This package contains examples for the use of models that can be found in Buildings.Airflow.Multizone.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
Name | Description |
---|---|
ChimneyShaftNoVolume | Test model that demonstrates the chimney effect with a shaft that does not contain an air volume |
ChimneyShaftWithVolume | Test model that demonstrates the chimney effect with a shaft that contains an air volume |
CO2TransportStep | Model that transport CO2 through buoyancy driven flow |
OneDoor | |
OneOpenDoor | |
OpenDoors | |
OneEffectiveAirLeakageArea | |
Orifice | |
ReverseBuoyancy | |
ReverseBuoyancy3Zones | |
Validation0 | |
Validation1 | |
NaturalVentilation | |
ZonalFlow |
model ChimneyShaftNoVolume "Test model that demonstrates the chimney effect with a shaft that does not contain an air volume" extends Modelica.Icons.Example; import Buildings; package Medium = Buildings.Media.IdealGases.SimpleAir;Fluid.MixingVolumes.MixingVolume roo( nPorts=3, V=2.5*5*5, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, T_start=273.15 + 20, redeclare package Medium = Medium, use_HeatTransfer=true, p_start=101325) "Air volume of a room"; Buildings.Airflow.Multizone.Orifice oriChiTop( m=0.5, redeclare package Medium = Medium, A=0.01); Buildings.Fluid.Sources.MassFlowSource_T boundary( redeclare package Medium = Medium, nPorts=1, use_m_flow_in=true, T=293.15); Buildings.Fluid.Sources.Boundary_pT bou0( redeclare package Medium = Medium, T=273.15, nPorts=2); Buildings.Airflow.Multizone.Orifice oriBot( m=0.5, redeclare package Medium = Medium, A=0.01); Modelica.Blocks.Sources.CombiTimeTable mRoo_flow(tableOnFile=false, table=[0, 0.05; 600,0.05; 601,0; 1800,0; 1801,-0.05; 2400,-0.05; 2401,0; 3600,0]) "Mass flow into and out of room to fill the medium column with air of different temperature"; MediumColumn staOut( redeclare package Medium = Medium, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop, h=1.5) "Model for stack effect"; Buildings.Airflow.Multizone.Orifice oriChiBot( m=0.5, redeclare package Medium = Medium, A=0.01); Buildings.HeatTransfer.Sources.PrescribedHeatFlow preHea "Prescribed heat flow"; Buildings.Controls.Continuous.LimPID con( Td=10, yMax=1, yMin=-1, Ti=60, controllerType=Modelica.Blocks.Types.SimpleController.P, k=5) "Controller to maintain volume temperature"; Modelica.Blocks.Sources.Constant TSet(k=293.15) "Temperature set point"; Modelica.Thermal.HeatTransfer.Sensors.TemperatureSensor temSen "Temperature sensor"; Modelica.Blocks.Math.Gain gain(k=3000); inner Modelica.Fluid.System system; Buildings.Airflow.Multizone.MediumColumn sha(redeclare package Medium = Medium, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.actual) "Shaft of chimney"; MediumColumn staOut1( redeclare package Medium = Medium, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom, h=1.5) "Model for stack effect"; equationconnect(boundary.ports[1],roo. ports[1]); connect(TSet.y, con.u_s); connect(temSen.T, con.u_m); connect(gain.u, con.y); connect(gain.y, preHea.Q_flow); connect(sha.port_a, oriChiTop.port_a); connect(sha.port_b, oriChiBot.port_b); connect(staOut.port_b, oriBot.port_a); connect(preHea.port, roo.heatPort); connect(roo.heatPort, temSen.port); connect(bou0.ports[1], oriChiTop.port_b); connect(bou0.ports[2], staOut.port_a); connect(roo.ports[2], oriChiBot.port_a); connect(oriBot.port_b, staOut1.port_a); connect(staOut1.port_b, roo.ports[3]); connect(mRoo_flow.y[1], boundary.m_flow_in); end ChimneyShaftNoVolume;
model ChimneyShaftWithVolume "Test model that demonstrates the chimney effect with a shaft that contains an air volume" extends Modelica.Icons.Example; import Buildings; package Medium = Buildings.Media.IdealGases.SimpleAir;Fluid.MixingVolumes.MixingVolume roo( nPorts=3, V=2.5*5*5, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, T_start=273.15 + 20, redeclare package Medium = Medium, use_HeatTransfer=true, p_start=101325) "Air volume of a room"; Buildings.Airflow.Multizone.Orifice oriChiTop( m=0.5, redeclare package Medium = Medium, A=0.01); Buildings.Fluid.Sources.MassFlowSource_T boundary( redeclare package Medium = Medium, nPorts=1, use_m_flow_in=true, T=293.15); Buildings.Fluid.Sources.Boundary_pT bou0( redeclare package Medium = Medium, T=273.15, nPorts=2); Buildings.Airflow.Multizone.Orifice oriBot( m=0.5, redeclare package