Buildings.Fluid.Storage

Package with thermal energy storage models

Information


This package contains thermal energy storage models.

Package Content

NameDescription
Buildings.Fluid.Storage.BaseClasses BaseClasses Package with base classes for tank models
Buildings.Fluid.Storage.Examples Examples Collection of models that illustrate model use and test models
Buildings.Fluid.Storage.Stratified Stratified Model of a stratified tank for thermal energy storage
Buildings.Fluid.Storage.StratifiedEnhanced StratifiedEnhanced Stratified tank model with enhanced discretization


Buildings.Fluid.Storage.Stratified Buildings.Fluid.Storage.Stratified

Model of a stratified tank for thermal energy storage

Buildings.Fluid.Storage.Stratified

Information


This is a model of a stratified storage tank. The tank uses several volumes to model the stratification. Heat conduction is modeled between the volumes through the fluid, and between the volumes and the ambient. The port heaPorVol may be used to connect a temperature sensor that measures the fluid temperature of an individual volume. It may also be used to add heat to individual volumes.

The heat ports outside the tank insulation can be used to specify an ambient temperature. Leave these ports unconnected to force adiabatic boundary conditions. Note, however, that all heat conduction elements through the tank wall (but not the top and bottom) are connected to the heat port heaPorSid. Thus, not connecting heaPorSid means an adiabatic boundary condition in the sense that heaPorSid.Q_flow = 0. This, however, still allows heat to flow through the tank walls, modelled by conWal, from one fluid volume to another one.

For a model with enhanced stratification, use Buildings.Fluid.Storage.StratifiedEnhanced.


Extends from Buildings.Fluid.Interfaces.PartialStaticTwoPortInterface (Partial model transporting fluid between two ports without storing mass or energy), Buildings.BaseClasses.BaseIcon (Base icon).

Parameters

TypeNameDefaultDescription
replaceable package MediumPartialMediumMedium in the component
VolumeVTan Tank volume [m3]
LengthhTan Height of tank (without insulation) [m]
LengthdIns Thickness of insulation [m]
ThermalConductivitykIns0.04Specific heat conductivity of insulation [W/(m.K)]
IntegernSeg2Number of volume segments
Timetau1Time constant for mixing due to temperature inversion [s]
Nominal condition
MassFlowRatem_flow_nominal Nominal mass flow rate [kg/s]
Initialization
MassFlowRatem_flow.start0Mass flow rate from port_a to port_b (m_flow > 0 is design flow direction) [kg/s]
Pressuredp.start0Pressure difference between port_a and port_b [Pa]
Assumptions
BooleanallowFlowReversalsystem.allowFlowReversal= true to allow flow reversal, false restricts to design direction (port_a -> port_b)
Dynamics
DynamicsenergyDynamicssystem.energyDynamicsFormulation of energy balance
DynamicsmassDynamicssystem.massDynamicsFormulation of mass balance
Advanced
MassFlowRatem_flow_small1E-4*m_flow_nominalSmall mass flow rate for regularization of zero flow [kg/s]
Diagnostics
Booleanshow_V_flowtrue= true, if volume flow rate at inflowing port is computed
Initialization
AbsolutePressurep_a_startp_startGuess value for inlet pressure [Pa]
AbsolutePressurep_b_startp_startGuess value for outlet pressure [Pa]
AbsolutePressurep_startsystem.p_startStart value of pressure [Pa]
Booleanuse_T_starttrue= true, use T_start, otherwise h_start
TemperatureT_startif use_T_start then system.T...Start value of temperature [K]
SpecificEnthalpyh_startif use_T_start then Medium.s...Start value of specific enthalpy [J/kg]
MassFractionX_start[Medium.nX]Medium.X_defaultStart value of mass fractions m_i/m [kg/kg]
ExtraPropertyC_start[Medium.nC]fill(0, Medium.nC)Start value of trace substances

Connectors

TypeNameDescription
FluidPort_aport_aFluid connector a (positive design flow direction is from port_a to port_b)
FluidPort_bport_bFluid connector b (positive design flow direction is from port_a to port_b)
replaceable package Medium 
HeatPort_aheaPorVol[nSeg]Heat port of fluid volumes
HeatPort_aheaPorSidHeat port tank side (outside insulation)
HeatPort_aheaPorTopHeat port tank top (outside insulation)
HeatPort_aheaPorBotHeat port tank bottom (outside insulation). Leave unconnected for adiabatic condition
output RealOutputQl_flowHeat loss of tank (positve if heat flows from to ambient)

