Buildings.Templates.Components.Dampers
Damper models
Information
This package contains models for dampers.
Extends from Modelica.Icons.VariantsPackage (Icon for package containing variants).
Package Content
| Name | Description |
|---|---|
| Modulating damper | |
| No damper | |
| Pressure independent damper | |
| Two-position damper |
Buildings.Templates.Components.Dampers.Modulating
Modulating damper
Information
This is a model for a modulating damper.
-
The damper opening is modulated with a fractional opening
signal
y(real).
y = 0corresponds to fully closed.y = 1corresponds to fully open. -
The actual damper position
y_actual(real) is returned.
y_actual = 0corresponds to fully closed.y_actual = 1corresponds to fully open.
Extends from Buildings.Templates.Components.Interfaces.PartialDamper (Interface class for damper).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package Medium | PartialMedium | Medium in the component | |
| Damper | dat | Design and operating parameters | |
| Configuration | |||
| Damper | typ | Buildings.Templates.Componen... | Equipment type |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal |
| Advanced | |||
| MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at port is computed |
| Dynamics | |||
| Filtered opening | |||
| Boolean | use_inputFilter | true | = true, if opening is filtered with a 2nd order CriticalDamping filter |
| Time | riseTime | 120 | Rise time of the filter (time to reach 99.6 % of an opening step) [s] |
| Init | init | Modelica.Blocks.Types.Init.I... | Type of initialization (no init/steady state/initial state/initial output) |
| Real | y_start | 1 | Initial position of actuator |
| Graphics | |||
| DamperBlades | typBla | Buildings.Templates.Componen... | Type of blades |
| Integer | text_rotation | 0 | Text rotation angle in icon layer |
| Boolean | text_flip | false | True to flip text horizontally in icon layer |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
| FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
| Bus | bus | Control bus |
Modelica definition
Buildings.Templates.Components.Dampers.None
No damper
Information
This is a direct fluid pass-through model to represent a configuration with no damper.
Extends from Buildings.Templates.Components.Interfaces.PartialDamper (Interface class for damper).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package Medium | PartialMedium | Medium in the component | |
| Damper | dat | Design and operating parameters | |
| Configuration | |||
| Damper | typ | Buildings.Templates.Componen... | Equipment type |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal |
| Advanced | |||
| MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at port is computed |
| Dynamics | |||
| Filtered opening | |||
| Boolean | use_inputFilter | true | = true, if opening is filtered with a 2nd order CriticalDamping filter |
| Time | riseTime | 120 | Rise time of the filter (time to reach 99.6 % of an opening step) [s] |
| Init | init | Modelica.Blocks.Types.Init.I... | Type of initialization (no init/steady state/initial state/initial output) |
| Real | y_start | 1 | Initial position of actuator |
| Graphics | |||
| DamperBlades | typBla | Buildings.Templates.Componen... | Type of blades |
| Integer | text_rotation | 0 | Text rotation angle in icon layer |
| Boolean | text_flip | false | True to flip text horizontally in icon layer |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
| FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
| Bus | bus | Control bus |
Modelica definition
Buildings.Templates.Components.Dampers.PressureIndependent
Pressure independent damper
Information
This is a model for a pressure independent damper.
-
The airflow setpoint is modulated with a fractional
airflow signal
y(real).
y = 0corresponds to zero airflow.y = 1corresponds to the maximum airflow. -
The actual damper position
y_actual(real) is returned.
y_actual = 0corresponds to fully closed.y_actual = 1corresponds to fully open.
Extends from Buildings.Templates.Components.Interfaces.PartialDamper (Interface class for damper).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package Medium | PartialMedium | Medium in the component | |
| Damper | dat | Design and operating parameters | |
| Configuration | |||
| Damper | typ | Buildings.Templates.Componen... | Equipment type |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal |
| Advanced | |||
| MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at port is computed |
| Dynamics | |||
| Filtered opening | |||
| Boolean | use_inputFilter | true | = true, if opening is filtered with a 2nd order CriticalDamping filter |
| Time | riseTime | 120 | Rise time of the filter (time to reach 99.6 % of an opening step) [s] |
| Init | init | Modelica.Blocks.Types.Init.I... | Type of initialization (no init/steady state/initial state/initial output) |
| Real | y_start | 1 | Initial position of actuator |
| Graphics | |||
| DamperBlades | typBla | Buildings.Templates.Componen... | Type of blades |
| Integer | text_rotation | 0 | Text rotation angle in icon layer |
| Boolean | text_flip | false | True to flip text horizontally in icon layer |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
| FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
| Bus | bus | Control bus |
Modelica definition
Buildings.Templates.Components.Dampers.TwoPosition
Two-position damper
Information
This is a model for a two-position damper.
-
The damper is commanded open with a Boolean signal
y1.
y1 = 0corresponds to fully closed.y1 = 1corresponds to fully open. -
The open end switch status
y1_actualand closed end switch statusy0_actual(Booleans) are returned.
y1_actual = falsecorresponds to fully closed.y1_actual = truecorresponds to fully open. And the opposite fory0_actual.
Extends from Buildings.Templates.Components.Interfaces.PartialDamper (Interface class for damper).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| replaceable package Medium | PartialMedium | Medium in the component | |
| Damper | dat | Design and operating parameters | |
| Configuration | |||
| Damper | typ | Buildings.Templates.Componen... | Equipment type |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal |
| Advanced | |||
| MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at port is computed |
| Dynamics | |||
| Filtered opening | |||
| Boolean | use_inputFilter | true | = true, if opening is filtered with a 2nd order CriticalDamping filter |
| Time | riseTime | 120 | Rise time of the filter (time to reach 99.6 % of an opening step) [s] |
| Init | init | Modelica.Blocks.Types.Init.I... | Type of initialization (no init/steady state/initial state/initial output) |
| Real | y_start | 1 | Initial position of actuator |
| Graphics | |||
| DamperBlades | typBla | Buildings.Templates.Componen... | Type of blades |
| Integer | text_rotation | 0 | Text rotation angle in icon layer |
| Boolean | text_flip | false | True to flip text horizontally in icon layer |
Connectors
| Type | Name | Description |
|---|---|---|
| FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) |
| FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) |
| Bus | bus | Control bus |