Medium = Medium, A=0.01); MediumColumn staOut( redeclare package Medium = Medium, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop, h=3/2) "Model for stack effect"; Buildings.Airflow.Multizone.Orifice oriChiBot( m=0.5, redeclare package Medium = Medium, A=0.01); Buildings.HeatTransfer.Sources.PrescribedHeatFlow preHea "Prescribed heat flow"; Buildings.Controls.Continuous.LimPID con( Td=10, yMax=1, yMin=-1, Ti=60, controllerType=Modelica.Blocks.Types.SimpleController.P, k=5) "Controller to maintain volume temperature"; Modelica.Blocks.Sources.Constant TSet(k=293.15) "Temperature set point"; Modelica.Thermal.HeatTransfer.Sensors.TemperatureSensor temSen "Temperature sensor"; Modelica.Blocks.Math.Gain gain(k=3000); inner Modelica.Fluid.System system; Buildings.Airflow.Multizone.MediumColumnDynamic sha( redeclare package Medium = Medium, V=3) "Shaft of chimney"; MediumColumn staOut1( redeclare package Medium = Medium, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom, h=3/2) "Model for stack effect"; Modelica.Blocks.Sources.CombiTimeTable mRoo_flow(tableOnFile=false, table=[0,0.05; 600,0.05; 601,0; 1800,0; 1801,-0.05; 2400,-0.05; 2401,0; 3600,0]) "Mass flow into and out of room to fill the medium column with air of different temperature"; equationconnect(boundary.ports[1],roo. ports[1]); connect(TSet.y, con.u_s); connect(temSen.T, con.u_m); connect(gain.u, con.y); connect(gain.y, preHea.Q_flow); connect(sha.port_a, oriChiTop.port_a); connect(sha.port_b, oriChiBot.port_b); connect(staOut.port_b, oriBot.port_a); connect(preHea.port, roo.heatPort); connect(roo.heatPort, temSen.port); connect(bou0.ports[1], oriChiTop.port_b); connect(bou0.ports[2], staOut.port_a); connect(roo.ports[2], oriChiBot.port_a); connect(oriBot.port_b, staOut1.port_a); connect(staOut1.port_b, roo.ports[3]); connect(mRoo_flow.y[1], boundary.m_flow_in); end ChimneyShaftWithVolume;
t=3600
, CO2 is added to volWes
.
As time progresses, the CO2 is transported to
the other rooms, and eventually its concentration decays.
Extends from Modelica.Icons.Example (Icon for runnable examples).
model CO2TransportStep "Model that transport CO2 through buoyancy driven flow" extends Modelica.Icons.Example; package Medium = Buildings.Media.IdealGases.SimpleAir(extraPropertiesNames={"CO2"});Buildings.Fluid.MixingVolumes.MixingVolume volEas( redeclare package Medium = Medium, T_start=273.15 + 20, V=2.5*5*5*1, nPorts=6, use_HeatTransfer=true, energyDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial, massDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial, traceDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, C_nominal={1E-6}); Buildings.Airflow.Multizone.Orifice oriOutBot( redeclare package Medium = Medium, A=0.01, m=0.5); Buildings.Airflow.Multizone.MediumColumn colOutTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriOutTop( redeclare package Medium = Medium, A=0.01, m=0.5); Buildings.Airflow.Multizone.MediumColumn colEasInTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Fluid.Sources.FixedBoundary volOut( redeclare package Medium = Medium, nPorts=2, p(displayUnit="Pa") = 101325, T=283.15); Buildings.Airflow.Multizone.MediumColumn colEasInBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Airflow.Multizone.MediumColumn colOutBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Airflow.Multizone.MediumColumn colWesBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriWesTop( redeclare package Medium = Medium, m=0.5, A=0.01); Buildings.Airflow.Multizone.MediumColumn colWesTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Airflow.Multizone.DoorDiscretizedOperable dooOpeClo( redeclare package Medium = Medium, LClo=20*1E-4, wOpe=1, hOpe=2.2, CDOpe=0.78, CDClo=0.78, nCom=10, hA=3/2, hB=3/2, dp_turbulent(displayUnit="Pa") = 0.01) "Discretized door"; Fluid.MixingVolumes.MixingVolume volWes( redeclare package Medium = Medium, T_start=273.15 + 25, nPorts=5, V=2.5*5*5, use_HeatTransfer=true, energyDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial, massDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial, traceDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, p_start=101325, C_nominal={1E-6}); Modelica.Blocks.Sources.Constant open(k=1); Buildings.Airflow.Multizone.MediumColumn col1EasBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriEasTop( redeclare