Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Generic.Validation
Collection of validation models
Information
This package contains validation models for the classes in Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.HeadPressure.
Note that most validation models contain simple input data which may not be realistic, but for which the correct output can be obtained through an analytic solution. The examples plot various outputs, which have been verified against these solutions. These model outputs are stored as reference data and used for continuous validation whenever models in the library change.
Package Content
| Name | Description |
|---|---|
| Validation the calculation of the chiller lifts | |
| Validation identifying stage index | |
| Validation model for the Timer block |
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Generic.Validation.ChillerLifts
Validation the calculation of the chiller lifts
Information
This example validates Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Generic.ChillerLifts. It shows how to calculate current chiller lifts.
Modelica definition
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Generic.Validation.IdentifyStage
Validation identifying stage index
Information
This example validates Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Generic.IdentifyStage. It shows how to identify the current chiller stage.
-
For instance
ideSta, the staging matrixstaMatis specified as{{1,0}, {0,1}, {1,1}}, which means that in stage 1 chiller 1 is enabled, in stage 2 chiller 2 is enabled and in stage 3 both chillers are enabled.- Before 2.5 seconds, since chiller 1 and 2 are enabled, the current stage is 3.
- From 2.5 seconds to 3.5 seconds, chiller 2 is enabled and chiller 1 is disabled, the current stage is 2.
- After 3.5 seconds, both chillers are disabled, thus, the current stage is 0.
-
For instance
ideSta1, the staging matrixstaMatis specified as{{1,0,0},{1,1,0},{1,1,1}}, which means that in stage 1 chiller 1 is enabled, in stage 2 chiller 1 and 2 is enabled, and in stage 3 all 3 chillers are enabled.- Before 2.5 seconds, no chiller is enabled. The current chiller stage is 0.
- From 2.5 seconds to 3.5 seconds, only chiller 1 is enabled. Thus, the current chiller stage is 1.
- From 3.5 seconds to 4.5 seconds, chiller 1 and 2 are enabled. Thus, the current chiller stage is 2.
- After 4.5 seconds, all three chillers are enabled. Thus, the current chiller stage is 3.
Modelica definition
Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Generic.Validation.TimerWithReset
Validation model for the Timer block
Information
Validation model for the block Buildings.Controls.OBC.ASHRAE.G36.Plants.Chillers.Generic.TimerWithReset.