Buildings.Fluid.DataCenters.Racks.Liquid.Examples
Collection of models that illustrate model use and test models
Information
This package contains examples for the use of models that can be found in Buildings.Fluid.DataCenters.Racks.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
Package Content
| Name | Description |
|---|---|
| Example model for cold plate |
Buildings.Fluid.DataCenters.Racks.Liquid.Examples.ColdPlateR_P
Example model for cold plate
Information
Example model of a cold plate with different GPU utilization.
The GPU utilization is modeled as a pulse that is parameterized based on the data of Patel et al. (2024), Figure 6(b) which is for the Llama2-50B LLM, neglecting the very high frequency and approximating the change in utilization with a periodic pulse input. The cold plate operates at a constant flow rate at the start of the simulation. The flow rate then ramps down to half the design value to show the change in case temperature.
References
Pratyush Patel, Esha Choukse, Chaojie Zhang, Íñigo Goiri, Brijesh Warrier, Nithish Mahalingam, and Ricardo Bianchini.
Characterizing Power Management Opportunities for LLMs in the Cloud.
In Proceedings of the 29th ACM International Conference on
Architectural Support for Programming Languages and Operating Systems, Volume 3 (ASPLOS '24).
Association for Computing Machinery, New York, NY, USA, 207–222. 2024.
doi:10.1145/3620666.3651329.
Extends from Modelica.Icons.Example (Icon for runnable examples).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| HeatFlowRate | P_nominal | 2*66000 | Design heat flow rate at u=1, also called Thermal Design Power (TDP) [W] |
| TemperatureDifference | dT_nominal | 7 | Design temperature difference of coolant fluid [K] |
| SpecificHeatCapacity | cp_default | Medium.specificHeatCapacityC... | Heat capacity, to compute additional dry mass [J/(kg.K)] |
| OCP_1kW_OAM_PG25 | dat | dat(PIT_nominal=P_nominal, m... | Performance data |