package Medium = Medium, m=0.5, A=0.01); Buildings.Airflow.Multizone.MediumColumn colEasTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Fluid.MixingVolumes.MixingVolume volTop( redeclare package Medium = Medium, T_start=273.15 + 20, V=2.5*5*10*1, nPorts=3, use_HeatTransfer=true, energyDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial, massDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial, traceDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, C_nominal={1E-6}); inner Modelica.Fluid.System system; Buildings.HeatTransfer.Sources.FixedTemperature TTop(T=293.15) "Fixed temperature"; Buildings.HeatTransfer.Sources.FixedTemperature TWes(T=298.15) "Fixed temperature"; Buildings.HeatTransfer.Sources.FixedTemperature TEas(T=293.15) "Fixed temperature"; Fluid.Sensors.TraceSubstances CO2SenTop(redeclare package Medium = Medium) "CO2 sensor"; Fluid.Sensors.TraceSubstances CO2SenWes(redeclare package Medium = Medium) "CO2 sensor"; Fluid.Sensors.TraceSubstances CO2SenEas(redeclare package Medium = Medium) "CO2 sensor"; Modelica.Blocks.Sources.Pulse pulse( amplitude=8.18E-6, width=1/24/10, period=86400, startTime=3600); Fluid.Sources.PrescribedExtraPropertyFlowRate prescribedExtraPropertyFlowRate( redeclare package Medium = Medium, use_m_flow_in=true, nPorts=1); equationconnect(open.y, dooOpeClo.y); connect(volWes.ports[1], dooOpeClo.port_b2); connect(volWes.ports[2], dooOpeClo.port_a1); connect(volWes.ports[3], colWesBot.port_b); connect(colWesBot.port_a, oriWesTop.port_b); connect(oriWesTop.port_a, colWesTop.port_b); connect(colWesTop.port_a, volTop.ports[1]); connect(volTop.ports[2], colEasTop.port_a); connect(colEasTop.port_b, oriEasTop.port_b); connect(oriEasTop.port_a, col1EasBot.port_a); connect(dooOpeClo.port_b1, volEas.ports[1]); connect(volEas.ports[2], dooOpeClo.port_a2); connect(colEasInBot.port_a, volEas.ports[3]); connect(volEas.ports[4], colEasInTop.port_b); connect(volEas.ports[5], col1EasBot.port_b); connect(colEasInTop.port_a, oriOutTop.port_a); connect(oriOutTop.port_b, colOutTop.port_a); connect(colOutTop.port_b, volOut.ports[1]); connect(colOutBot.port_a, volOut.ports[2]); connect(colOutBot.port_b, oriOutBot.port_b); connect(oriOutBot.port_a, colEasInBot.port_b); connect(TTop.port, volTop.heatPort); connect(TEas.port, volEas.heatPort); connect(TWes.port, volWes.heatPort); connect(CO2SenTop.port, volTop.ports[3]); connect(CO2SenWes.port, volWes.ports[4]); connect(CO2SenEas.port, volEas.ports[6]); connect(prescribedExtraPropertyFlowRate.m_flow_in, pulse.y); connect(prescribedExtraPropertyFlowRate.ports[1], volWes.ports[5]); end CO2TransportStep;
model OneDoor extends Modelica.Icons.Example; package Medium = Buildings.Media.PerfectGases.MoistAirUnsaturated;Buildings.Fluid.MixingVolumes.MixingVolume volH( redeclare package Medium = Medium, T_start=273.15 + 50, V=2.5*10*10, nPorts=4, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial); Buildings.Airflow.Multizone.DoorDiscretizedOperable dooOpeClo(redeclare package Medium = Medium, LClo=20*1E-4) "Discretized door"; Modelica.Blocks.Sources.Constant open(k=1); Buildings.Fluid.MixingVolumes.MixingVolume volC( redeclare package Medium = Medium, T_start=273.15 + 0, V=2.5*10*10, nPorts=4, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial); Buildings.Airflow.Multizone.DoorDiscretizedOperable dooOpeClo1(redeclare package Medium = Medium, LClo=20*1E-4) "Discretized door"; Modelica.Blocks.Sources.Constant open1(k=1); inner Modelica.Fluid.System system; equationconnect(open.y, dooOpeClo.y); connect(open1.y, dooOpeClo1.y); connect(volC.ports[1], dooOpeClo.port_a1); connect(volC.ports[2], dooOpeClo.port_b2); connect(dooOpeClo.port_b1, volH.ports[1]); connect(dooOpeClo.port_a2, volH.ports[2]); connect(volC.ports[3], dooOpeClo1.port_a1); connect(volC.ports[4], dooOpeClo1.port_b2); connect(dooOpeClo1.port_b1, volH.ports[3]); connect(dooOpeClo1.port_a2, volH.ports[4]); end OneDoor;
