This package contains examples for the use of models that can be found in Buildings.HeatTransfer.Windows.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
| Name | Description | 
|---|---|
| Test model for the window | |
| Test model for the heat transfer at the window boundary condition | 
Buildings.HeatTransfer.Windows.Examples.Window
| Type | Name | Default | Description | 
|---|---|---|---|
| Area | A | 1 | Window surface area [m2] | 
| Real | fFra | 0.2 | Fraction of frame, = frame area divided by total area | 
| Boolean | linearize | false | Set to true to linearize emissive power | 
| Angle | lat | 0.34906585039887 | Latitude [rad] | 
| Angle | azi | 0 | Surface azimuth [rad] | 
| Angle | til | 1.5707963267949 | Surface tilt [rad] | 
| Type | Name | Description | 
|---|---|---|
| Bus | weaBus | 
model Window "Test model for the window"
  import Buildings;
  extends Modelica.Icons.Example;
  parameter Modelica.SIunits.Area A=1 "Window surface area";
  parameter Real fFra=0.2 
    "Fraction of frame, = frame area divided by total area";
  parameter Boolean linearize = false "Set to true to linearize emissive power";
  parameter Modelica.SIunits.Angle lat=0.34906585039887 "Latitude";
  parameter Modelica.SIunits.Angle azi=0 "Surface azimuth";
  parameter Modelica.SIunits.Angle til=1.5707963267949 "Surface tilt";
  Buildings.HeatTransfer.Windows.Window window(
    A=A,
    fFra=fFra,
    glaSys=glaSys,
    linearize=linearize,
    til=til) "Window";
  Buildings.HeatTransfer.Windows.InteriorHeatTransfer intCon(A=A, fFra=fFra,
    linearizeRadiation=linearize,
    absIRSha_air=glaSys.shade.absIR_a,
    absIRSha_glass=glaSys.shade.absIR_b,
    tauIRSha_air=glaSys.shade.tauIR_a,
    tauIRSha_glass=glaSys.shade.tauIR_b,
    haveExteriorShade=glaSys.haveExteriorShade,
    haveInteriorShade=glaSys.haveInteriorShade) 
    "Room-side convective heat transfer";
  Buildings.HeatTransfer.Windows.ExteriorHeatTransfer extCon(A=A, fFra=fFra,
    linearizeRadiation=linearize,
    absIRSha_air=glaSys.shade.absIR_a,
    absIRSha_glass=glaSys.shade.absIR_b,
    tauIRSha_air=glaSys.shade.tauIR_a,
    tauIRSha_glass=glaSys.shade.tauIR_b,
    haveExteriorShade=glaSys.haveExteriorShade,
    haveInteriorShade=glaSys.haveInteriorShade,
    F_sky=0.5) "Exterior convective heat transfer";
  Modelica.Blocks.Sources.Constant TRooAir(k=293.15, y(unit="K")) 
    "Room air temperature";
  Modelica.Blocks.Sources.Ramp uSha(duration=0.5, startTime=0.25) 
    "Shading control signal";
  Buildings.HeatTransfer.Sources.PrescribedTemperature TOuts 
    "Outside air temperature";
  Buildings.HeatTransfer.Sources.PrescribedTemperature TRAir 
    "Room air temperature";
  Modelica.Blocks.Sources.Constant fClr(k=0) "Fraction of sky that is clear";
  Buildings.HeatTransfer.Radiosity.IndoorRadiosity indRad(A=A) 
    "Model for indoor radiosity";
  Buildings.HeatTransfer.Sources.FixedHeatFlow fixedHeatFlow(Q_flow=0);
  Buildings.HeatTransfer.Data.GlazingSystems.DoubleClearAir13Clear glaSys(
    shade=Buildings.HeatTransfer.Data.Shades.Gray(),
    haveExteriorShade=false,
    haveInteriorShade=true);
  Buildings.BoundaryConditions.SolarIrradiation.DirectTiltedSurface HDirTil(
    til=til,
    lat=lat,
    azi=azi);