Modelica definition

model Stratified 
  "Model of a stratified tank for thermal energy storage"
  extends Buildings.Fluid.Interfaces.PartialStaticTwoPortInterface(final 
      p_a_start =                                                                     p_start,
                                                                    final 
      p_b_start =                                                                     p_start);
  extends Buildings.BaseClasses.BaseIcon;
  replaceable package Medium = 
      Modelica.Media.Interfaces.PartialSimpleMedium;
  import Modelica.Fluid.Types;
  import Modelica.Fluid.Types.Dynamics;
  parameter Modelica.SIunits.Volume VTan "Tank volume";
  parameter Modelica.SIunits.Length hTan "Height of tank (without insulation)";
  parameter Modelica.SIunits.Length dIns "Thickness of insulation";
  parameter Modelica.SIunits.ThermalConductivity kIns = 0.04 
    "Specific heat conductivity of insulation";
  parameter Integer nSeg(min=2) = 2 "Number of volume segments";

  ////////////////////////////////////////////////////////////////////
  // Assumptions
  parameter Types.Dynamics energyDynamics=system.energyDynamics 
    "Formulation of energy balance";
  parameter Types.Dynamics massDynamics=system.massDynamics 
    "Formulation of mass balance";

  // Initialization
  parameter Medium.AbsolutePressure p_start = system.p_start 
    "Start value of pressure";
  parameter Boolean use_T_start = true "= true, use T_start, otherwise h_start";
  parameter Medium.Temperature T_start=
    if use_T_start then system.T_start else Medium.temperature_phX(p_start,h_start,X_start) 
    "Start value of temperature";
  parameter Medium.SpecificEnthalpy h_start=
    if use_T_start then Medium.specificEnthalpy_pTX(p_start, T_start, X_start) else Medium.h_default 
    "Start value of specific enthalpy";
  parameter Medium.MassFraction X_start[Medium.nX] = Medium.X_default 
    "Start value of mass fractions m_i/m";
  parameter Medium.ExtraProperty C_start[Medium.nC](
       quantity=Medium.extraPropertiesNames)=fill(0, Medium.nC) 
    "Start value of trace substances";

  ////////////////////////////////////////////////////////////////////

  MixingVolumes.MixingVolume[nSeg] vol(
    redeclare each package Medium = Medium,
    each energyDynamics=energyDynamics,
    each massDynamics=massDynamics,
    each p_start=p_start,
    each use_T_start=use_T_start,
    each T_start=T_start,
    each h_start=h_start,
    each X_start=X_start,
    each C_start=C_start,
    each V=VTan/nSeg,
    each nPorts=nPorts,
    each m_flow_small = m_flow_small,
    each use_HeatTransfer=true,
    redeclare each model HeatTransfer = 
        Modelica.Fluid.Vessels.BaseClasses.HeatTransfer.IdealHeatTransfer) 
    "Tank segment";
  Sensors.EnthalpyFlowRate hA(redeclare package Medium = Medium);
  Sensors.EnthalpyFlowRate[nSeg-1] hVol_flow(redeclare package Medium = Medium);
  Sensors.EnthalpyFlowRate hB(redeclare package Medium = Medium);
  BaseClasses.Buoyancy buo(
    redeclare package Medium = Medium,
    V=VTan,
    nSeg=nSeg,
    tau=tau) "Model to prevent unstable tank stratification";
  parameter Modelica.SIunits.Time tau=1 
    "Time constant for mixing due to temperature inversion";
  Modelica.Thermal.HeatTransfer.Components.ThermalConductor[
                                                 nSeg - 1] conFlu(
                                                                each G=conFluSeg) 
    "Thermal conductance in fluid between the segments";
  Modelica.Thermal.HeatTransfer.Components.ThermalConductor[
                                                 nSeg] conWal(
     each G=2*Modelica.Constants.pi*kIns*hSeg/ln((rTan+dIns)/rTan)) 
    "Thermal conductance through tank wall";
  Modelica.Thermal.HeatTransfer.Components.ThermalConductor conTop(
     G=conTopSeg) "Thermal conductance through tank top";
  Modelica.Thermal.HeatTransfer.Components.ThermalConductor conBot(
     G=conTopSeg) "Thermal conductance through tank bottom";
  Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a[nSeg] heaPorVol 
    "Heat port of fluid volumes";
  Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a heaPorSid 
    "Heat port tank side (outside insulation)";
  Modelica.Thermal.HeatTransfer.Sensors.HeatFlowSensor heaFloSid[
                                                         nSeg] 
    "Heat flow at wall of tank (outside insulation)";
  Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a heaPorTop 
    "Heat port tank top (outside insulation)";
  Modelica.Thermal.HeatTransfer.Sensors.HeatFlowSensor heaFloTop 
    "Heat flow at top of tank (outside insulation)";
  Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a heaPorBot 
    "Heat port tank bottom (outside insulation). Leave unconnected for adiabatic condition";
  Modelica.Thermal.HeatTransfer.Sensors.HeatFlowSensor heaFloBot 
    "Heat flow at bottom of tank (outside insulation)";
  Modelica.Blocks.Interfaces.RealOutput Ql_flow 
    "Heat loss of tank (positve if heat flows from to ambient)";