model OneOpenDoor extends Modelica.Icons.Example; package Medium = Buildings.Media.IdealGases.SimpleAir;Buildings.Airflow.Multizone.DoorDiscretizedOpen dooOpe(redeclare package Medium = Medium) "Discretized door"; Buildings.Fluid.MixingVolumes.MixingVolume volA( redeclare package Medium = Medium, V=2.5*5*5, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, nPorts=4); Buildings.Fluid.MixingVolumes.MixingVolume volB( redeclare package Medium = Medium, V=2.5*5*5, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, use_HeatTransfer=true, nPorts=4); Buildings.HeatTransfer.Sources.PrescribedHeatFlow preHeaFlo; Modelica.Blocks.Sources.Sine heaSou(freqHz=1/3600); Modelica.Blocks.Math.Gain Gain1(k=100); Buildings.Airflow.Multizone.DoorDiscretizedOperable dooOpeClo(redeclare package Medium = Medium, LClo=20*1E-4) "Discretized door"; Modelica.Blocks.Sources.Ramp ramp( duration=120, height=1, offset=0, startTime=1000); inner Modelica.Fluid.System system; equationconnect(Gain1.y, preHeaFlo.Q_flow); connect(heaSou.y, Gain1.u); connect(ramp.y, dooOpeClo.y); connect(preHeaFlo.port, volB.heatPort); connect(volA.ports[1], dooOpeClo.port_b2); connect(volA.ports[2], dooOpeClo.port_a1); connect(volA.ports[3], dooOpe.port_b2); connect(volA.ports[4], dooOpe.port_a1); connect(volB.ports[1], dooOpe.port_b1); connect(volB.ports[2], dooOpe.port_a2); connect(volB.ports[3], dooOpeClo.port_b1); connect(volB.ports[4], dooOpeClo.port_a2); end OneOpenDoor;
model OpenDoors extends Modelica.Icons.Example; package Medium = Buildings.Media.IdealGases.SimpleAir;Buildings.Airflow.Multizone.DoorDiscretizedOperable dooAB( redeclare package Medium = Medium, LClo=20*1E-4, forceErrorControlOnFlow=true) "Discretized door"; Buildings.Fluid.MixingVolumes.MixingVolume volA( redeclare package Medium = Medium, V=2.5*5*5, nPorts=4, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial); Buildings.Fluid.MixingVolumes.MixingVolume volB( redeclare package Medium = Medium, V=2.5*5*5, use_HeatTransfer=true, nPorts=4, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial); Buildings.HeatTransfer.Sources.PrescribedHeatFlow PrescribedHeatFlow1; Modelica.Blocks.Sources.Sine Sine1(freqHz=1/3600); Modelica.Blocks.Math.Gain Gain1(k=100); Buildings.Fluid.MixingVolumes.MixingVolume volC( redeclare package Medium = Medium, V=2.5*5*5, nPorts=4, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial); Buildings.Airflow.Multizone.DoorDiscretizedOperable dooAC( redeclare package Medium = Medium, LClo=20*1E-4, forceErrorControlOnFlow=true) "Discretized door"; Modelica.Blocks.Sources.Constant open(k=0); Buildings.Airflow.Multizone.DoorDiscretizedOperable dooBC( redeclare package Medium = Medium, LClo=20*1E-4, forceErrorControlOnFlow=true) "Discretized door"; equationconnect(Gain1.y, PrescribedHeatFlow1.Q_flow); connect(Sine1.y, Gain1.u); connect(open.y, dooAB.y); connect(open.y, dooAC.y); connect(open.y, dooBC.y); connect(PrescribedHeatFlow1.port, volB.heatPort); connect(volC.ports[1], dooAC.port_b1); connect(volC.ports[2], dooAC.port_a2); connect(volC.ports[3], dooBC.port_b1); connect(volC.ports[4], dooBC.port_a2); connect(volB.ports[1], dooAB.port_b1); connect(volB.ports[2], dooAB.port_a2); connect(volB.ports[3], dooBC.port_a1); connect(volB.ports[4], dooBC.port_b2); connect(volA.ports[1], dooAC.port_b2); connect(volA.ports[2], dooAC.port_a1); connect(volA.ports[3], dooAB.port_b2); connect(volA.ports[4], dooAB.port_a1); end OpenDoors;
model OneEffectiveAirLeakageArea extends Modelica.Icons.Example; package Medium = Buildings.Media.IdealGases.SimpleAir;Buildings.Fluid.MixingVolumes.MixingVolume volA( redeclare package Medium = Medium, V=2.5*5*5, nPorts=2, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial); Buildings.Fluid.MixingVolumes.MixingVolume volB( redeclare package Medium = Medium, V=2.5*5*5, use_HeatTransfer=true, nPorts=1, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial); Buildings.HeatTransfer.Sources.PrescribedHeatFlow preHeaFlo; Modelica.Blocks.Sources.Sine Sine1(freqHz=1/3600); Modelica.Blocks.Math.Gain Gain1(k=100); Buildings.Airflow.Multizone.EffectiveAirLeakageArea cra(redeclare package Medium = Medium, L=20E-4); Buildings.Fluid.Sources.MassFlowSource_T sou( redeclare package Medium = Medium, nPorts=1, use_m_flow_in=true); Modelica.Blocks.Sources.Ramp ramSou( duration=3600, height=0.01, offset=0, startTime=1800); inner Modelica.Fluid.System system; equationconnect(sou.ports[1], volA.ports[1]); connect(ramSou.y, sou.m_flow_in); connect(volB.ports[1], cra.port_b); connect(volA.ports[2], cra.port_a); connect(preHeaFlo.port, volB.heatPort); connect(Gain1.y, preHeaFlo.Q_flow); connect(Gain1.u, Sine1.y); end OneEffectiveAirLeakageArea;
