and a return fan with an actuated relief damper (modulating).
Extends from Buildings.Templates.AirHandlersFans.Components.Interfaces.PartialReliefReturnSection (Interface class for relief/return air section).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package MediumAir | Air | Air medium | |
| OutdoorReliefReturnSection | dat | Design and operating parameters | |
| SingleVariable | fanRet | redeclare Buildings.Template... | Return fan |
| Configuration | |||
| ReliefReturnSection | typ | Buildings.Templates.AirHandl... | Relief/return air section type |
| Damper | typDamRel | damRel.typ | Relief damper type |
| Fan | typFanRel | Buildings.Templates.Componen... | Relief fan type |
| Fan | typFanRet | fanRet.typ | Return fan type |
| Dynamics | |||
| Conservation equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
| FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
| FluidPort_a | port_aHeaRec | Optional fluid connector for heat recovery |
| FluidPort_b | port_bHeaRec | Optional fluid connector for heat recovery |
| FluidPort_b | port_bRet | Optional fluid connector for return branch |
| FluidPort_b | port_bPre | Fluid connector for differential pressure sensor |
| Bus | bus | Control bus |