protected 
  constant Integer nPorts = 2 "Number of ports of volume";
  parameter Modelica.SIunits.Length hSeg = hTan / nSeg 
    "Height of a tank segment";
  parameter Modelica.SIunits.Area ATan = VTan/hTan 
    "Tank cross-sectional area (without insulation)";
  parameter Modelica.SIunits.Length rTan = sqrt(ATan/Modelica.Constants.pi) 
    "Tank diameter (without insulation)";
  parameter Modelica.SIunits.ThermalConductance conFluSeg = ATan*Medium.lambda_const/hSeg 
    "Thermal conductance between fluid volumes";
  parameter Modelica.SIunits.ThermalConductance conTopSeg = 1/(1/conFluSeg+1/(ATan*kIns/dIns)) 
    "Thermal conductance from center of top (or bottom) volume through tank insulation at top (or bottom)";

protected 
  Modelica.Blocks.Routing.Multiplex3 mul(
    n1=1,
    n2=nSeg,
    n3=1);
  Modelica.Blocks.Math.Sum sum1(nin=nSeg + 2);
equation 
  connect(hA.port_b, vol[1].ports[1]);
  connect(vol[nSeg].ports[2], hB.port_a);
  connect(hB.port_b, port_b);
  for i in 1:(nSeg-1) loop

  connect(vol[i].ports[2], hVol_flow[i].port_a);
  connect(hVol_flow[i].port_b, vol[i+1].ports[1]);
  end for;
  connect(port_a, hA.port_a);
  connect(buo.heatPort, vol.heatPort);
  for i in 1:nSeg-1 loop
  // heat conduction between fluid nodes
     connect(vol[i].heatPort, conFlu[i].port_a);
    connect(vol[i+1].heatPort, conFlu[i].port_b);
  end for;
  connect(vol[1].heatPort, conTop.port_a);
  connect(vol.heatPort, conWal.port_a);
  connect(conBot.port_a, vol[nSeg].heatPort);
  connect(vol.heatPort, heaPorVol);
  connect(conWal.port_b, heaFloSid.port_a);
  for i in 1:nSeg loop

    connect(heaFloSid[i].port_b, heaPorSid);
  end for;

  connect(conTop.port_b, heaFloTop.port_a);
  connect(conBot.port_b, heaFloBot.port_a);
  connect(heaFloTop.port_b, heaPorTop);
  connect(heaFloBot.port_b, heaPorBot);
  connect(heaFloTop.Q_flow, mul.u1[1]);
  connect(heaFloSid.Q_flow, mul.u2);
  connect(heaFloBot.Q_flow, mul.u3[1]);
  connect(mul.y, sum1.u);
  connect(sum1.y, Ql_flow);
end Stratified;

Buildings.Fluid.Storage.StratifiedEnhanced Buildings.Fluid.Storage.StratifiedEnhanced

Stratified tank model with enhanced discretization

Buildings.Fluid.Storage.StratifiedEnhanced

Information


This is a model of a stratified storage tank for thermal energy storage. The model is identical to Buildings.Fluid.Storage.Stratified, except that it adds a correction that reduces the numerical dissipation. The correction is identical to the one described by Wischhusen (2006).