model Orifice extends Modelica.Icons.Example; package Medium = Buildings.Media.PerfectGases.MoistAirUnsaturated;Buildings.Airflow.Multizone.Orifice ori(redeclare package Medium = Medium, A= 0.2); Buildings.Fluid.Sources.Boundary_pT roo1( redeclare package Medium = Medium, use_p_in=true, use_T_in=true, nPorts=1); Buildings.Fluid.Sources.Boundary_pT roo2( redeclare package Medium = Medium, use_p_in=true, use_T_in=true, nPorts=1); Modelica.Blocks.Sources.Ramp Ramp1( duration=0.5, height=2, offset=-1, startTime=0.25); Modelica.Blocks.Sources.Constant Pre(k=100000); Modelica.Blocks.Math.Add Add1; Modelica.Blocks.Sources.Constant Tem1(k=273.15 + 5); Modelica.Blocks.Sources.Constant Tem2(k=273.15 + 20); Fluid.Sensors.DensityTwoPort den1(redeclare package Medium = Medium, m_flow_nominal=0.1) "Density sensor"; Fluid.Sensors.DensityTwoPort den2(redeclare package Medium = Medium, m_flow_nominal=0.1) "Density sensor"; inner Modelica.Fluid.System system; equationconnect(Pre.y, Add1.u1); connect(Ramp1.y, Add1.u2); connect(Tem1.y, roo1.T_in); connect(Pre.y, roo1.p_in); connect(Add1.y, roo2.p_in); connect(Tem2.y, roo2.T_in); connect(roo1.ports[1], den1.port_a); connect(den1.port_b, ori.port_a); connect(ori.port_b, den2.port_a); connect(den2.port_b, roo2.ports[1]); end Orifice;
model ReverseBuoyancy extends Modelica.Icons.Example; package Medium = Buildings.Media.IdealGases.SimpleAir;Buildings.Fluid.MixingVolumes.MixingVolume volEas( redeclare package Medium = Medium, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, V=2.5*5*5, T_start=273.15 + 25, nPorts=5); Buildings.Airflow.Multizone.Orifice oriOutBot( redeclare package Medium = Medium, m=0.5, A=0.01, dp_turbulent=0.1); Buildings.Airflow.Multizone.MediumColumn colOutTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriOutTop( redeclare package Medium = Medium, m=0.5, A=0.01, dp_turbulent=0.1); Buildings.Airflow.Multizone.MediumColumn colEasInTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Fluid.MixingVolumes.MixingVolume volOut( redeclare package Medium = Medium, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, V=1E12, T_start=273.15 + 15, nPorts=3); Buildings.Airflow.Multizone.Orifice dummy( redeclare package Medium = Medium, m=1, A=100, dp_turbulent=0.1) "to fix absolute pressure"; Buildings.Airflow.Multizone.MediumColumn colEasInBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Airflow.Multizone.MediumColumn colOutBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); MediumColumn colWesBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriWesTop( redeclare package Medium = Medium, m=0.5, A=0.01, dp_turbulent=0.1); Buildings.Airflow.Multizone.MediumColumn colWesTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Airflow.Multizone.DoorDiscretizedOperable dooOpeClo( redeclare package Medium = Medium, LClo=20*1E-4, wOpe=1, hOpe=2.2, hA=3/2, hB=3/2, CDOpe=0.78, CDClo=0.78, nCom=10, vZer=0.01, dp_turbulent=0.1) "Discretized door"; Buildings.Fluid.Delays.DelayFirstOrder volWes( redeclare package Medium = Medium, m_flow_nominal=1.2, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, tau=2.5*5*5, p_start=101325, T_start=273.15 + 22, nPorts=3); Modelica.Blocks.Sources.Constant ope(k=1); Buildings.Airflow.Multizone.MediumColumn col1EasBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriEasTop( redeclare package Medium = Medium, m=0.5, A=0.01, dp_turbulent=0.1); Buildings.Airflow.Multizone.MediumColumn colEasTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Fluid.MixingVolumes.MixingVolume volTopEas( redeclare package Medium = Medium, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, V=2.5*5*10, T_start=273.15 + 21, nPorts=3); Buildings.Fluid.MixingVolumes.MixingVolume volTopWes( redeclare package Medium = Medium, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, T_start=273.15 + 20, V=2.5*5*10, nPorts=3); Buildings.Airflow.Multizone.DoorDiscretizedOperable dooOpeCloTop( redeclare package Medium = Medium, LClo=20*1E-4, wOpe=1, hOpe=2.2, hA=3/2, hB=3/2, CDOpe=0.78, CDClo=0.78, nCom=10, vZer=0.01, dp_turbulent=0.1) "Discretized door"; Fluid.Sources.FixedBoundary amb( redeclare package Medium = Medium, p=100000, T=283.15, nPorts=1) "Ambient conditions"; inner Modelica.Fluid.System