Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx
600 series of ANSI/ASHRAE BESTEST
Information
This package contains the validation cases of the 600 series of the BESTEST validation (ANSI/ASHRAE 2007).
References
ANSI/ASHRAE. 2007. ANSI/ASHRAE Standard 140-2007, Standard Method of Test for the Evaluation of Building Energy Analysis Computer Programs.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
Package Content
Name | Description |
---|---|
Case600 | Case 600FF, but with dual-setpoint for heating and cooling |
Case600FF | Basic test with light-weight construction and free floating temperature |
Case610 | Case 600 with south shading |
Case620 | Case 600, but with windows on East and West side walls |
Case630 | Case 620, but with added overhang and sidefins |
Case640 | Case 600, but with heating schedule |
Case650 | Case 600, but cooling based on schedule, night venting, and no heating |
Case650FF | Case 600, no heating, no cooling, and ventilation as in case 650 |
Case660 | Case 600, but with low-emissivity windows with Argon gas |
Case670 | Case 600, but has single pane window with clear glass |
Case680 | Case 600, but with increased exterior wall and roof insulation |
Case680FF | Case 600FF, but with increased exterior wall and roof insulation |
Case685 | Case 600, but with single setpoint for heating and cooling |
Case695 | Case 600, but with increased exterior wall and roof insulation and single cooling and heating setpoint |
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600
Case 600FF, but with dual-setpoint for heating and cooling
Information
This model is used for the basic test case 600 of the BESTEST validation suite. Case 600 is a light-weight building with room temperature control set to 20°C for heating and 27°C for cooling. The room has no shade and a window that faces south.
Extends from Case600FF (Basic test with light-weight construction and free floating temperature).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | Exterior wall | |
Generic | matFlo | Floor | |
Generic | roof | Roof | |
Win600 | window600 | redeclare parameter Building... | Window |
DaySchedule | TSetHea | TSetHea(table=[0.0, 273.15 +... | Heating setpoint |
DaySchedule | TSetCoo | TSetCoo(table=[0.0, 273.15 +... | Cooling setpoint |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600FF
Basic test with light-weight construction and free floating temperature
Information
This model is used for the test case 600FF of the BESTEST validation suite. Case 600FF is a light-weight building. The room temperature is free floating.
Extends from Modelica.Icons.Example (Icon for runnable examples).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | matExtWal(nLay=3, absIR_a=0.... | Exterior wall |
Generic | matFlo | matFlo(final nLay=2, absIR_a... | Floor |
Generic | roof | roof(nLay=3, absIR_a=0.9, ab... | Roof |
Win600 | window600 | window600(UFra=3, haveExteri... | Window |
StandardResultsFreeFloating | staRes | staRes(minT(Min=-13.8 + 273.... | Reference results from ASHRAE/ANSI Standard 140 |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case610
Case 600 with south shading
Information
This model is the case 610 of the BESTEST validation suite. Case 610 differs from case 600 in that the window has an overhang.
Implementation
Two overhangs have been added, one for each window, because each window only sees its own overhang.
Extends from Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600 (Case 600FF, but with dual-setpoint for heating and cooling).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | Exterior wall | |
Generic | matFlo | Floor | |
Generic | roof | Roof | |
Win600 | window600 | redeclare parameter Building... | Window |
DaySchedule | TSetHea | redeclare BaseClasses.DaySch... | Heating setpoint |
DaySchedule | TSetCoo | redeclare BaseClasses.DaySch... | Cooling setpoint |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case620
Case 600, but with windows on East and West side walls
Information
This model is the case 620 of the BESTEST validation suite. Case 620 differs from case 600 in that the west and east facing walls have a window, but there is no window in the south facing wall.
Extends from Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600 (Case 600FF, but with dual-setpoint for heating and cooling).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | Exterior wall | |
Generic | matFlo | Floor | |
Generic | roof | Roof | |
Win600 | window600 | redeclare parameter Building... | Window |
DaySchedule | TSetHea | redeclare BaseClasses.DaySch... | Heating setpoint |
DaySchedule | TSetCoo | redeclare BaseClasses.DaySch... | Cooling setpoint |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case630
Case 620, but with added overhang and sidefins
Information
This model is case 630 of the BESTEST validation suite. Case 630 differs from case 620 in that the windows on the west and east walls have an overhang and side fins.
