Buildings.Templates.AirHandlersFans.Components.Data
Records for design and operating parameters
Information
This package provides records for design and operating parameters.
Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).
Package Content
Name | Description |
---|---|
OutdoorReliefReturnSection | Record for outdoor/relief/return air section |
PartialController | Record for controller interface class |
VAVMultiZoneController | Record for multiple-zone VAV controller |
Buildings.Templates.AirHandlersFans.Components.Data.OutdoorReliefReturnSection
Record for outdoor/relief/return air section
Information
This record provides the set of sizing and operating parameters for the classes within Buildings.Templates.AirHandlersFans.Components.OutdoorReliefReturnSection.
Extends from Modelica.Icons.Record (Icon for records).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Configuration | |||
Damper | typDamOut | Outdoor air damper type | |
Damper | typDamOutMin | Minimum outdoor air damper type | |
Damper | typDamRel | Relief damper type | |
Damper | typDamRet | Return damper type | |
Fan | typFanRel | Type of relief fan | |
Fan | typFanRet | Type of return fan | |
Dampers and economizers | |||
MassFlowRate | mOutMin_flow_nominal | Minimum outdoor air mass flow rate at design conditions [kg/s] | |
Damper | damOut | damOut(final typ=typDamOut) | Outdoor air damper |
Damper | damOutMin | damOutMin(final typ=typDamOu... | Minimum outdoor air damper |
Damper | damRel | damRel(final typ=typDamRel) | Relief damper |
Damper | damRet | damRet(final typ=typDamRet) | Return damper |
Fans | |||
Fan | fanRel | fanRel(final typ=typFanRel) | Relief fan |
Fan | fanRet | fanRet(final typ=typFanRet) | Return fan |
Modelica definition
Buildings.Templates.AirHandlersFans.Components.Data.PartialController
Record for controller interface class
Information
This record provides the set of sizing and operating parameters for the class Buildings.Templates.AirHandlersFans.Components.Controls.Interfaces.PartialController.
Extends from Modelica.Icons.Record (Icon for records).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Configuration | |||
Controller | typ | Type of controller | |
Fan | typFanSup | Type of supply fan | |
Fan | typFanRel | Type of relief fan | |
Fan | typFanRet | Type of return fan |
Modelica definition
Buildings.Templates.AirHandlersFans.Components.Data.VAVMultiZoneController
Record for multiple-zone VAV controller
Information
This record provides the set of sizing and operating parameters for multiple-zone VAV controllers within Buildings.Templates.AirHandlersFans.Components.Controls.
Extends from Buildings.Templates.AirHandlersFans.Components.Data.PartialController (Record for controller interface class).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Configuration | |||
Controller | typ | Type of controller | |
Fan | typFanSup | Type of supply fan | |
Fan | typFanRel | Type of relief fan | |
Fan | typFanRet | Type of return fan | |
OutdoorAirSection | typSecOut | Type of outdoor air section | |
BuildingPressureControlTypes | buiPreCon | Type of building pressure control system | |
Energy and ventilation standards | |||
VentilationStandard | stdVen | Ventilation standard | |
Temperature setpoints | |||
Temperature | TAirSupSet_min | 12 + 273.15 | Lowest supply air temperature setpoint [K] |
Temperature | TAirSupSet_max | 18 + 273.15 | Highest supply air temperature setpoint [K] |
Temperature | TOutRes_min | 16 + 273.15 | Lowest value of the outdoor air temperature reset range [K] |
Temperature | TOutRes_max | 21 + 273.15 | Highest value of the outdoor air temperature reset range [K] |
Ventilation setpoints | |||
VolumeFlowRate | VOutUnc_flow_nominal | Uncorrected design outdoor air flow rate, including diversity where applicable [m3/s] | |
VolumeFlowRate | VOutTot_flow_nominal | Design total outdoor air flow rate [m3/s] | |
VolumeFlowRate | VOutAbsMin_flow_nominal | Design outdoor air flow rate when all zones with CO2 sensors or occupancy sensors are unpopulated [m3/s] | |
VolumeFlowRate | VOutMin_flow_nominal | Design minimum outdoor air flow rate when all zones are occupied at their design population, including diversity [m3/s] | |
Information provided by testing, adjusting, and balancing contractor | |||
PressureDifference | pAirSupSet_rel_max | Duct design maximum static pressure [Pa] | |
PressureDifference | dpDamOutMinAbs | Differential pressure across the minimum outdoor air damper that provides the absolute minimum outdoor airflow [Pa] | |
PressureDifference | dpDamOutMin_nominal | Differential pressure across the minimum outdoor air damper that provides the design minimum outdoor airflow [Pa] | |
PressureDifference | pAirRetSet_rel_min | 10 | Return fan minimum discharge static pressure setpoint [Pa] |
PressureDifference | pAirRetSet_rel_max | 40 | Return fan maximum discharge static pressure setpoint [Pa] |
VolumeFlowRate | dVFanRet_flow | Airflow differential between supply and return fans to maintain building pressure at setpoint [m3/s] | |
Real | yFanSup_min | 0.1 | Lowest allowed fan speed if fan is on [1] |
Real | yFanRel_min | 0.1 | Minimum relief fan speed [1] |
Real | yFanRet_min | 0.1 | Minimum return fan speed [1] |