system; equationconnect(ope.y, dooOpeClo.y); connect(ope.y, dooOpeCloTop.y); connect(oriEasTop.port_b, colEasTop.port_b); connect(oriWesTop.port_b, colWesBot.port_a); connect(oriWesTop.port_a, colWesTop.port_b); connect(oriOutBot.port_b, colOutBot.port_b); connect(colEasInBot.port_b, oriOutBot.port_a); connect(colEasInTop.port_a, oriOutTop.port_a); connect(oriOutTop.port_b, colOutTop.port_a); connect(volWes.ports[1], dooOpeClo.port_b2); connect(volWes.ports[2], dooOpeClo.port_a1); connect(colWesBot.port_b, volWes.ports[3]); connect(volTopWes.ports[1], colWesTop.port_a); connect(volTopWes.ports[2], dooOpeCloTop.port_b2); connect(volTopWes.ports[3], dooOpeCloTop.port_a1); connect(volTopEas.ports[1], dooOpeCloTop.port_b1); connect(dooOpeCloTop.port_a2, volTopEas.ports[2]); connect(colEasTop.port_a, volTopEas.ports[3]); connect(oriEasTop.port_a, col1EasBot.port_a); connect(dooOpeClo.port_b1, volEas.ports[1]); connect(dooOpeClo.port_a2, volEas.ports[2]); connect(colEasInBot.port_a, volEas.ports[3]); connect(colEasInTop.port_b, volEas.ports[4]); connect(col1EasBot.port_b, volEas.ports[5]); connect(colOutTop.port_b, volOut.ports[1]); connect(colOutBot.port_a, volOut.ports[2]); connect(dummy.port_a, volOut.ports[3]); connect(amb.ports[1], dummy.port_b); end ReverseBuoyancy;
model ReverseBuoyancy3Zones extends Modelica.Icons.Example; package Medium = Buildings.Media.IdealGases.SimpleAir;Buildings.Fluid.MixingVolumes.MixingVolume volEas( redeclare package Medium = Medium, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, V=2.5*5*5, T_start=273.15 + 25, nPorts=5); Buildings.Airflow.Multizone.Orifice oriOutBot( redeclare package Medium = Medium, m=0.5, A=0.01, dp_turbulent=0.1); Buildings.Airflow.Multizone.MediumColumn colOutTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriOutTop( redeclare package Medium = Medium, m=0.5, A=0.01, dp_turbulent=0.1); Buildings.Airflow.Multizone.MediumColumn colEasInTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Fluid.MixingVolumes.MixingVolume volOut( redeclare package Medium = Medium, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, V=1E12, T_start=273.15 + 15, nPorts=2); Buildings.Airflow.Multizone.MediumColumn colEasInBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Airflow.Multizone.MediumColumn colOutBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Airflow.Multizone.MediumColumn colWesBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriWesTop( redeclare package Medium = Medium, m=0.5, A=0.01, dp_turbulent=0.1); Buildings.Airflow.Multizone.MediumColumn colWesTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Airflow.Multizone.DoorDiscretizedOperable dooOpeClo( redeclare package Medium = Medium, LClo=20*1E-4, wOpe=1, hOpe=2.2, hA=3/2, hB=3/2, CDOpe=0.78, CDClo=0.78, nCom=10, vZer=0.01, dp_turbulent=0.1) "Discretized door"; Modelica.Blocks.Sources.Constant ope(k=1); Buildings.Airflow.Multizone.MediumColumn col1EasBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriEasTop( redeclare package Medium = Medium, m=0.5, A=0.01, dp_turbulent=0.1); Buildings.Airflow.Multizone.MediumColumn colEasTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Fluid.MixingVolumes.MixingVolume volTopEas( redeclare package Medium = Medium, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, V=2.5*5*10, T_start=273.15 + 21, nPorts=3); Buildings.Fluid.MixingVolumes.MixingVolume volTopWes( redeclare package Medium = Medium, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, T_start=273.15 + 20, V=2.5*5*10, nPorts=3); Buildings.Airflow.Multizone.DoorDiscretizedOperable dooOpeCloTop( redeclare package Medium = Medium, LClo=20*1E-4, wOpe=1, hOpe=2.2, hA=3/2, hB=3/2, CDOpe=0.78, CDClo=0.78, nCom=10, vZer=0.01, dp_turbulent=0.1) "Discretized door"; Buildings.Fluid.MixingVolumes.MixingVolume volWes( redeclare package Medium = Medium, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, V=2.5*5*5, T_start=273.15 + 22, nPorts=3); inner Modelica.Fluid.System