Extends from Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case620 (Case 600, but with windows on East and West side walls).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | Exterior wall | |
Generic | matFlo | Floor | |
Generic | roof | Roof | |
Win600 | window600 | redeclare parameter Building... | Window |
DaySchedule | TSetHea | redeclare BaseClasses.DaySch... | Heating setpoint |
DaySchedule | TSetCoo | redeclare BaseClasses.DaySch... | Cooling setpoint |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case640
Case 600, but with heating schedule
Information
This model is used for the basic test case 640 of the BESTEST validation suite. Case640 is the same as Case600, but with the following modifications:
- From 2300 hours to 0700 hours, heat = on if zone temperature is below 10°C
- From 0700 hours to 0800 hours, the thermostat set point shall vary linearly with time from 10 °C to 20 °C. If the zone temperature is less than the thermostat set point for a subhourly time step, heat shall be added to the zone such that the zone temperature at the end of each subhourly time step shall correspond to the thermostat set point that occurs at the end of each subhourly time step.
- From 0800 hours to 2300 hours, heat = on if zone temperature is below 20°C
- All hours, cool = on if zone temperature above 27°C
- Otherwise, mechanical equipment is off.
Extends from Case600 (Case 600FF, but with dual-setpoint for heating and cooling).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | Exterior wall | |
Generic | matFlo | Floor | |
Generic | roof | Roof | |
Win600 | window600 | redeclare parameter Building... | Window |
DaySchedule | TSetCoo | redeclare BaseClasses.DaySch... | Cooling setpoint |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case650
Case 600, but cooling based on schedule, night venting, and no heating
Information
This model is used for the test case 650 of the BESTEST validation suite. Case650 is the same as Case600, but with the following modifications:
- From 1800 hours to 0700 hours, vent fan = on
- From 0700 hours to 1800 hours, vent fan = off
- Heating is always off
- From 0700 hours to 1800 hours, cooling is on if zone temperature > 27°C, otherwise cool = off.
- From 1800 hours to 0700 hours, cooling is always off.
- Ventilation fan capacity is 1700 standard m3/h (in addition to specified infiltration rate). After adjustment for the altitude, the capacity is 1409 m3/h.
- No waste heat from fan.
Extends from Case600 (Case 600FF, but with dual-setpoint for heating and cooling).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | Exterior wall | |
Generic | matFlo | Floor | |
Generic | roof | Roof | |
Win600 | window600 | redeclare parameter Building... | Window |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case650FF
Case 600, no heating, no cooling, and ventilation as in case 650
Information
This model is used for the test case 650FF of the BESTEST validation suite. Case 650FF is identical to case 650, except that there is no heating and no cooling.
Extends from Case600FF (Basic test with light-weight construction and free floating temperature).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | Exterior wall | |
Generic | matFlo | Floor | |
Generic | roof | Roof | |
Win600 | window600 | redeclare parameter Building... | Window |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case660
Case 600, but with low-emissivity windows with Argon gas
Information
This model is the case 660 of the BESTEST validation suite. Case 660 differs from case 600 in that it has low-emissivity windwos with Argon gas.
Extends from Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600 (Case 600FF, but with dual-setpoint for heating and cooling).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | Exterior wall | |
Generic | matFlo | Floor | |
Generic | roof | Roof | |
DaySchedule | TSetHea | redeclare BaseClasses.DaySch... | Heating setpoint |
DaySchedule | TSetCoo | redeclare BaseClasses.DaySch... | Cooling setpoint |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case670
Case 600, but has single pane window with clear glass
Information
This model is the case 670 of the BESTEST validation suite. Case 670 differs from case 600 in that it has single pane window with clear glass.
