Buildings.Fluid.HeatExchangers.ActiveBeams.Data
Package with performance data
Information
Package with performance data for active beams.
Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).
Package Content
| Name | Description | 
|---|---|
|  Trox | Performance data for Trox | 
|  Generic | Generic data record for active beam | 
|  BaseClasses | Base classes for performance data | 
 Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Generic
Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Generic
Generic data record for active beam
Information
Performance data for a generic active beam.
Extends from Modelica.Icons.Record (Icon for records).
Contents
| Type | Name | Default | Description | 
|---|---|---|---|
| AirFlow | primaryAir | primaryAir(r_V={0,0.2,1}, f=... | Performance data for primary air | 
| WaterFlow | water | water(r_V={0,0.5,1}, f={0,0.... | Performance data for water | 
| TemperatureDifference | dT | dT(r_dT={0,0.5,1}, f={0,0.5,... | Performance data for normalized temperature difference room minus water inlet | 
| Nominal condition | |||
| MassFlowRate | mAir_flow_nominal | Nominal air mass flow rate per beam [kg/s] | |
| MassFlowRate | mWat_flow_nominal | Nominal water mass flow rate per beam [kg/s] | |
| PressureDifference | dpWat_nominal | Water-side nominal pressure drop per beam [Pa] | |
| PressureDifference | dpAir_nominal | Air-side nominal pressure drop [Pa] | |
| TemperatureDifference | dT_nominal | Nominal temperature difference water inlet minus room air [K] | |
| HeatFlowRate | Q_flow_nominal | Nominal capacity per beam [W] | |
Modelica definition
record Generic "Generic data record for active beam"
   extends Modelica.Icons.Record;
  parameter BaseClasses.AirFlow primaryAir(
    r_V={0,0.2,1},
    f={0,0.5,1}) "Performance data for primary air";
  parameter Buildings.Fluid.HeatExchangers.ActiveBeams.Data.BaseClasses.WaterFlow
                                                                          water(
      r_V={0,0.5,1},
      f={0,0.7,1}) "Performance data for water";
  parameter BaseClasses.TemperatureDifference dT(
    r_dT={0,0.5,1},
    f={0,0.5,1})
    "Performance data for normalized temperature difference room minus water inlet";
  parameter Modelica.Units.SI.MassFlowRate mAir_flow_nominal
    "Nominal air mass flow rate per beam";
  parameter Modelica.Units.SI.MassFlowRate mWat_flow_nominal
    "Nominal water mass flow rate per beam";
  parameter Modelica.Units.SI.PressureDifference dpWat_nominal(displayUnit="Pa")
    "Water-side nominal pressure drop per beam";
  parameter Modelica.Units.SI.PressureDifference dpAir_nominal(displayUnit="Pa")
    "Air-side nominal pressure drop";
  parameter Modelica.Units.SI.TemperatureDifference dT_nominal
    "Nominal temperature difference water inlet minus room air";
  parameter Modelica.Units.SI.HeatFlowRate Q_flow_nominal
    "Nominal capacity per beam";
end Generic;