  Buildings.BoundaryConditions.SolarIrradiation.DiffuseIsotropic HDifTilIso(
               til=til);
  Buildings.BoundaryConditions.WeatherData.ReaderTMY3 weaDat(
                                                        filNam=
        "Resources/weatherdata/USA_IL_Chicago-OHare.Intl.AP.725300_TMY3.mos");
  Modelica.Blocks.Math.Gain HRoo(k=0.1) "Solar irradiation from room";
  Buildings.HeatTransfer.Windows.BaseClasses.WindowRadiation winRad(
    AWin=1,
    N=glaSys.nLay,
    tauGlaSol=glaSys.glass.tauSol,
    rhoGlaSol_a=glaSys.glass.rhoSol_a,
    rhoGlaSol_b=glaSys.glass.rhoSol_b,
    tauShaSol_a=glaSys.shade.tauSol_a,
    tauShaSol_b=glaSys.shade.tauSol_b,
    rhoShaSol_a=glaSys.shade.rhoSol_a,
    rhoShaSol_b=glaSys.shade.rhoSol_b,
    haveExteriorShade=glaSys.haveExteriorShade,
    haveInteriorShade=glaSys.haveInteriorShade);
  Buildings.BoundaryConditions.WeatherData.Bus weaBus; 
equation 
  connect(uSha.y, extCon.uSha);
  connect(uSha.y, window.uSha);
  connect(uSha.y, intCon.uSha);
  connect(TOuts.port, extCon.air);
  connect(TRAir.port, intCon.air);
  connect(TRooAir.y, TRAir.T);
  connect(window.glaUns_b, intCon.glaUns);
  connect(window.glaSha_b, intCon.glaSha);
  connect(window.glaUns_a, extCon.glaUns);
  connect(window.glaSha_a, extCon.glaSha);
  connect(window.fra_a, extCon.frame);
  connect(window.fra_b, intCon.frame);
  connect(extCon.JOutUns, window.JInUns_a);
  connect(extCon.JInUns, window.JOutUns_a);
  connect(extCon.JOutSha, window.JInSha_a);
  connect(extCon.JInSha, window.JOutSha_a);
  connect(window.JOutUns_b, intCon.JInUns);
  connect(intCon.JOutUns, window.JInUns_b);
  connect(window.JOutSha_b, intCon.JInSha);
  connect(intCon.JOutSha, window.JInSha_b);
  connect(fClr.y, extCon.f_clr);
  connect(indRad.JOut, intCon.JInRoo);
  connect(intCon.JOutRoo, indRad.JIn);
  connect(fixedHeatFlow.port, indRad.heatPort);
  connect(winRad.QTra_flow,HRoo. u);
  connect(HRoo.y,winRad. HRoo);
  connect(HDifTilIso.H, winRad.HDif);
  connect(HDirTil.H, winRad.HDir);
  connect(HDirTil.inc, winRad.incAng);
  connect(winRad.QAbsExtSha_flow, extCon.QAbs_flow);
  connect(winRad.QAbsIntSha_flow, intCon.QAbs_flow);
  connect(winRad.QAbsGlaUns_flow, window.QAbsUns_flow);
  connect(winRad.QAbsGlaSha_flow, window.QAbsSha_flow);
  connect(weaDat.weaBus, weaBus);
  connect(weaBus, HDirTil.weaBus);
  connect(HDifTilIso.weaBus, weaBus);
  connect(TOuts.T, weaBus.TDryBul);
  connect(uSha.y, winRad.uSha);
  connect(weaBus.winSpe, extCon.vWin); 
end Window;
 
Buildings.HeatTransfer.Windows.Examples.BoundaryHeatTransfer
| Type | Name | Default | Description | 
|---|---|---|---|
| Area | A | 1 | Window surface area [m2] | 
| Real | fFra | 0.2 | Fraction of frame, = frame area divided by total area | 
| Boolean | linearizeRadiation | false | Set to true to linearize emissive power | 
model BoundaryHeatTransfer 
  "Test model for the heat transfer at the window boundary condition"
  import Buildings;
  extends Modelica.Icons.Example;
  parameter Modelica.SIunits.Area A=1 "Window surface area";
  parameter Real fFra=0.2 
    "Fraction of frame, = frame area divided by total area";
  parameter Boolean linearizeRadiation = false 
    "Set to true to linearize emissive power";
  Buildings.HeatTransfer.Windows.ExteriorHeatTransfer extCon(A=A, fFra=fFra,