Extends from Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600 (Case 600FF, but with dual-setpoint for heating and cooling).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | Exterior wall | |
Generic | matFlo | Floor | |
Generic | roof | Roof | |
DaySchedule | TSetHea | redeclare BaseClasses.DaySch... | Heating setpoint |
DaySchedule | TSetCoo | redeclare BaseClasses.DaySch... | Cooling setpoint |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case680
Case 600, but with increased exterior wall and roof insulation
Information
This model is the case 680 of the BESTEST validation suite. Case 680 differs from case 600 in that it has increased exterior wall and roof insulation.
Extends from Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600 (Case 600FF, but with dual-setpoint for heating and cooling).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | extWalCase680 | Exterior wall |
Generic | matFlo | Floor | |
Generic | roof | roofCase680 | Roof |
Win600 | window600 | redeclare parameter Building... | Window |
DaySchedule | TSetHea | redeclare BaseClasses.DaySch... | Heating setpoint |
DaySchedule | TSetCoo | redeclare BaseClasses.DaySch... | Cooling setpoint |
ExteriorWallCase680 | extWalCase680 | Exterior wall | |
RoofCase680 | roofCase680 | Roof |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case680FF
Case 600FF, but with increased exterior wall and roof insulation
Information
This model is used for the test case 680FF of the BESTEST validation suite. Case 680FF is a light-weight building with increased exterior wall and roof insulation. The room temperature is free floating.
Extends from Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600FF (Basic test with light-weight construction and free floating temperature).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | extWalCase680 | Exterior wall |
Generic | matFlo | Floor | |
Generic | roof | roofCase680 | Roof |
Win600 | window600 | redeclare parameter Building... | Window |
ExteriorWallCase680 | extWalCase680 | extWalCase680(roughness_a=Bu... | Exterior wall |
RoofCase680 | roofCase680 | roofCase680(roughness_a=Buil... | Roof |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case685
Case 600, but with single setpoint for heating and cooling
Information
This model is the case 685 of the BESTEST validation suite. Case 685 differs from case 600 in that it has single heating and cooling setpoint.
- Heat = on if zone temperature is below 20°C
- Cool = on if zone temperature is above 20°C
Extends from Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600 (Case 600FF, but with dual-setpoint for heating and cooling).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | Exterior wall | |
Generic | matFlo | Floor | |
Generic | roof | Roof | |
Win600 | window600 | redeclare parameter Building... | Window |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |
Modelica definition
Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case695
Case 600, but with increased exterior wall and roof insulation and single cooling and heating setpoint
Information
This model is the case 695 of the BESTEST validation suite. Case 695 differs from case 600 in that it has increased exterior wall and roof insulation and it has single heating and cooling setpoint.
- Heat = on if zone temperature is below 20°C
- Cool = on if zone temperature is above 20°C
Extends from Buildings.ThermalZones.Detailed.Validation.BESTEST.Cases6xx.Case600 (Case 600FF, but with dual-setpoint for heating and cooling).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Angle | S_ | Buildings.Types.Azimuth.S | Azimuth for south walls [rad] |
Angle | E_ | Buildings.Types.Azimuth.E | Azimuth for east walls [rad] |
Angle | W_ | Buildings.Types.Azimuth.W | Azimuth for west walls [rad] |
Angle | N_ | Buildings.Types.Azimuth.N | Azimuth for north walls [rad] |
Angle | C_ | Buildings.Types.Tilt.Ceiling | Tilt for ceiling [rad] |
Angle | F_ | Buildings.Types.Tilt.Floor | Tilt for floor [rad] |
Angle | Z_ | Buildings.Types.Tilt.Wall | Tilt for wall [rad] |
Integer | nConExtWin | 1 | Number of constructions with a window |
Integer | nConBou | 1 | Number of surface that are connected to constructions that are modeled inside the room |
Generic | matExtWal | extWalCase680 | Exterior wall |
Generic | matFlo | Floor | |
Generic | roof | roofCase680 | Roof |
Win600 | window600 | redeclare parameter Building... | Window |
ExteriorWallCase680 | extWalCase680 | Exterior wall | |
RoofCase680 | roofCase680 | Roof |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus | Weather data bus |