References

Wischhusen Stefan, An Enhanced Discretization Method for Storage Tank Models within Energy Systems, Modelica Conference, Vienna, Austria, September 2006.


Extends from Stratified (Model of a stratified tank for thermal energy storage).

Parameters

TypeNameDefaultDescription
replaceable package MediumPartialMediumMedium in the component
VolumeVTan Tank volume [m3]
LengthhTan Height of tank (without insulation) [m]
LengthdIns Thickness of insulation [m]
ThermalConductivitykIns0.04Specific heat conductivity of insulation [W/(m.K)]
IntegernSeg2Number of volume segments
Timetau1Time constant for mixing due to temperature inversion [s]
Reala1E-4Tuning factor. a=0 is equivalent to not using this model
Nominal condition
MassFlowRatem_flow_nominal Nominal mass flow rate [kg/s]
Initialization
MassFlowRatem_flow.start0Mass flow rate from port_a to port_b (m_flow > 0 is design flow direction) [kg/s]
Pressuredp.start0Pressure difference between port_a and port_b [Pa]
Assumptions
BooleanallowFlowReversalsystem.allowFlowReversal= true to allow flow reversal, false restricts to design direction (port_a -> port_b)
Dynamics
DynamicsenergyDynamicssystem.energyDynamicsFormulation of energy balance
DynamicsmassDynamicssystem.massDynamicsFormulation of mass balance
Advanced
MassFlowRatem_flow_small1E-4*m_flow_nominalSmall mass flow rate for regularization of zero flow [kg/s]
Diagnostics
Booleanshow_V_flowtrue= true, if volume flow rate at inflowing port is computed
Initialization
AbsolutePressurep_startsystem.p_startStart value of pressure [Pa]
Booleanuse_T_starttrue= true, use T_start, otherwise h_start
TemperatureT_startif use_T_start then system.T...Start value of temperature [K]
SpecificEnthalpyh_startif use_T_start then Medium.s...Start value of specific enthalpy [J/kg]
MassFractionX_start[Medium.nX]Medium.X_defaultStart value of mass fractions m_i/m [kg/kg]
ExtraPropertyC_start[Medium.nC]fill(0, Medium.nC)Start value of trace substances

Connectors

TypeNameDescription
FluidPort_aport_aFluid connector a (positive design flow direction is from port_a to port_b)
FluidPort_bport_bFluid connector b (positive design flow direction is from port_a to port_b)
HeatPort_aheaPorVol[nSeg]Heat port of fluid volumes
HeatPort_aheaPorSidHeat port tank side (outside insulation)
HeatPort_aheaPorTopHeat port tank top (outside insulation)
HeatPort_aheaPorBotHeat port tank bottom (outside insulation). Leave unconnected for adiabatic condition
output RealOutputQl_flowHeat loss of tank (positve if heat flows from to ambient)

Modelica definition

model StratifiedEnhanced 
  "Stratified tank model with enhanced discretization"
  extends Stratified(nPorts=3);
  BaseClasses.Stratifier str(
    redeclare package Medium = Medium,
    nSeg=nSeg,
    a=a) "Model to reduce numerical dissipation";
  parameter Real a=1E-4 
    "Tuning factor. a=0 is equivalent to not using this model";
  Modelica.Blocks.Sources.RealExpression mTan_flow(y=port_a.m_flow) 
    "Mass flow rate at port a";
equation 
  connect(vol[1:nSeg].ports[3], str.fluidPort[2:nSeg+1]);
  connect(hA.H_flow, str.H_flow[1]);
  connect(hVol_flow[1:nSeg-1].H_flow, str.H_flow[2:nSeg]);
  connect(hB.H_flow, str.H_flow[nSeg + 1]);
  connect(str.heatPort, vol.heatPort);
  connect(port_a, str.fluidPort[1]);
  connect(port_b, str.fluidPort[nSeg + 2]);
  connect(mTan_flow.y, str.m_flow);
end StratifiedEnhanced;