system; equationconnect(dooOpeClo.port_b2, volWes.ports[1]); connect(dooOpeClo.port_a1, volWes.ports[2]); connect(dooOpeCloTop.port_b1, volTopEas.ports[1]); connect(dooOpeCloTop.port_a2, volTopEas.ports[2]); connect(dooOpeClo.port_b1, volEas.ports[1]); connect(dooOpeClo.port_a2, volEas.ports[2]); connect(colWesTop.port_a, volTopWes.ports[1]); connect(volTopWes.ports[2], dooOpeCloTop.port_b2); connect(dooOpeCloTop.port_a1, volTopWes.ports[3]); connect(colWesTop.port_b, oriWesTop.port_a); connect(oriWesTop.port_b, colWesBot.port_a); connect(colWesBot.port_b, volWes.ports[3]); connect(volTopEas.ports[3], colEasTop.port_a); connect(colEasTop.port_b, oriEasTop.port_b); connect(oriEasTop.port_a, col1EasBot.port_a); connect(colEasInBot.port_a, volEas.ports[3]); connect(colEasInTop.port_b, volEas.ports[4]); connect(col1EasBot.port_b, volEas.ports[5]); connect(colOutTop.port_b, volOut.ports[1]); connect(volOut.ports[2], colOutBot.port_a); connect(colOutBot.port_b, oriOutBot.port_b); connect(oriOutBot.port_a, colEasInBot.port_b); connect(colEasInTop.port_a, oriOutTop.port_a); connect(oriOutTop.port_b, colOutTop.port_a); connect(dooOpeCloTop.y, ope.y); connect(ope.y, dooOpeClo.y); end ReverseBuoyancy3Zones;
model Validation0 extends Modelica.Icons.Example; package Medium = Buildings.Media.IdealGases.SimpleAir;Buildings.Fluid.MixingVolumes.MixingVolume volEas( redeclare package Medium = Medium, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, T_start=273.15 + 20, V=2.5*5*5, nPorts=2); Buildings.Airflow.Multizone.Orifice oriOutBot( redeclare package Medium = Medium, A=0.01, m=0.5); Buildings.Airflow.Multizone.MediumColumn colOutTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriOutTop( redeclare package Medium = Medium, A=0.01, m=0.5); Buildings.Airflow.Multizone.MediumColumn colEasInTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Fluid.MixingVolumes.MixingVolume volOut( redeclare package Medium = Medium, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, T_start=273.15 + 10, V=1E12, p_start=Medium.p_default, nPorts=2); Buildings.Airflow.Multizone.MediumColumn colEasInBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Airflow.Multizone.MediumColumn colOutBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); inner Modelica.Fluid.System system; equationconnect(colEasInTop.port_a, oriOutTop.port_a); connect(colEasInTop.port_b, volEas.ports[1]); connect(colEasInBot.port_a, volEas.ports[2]); connect(colEasInBot.port_b, oriOutBot.port_a); connect(oriOutBot.port_b, colOutBot.port_b); connect(colOutBot.port_a, volOut.ports[1]); connect(colOutTop.port_b, volOut.ports[2]); connect(colOutTop.port_a, oriOutTop.port_b); end Validation0;
model Validation1 extends Modelica.Icons.Example; package Medium = Buildings.Media.IdealGases.SimpleAir;Buildings.Fluid.MixingVolumes.MixingVolume volEas( redeclare package Medium = Medium, T_start=273.15 + 20, V=2.5*5*5*1, nPorts=5, use_HeatTransfer=true, energyDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial, massDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial); Buildings.Airflow.Multizone.Orifice oriOutBot( redeclare package Medium = Medium, A=0.01, m=0.5); Buildings.Airflow.Multizone.MediumColumn colOutTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriOutTop( redeclare package Medium = Medium, A=0.01, m=0.5); Buildings.Airflow.Multizone.MediumColumn colEasInTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Fluid.Sources.FixedBoundary volOut( redeclare package Medium = Medium, nPorts=2, p(displayUnit="Pa") = 101325, T=283.15); Buildings.Airflow.Multizone.MediumColumn colEasInBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Airflow.Multizone.MediumColumn colOutBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Airflow.Multizone.MediumColumn colWesBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriWesTop( redeclare package Medium = Medium, m=0.5, A=0.01); Buildings.Airflow.Multizone.MediumColumn colWesTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Airflow.Multizone.DoorDiscretizedOperable dooOpeClo( redeclare package Medium = Medium, LClo=20*1E-4, wOpe=1, hOpe=2.2, CDOpe=0.78, CDClo=0.78, nCom=10, hA=3/2, hB=3/2, dp_turbulent(displayUnit="Pa") = 0.01) "Discretized door"; Fluid.MixingVolumes.MixingVolume volWes( redeclare package Medium = Medium, T_start=273.15 + 25, nPorts=3, p_start=101325, V=2.5*5*5, use_HeatTransfer=true, energyDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial, massDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial); Modelica.Blocks.Sources.Constant open(k=1); Buildings.Airflow.Multizone.MediumColumn col1EasBot( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriEasTop( redeclare package Medium = Medium, m=0.5, A=0.01); Buildings.Airflow.Multizone.MediumColumn colEasTop( redeclare package Medium = Medium, h=1.5, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromTop); Buildings.Fluid.MixingVolumes.MixingVolume