    linearizeRadiation=linearizeRadiation,
    absIRSha_air=glaSys.shade.absIR_a,
    absIRSha_glass=glaSys.shade.absIR_b,
    tauIRSha_air=glaSys.shade.tauIR_a,
    tauIRSha_glass=glaSys.shade.tauIR_b,
    haveExteriorShade=glaSys.haveExteriorShade,
    haveInteriorShade=glaSys.haveInteriorShade,
    F_sky=0.5) "Exterior convective heat transfer";
  Modelica.Blocks.Sources.Constant TOut(y(unit="K"), k=273.15) 
    "Outside air temperature";
  Modelica.Blocks.Sources.Constant TRooAir(k=293.15, y(unit="K")) 
    "Room air temperature";
  Modelica.Blocks.Sources.Constant TRooRad(k=293.15, y(unit="K")) 
    "Room radiative temperature";
  Modelica.Blocks.Sources.Ramp uSha(duration=1, startTime=0) 
    "Shading control signal";
  Modelica.Blocks.Sources.Constant vWin(k=1) "Wind speed";
  Buildings.HeatTransfer.Sources.PrescribedTemperature TOuts 
    "Outside air temperature";
  Buildings.HeatTransfer.Sources.PrescribedTemperature TRAir 
    "Room air temperature";
  Modelica.Blocks.Sources.Constant fClr(k=0) "Fraction of sky that is clear"; 
  Buildings.HeatTransfer.Data.GlazingSystems.DoubleClearAir13Clear glaSys2(
    shade=Buildings.HeatTransfer.Data.Shades.Gray(),
    UFra=2,
    haveInteriorShade=false,
    haveExteriorShade=false) "Parameters for glazing system";
  Buildings.HeatTransfer.Data.GlazingSystems.SingleClear3 glaSys1(UFra=2);
  Buildings.HeatTransfer.Data.GlazingSystems.TripleClearAir13ClearAir13Clear
    glaSys3(UFra=1) "Parameters for glazing system";
  Buildings.HeatTransfer.Data.GlazingSystems.DoubleClearAir13Clear glaSys(
    shade=Buildings.HeatTransfer.Data.Shades.Gray(),
    UFra=1.5,
    haveExteriorShade=true,
    haveInteriorShade=false) "Parameters for glazing system";
 Buildings.HeatTransfer.Radiosity.IndoorRadiosity radIn(
    final linearize=linearizeRadiation, final A=A) "Indoor radiosity";
protected 
  Buildings.HeatTransfer.Radiosity.RadiositySplitter radShaOut 
    "Radiosity that strikes shading device";
public 
  Buildings.HeatTransfer.Windows.BaseClasses.ShadingSignal shaSig(haveShade=true) 
    "Conversion for shading signal";
  Buildings.HeatTransfer.Sources.PrescribedTemperature TRAir1 
    "Room air temperature";
  Buildings.HeatTransfer.Sources.PrescribedTemperature TRAir2 
    "Room air temperature";
  Buildings.HeatTransfer.Sources.PrescribedTemperature TRAir3 
    "Room air temperature";
  Modelica.Blocks.Sources.Constant QAbsSW_flow(k=0) "Absorbed solar radiation"; 
equation 
  connect(uSha.y, extCon.uSha);
  connect(TOuts.port, extCon.air);
  connect(TRooAir.y, TRAir.T);
  connect(fClr.y, extCon.f_clr);
  connect(extCon.vWin, vWin.y);
  connect(TOuts.T, TOut.y);
  connect(shaSig.y,radShaOut. u);
  connect(radIn.JOut, radShaOut.JIn);
  connect(shaSig.u, uSha.y);
  connect(radShaOut.JOut_2, extCon.JInUns);
  connect(radShaOut.JOut_1, extCon.JInSha);
  connect(radIn.heatPort, TRAir.port);
  connect(extCon.JOutUns, radIn.JIn);
  connect(extCon.JOutSha, radIn.JIn);
  connect(TRooAir.y, TRAir1.T);
  connect(TRooAir.y, TRAir2.T);
  connect(TRooAir.y, TRAir3.T);
  connect(TRAir1.port, extCon.glaUns);
  connect(TRAir2.port, extCon.glaSha);
  connect(TRAir3.port, extCon.frame);
  connect(extCon.QAbs_flow, QAbsSW_flow.y); 
end BoundaryHeatTransfer;