volTop( redeclare package Medium = Medium, T_start=273.15 + 20, V=2.5*5*10*1, nPorts=2, use_HeatTransfer=true, energyDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial, massDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial); inner Modelica.Fluid.System system; Buildings.HeatTransfer.Sources.FixedTemperature TTop(T=293.15) "Fixed temperature"; Buildings.HeatTransfer.Sources.FixedTemperature TWes(T=298.15) "Fixed temperature"; Buildings.HeatTransfer.Sources.FixedTemperature TEas(T=293.15) "Fixed temperature"; equationconnect(open.y, dooOpeClo.y); connect(volWes.ports[1], dooOpeClo.port_b2); connect(volWes.ports[2], dooOpeClo.port_a1); connect(volWes.ports[3], colWesBot.port_b); connect(colWesBot.port_a, oriWesTop.port_b); connect(oriWesTop.port_a, colWesTop.port_b); connect(colWesTop.port_a, volTop.ports[1]); connect(volTop.ports[2], colEasTop.port_a); connect(colEasTop.port_b, oriEasTop.port_b); connect(oriEasTop.port_a, col1EasBot.port_a); connect(dooOpeClo.port_b1, volEas.ports[1]); connect(volEas.ports[2], dooOpeClo.port_a2); connect(colEasInBot.port_a, volEas.ports[3]); connect(volEas.ports[4], colEasInTop.port_b); connect(volEas.ports[5], col1EasBot.port_b); connect(colEasInTop.port_a, oriOutTop.port_a); connect(oriOutTop.port_b, colOutTop.port_a); connect(colOutTop.port_b, volOut.ports[1]); connect(colOutBot.port_a, volOut.ports[2]); connect(colOutBot.port_b, oriOutBot.port_b); connect(oriOutBot.port_a, colEasInBot.port_b); connect(TTop.port, volTop.heatPort); connect(TEas.port, volEas.heatPort); connect(TWes.port, volWes.heatPort); end Validation1;
model NaturalVentilation extends Modelica.Icons.Example; package Medium = Buildings.Media.IdealGases.SimpleAir;Buildings.Fluid.MixingVolumes.MixingVolume volA( redeclare package Medium = Medium, V=2.5*10*5, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, T_start=273.15 + 18, use_HeatTransfer=true, nPorts=2); Buildings.Airflow.Multizone.Orifice oriOutBot( redeclare package Medium = Medium, A=0.1, m=0.5, dp_turbulent=0.1); Buildings.Airflow.Multizone.MediumColumn colOut( redeclare package Medium = Medium, h=3, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Airflow.Multizone.Orifice oriOutTop( redeclare package Medium = Medium, A=0.1, m=0.5, dp_turbulent=0.1); Buildings.Airflow.Multizone.MediumColumn colRooTop( redeclare package Medium = Medium, h=3, densitySelection=Buildings.Airflow.Multizone.Types.densitySelection.fromBottom); Buildings.Fluid.MixingVolumes.MixingVolume volOut( redeclare package Medium = Medium, energyDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, massDynamics=Modelica.Fluid.Types.Dynamics.FixedInitial, V=1E10, T_start=273.15 + 20, nPorts=2); Buildings.HeatTransfer.Sources.PrescribedHeatFlow preHeaFlo; Modelica.Blocks.Sources.Step q_flow( height=-100, offset=100, startTime=3600); inner Modelica.Fluid.System system; equationconnect(q_flow.y, preHeaFlo.Q_flow); connect(oriOutBot.port_b, volOut.ports[1]); connect(preHeaFlo.port, volA.heatPort); connect(volA.ports[1], oriOutBot.port_a); connect(volA.ports[2], colRooTop.port_b); connect(colRooTop.port_a, oriOutTop.port_a); connect(volOut.ports[2], colOut.port_b); connect(colOut.port_a, oriOutTop.port_b); end NaturalVentilation;
Type | Name | Default | Description |
---|---|---|---|
Volume | volA | 100 | Volume of room A [m3] |
Volume | volB | 1 | Volume of room B [m3] |
model ZonalFlow extends Modelica.Icons.Example; package Medium = Buildings.Media.PerfectGases.MoistAirUnsaturated; parameter Modelica.SIunits.Volume volA=100 "Volume of room A"; parameter Modelica.SIunits.Volume volB=1 "Volume of room B";Buildings.Fluid.MixingVolumes.MixingVolume rooA( V=volA, redeclare package Medium = Medium, X_start={0.015,0.985}, T_start=303.15, nPorts=2) "Room A"; Buildings.Fluid.MixingVolumes.MixingVolume rooB( V=volB, redeclare package Medium = Medium, X_start={0.01,0.99}, T_start=293.15, nPorts=2) "Room B"; Modelica.Blocks.Sources.Constant ACS_con(k=5/3600); ZonalFlow_ACS zonFlo(redeclare package Medium = Medium, V=min(volA, volB)); inner Modelica.Fluid.System system; equationconnect(rooA.ports[1], zonFlo.port_a1); connect(zonFlo.port_b1, rooB.ports[1]); connect(zonFlo.port_b2, rooA.ports[2]); connect(zonFlo.port_a2, rooB.ports[2]); connect(zonFlo.ACS, ACS_con.y); end ZonalFlow;