Buildings.Fluid.Chillers.Data.ElectricEIR
Performance data for chiller ElectricEIR
Information
Package with performance data for chillers.
Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).
Package Content
Name | Description |
---|---|
Generic | Generic data record for chiller ElectricEIR |
ElectricEIRChiller_McQuay_WSC_471kW_5_89COP_Vanes | ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes |
ElectricEIRChiller_York_YT_563kW_10_61COP_Vanes | ElectricEIRChiller York YT 563kW/10.61COP/Vanes |
ElectricEIRChiller_McQuay_PEH_703kW_7_03COP_Vanes | ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes |
ElectricEIRChiller_Carrier_23XL_724kW_6_04COP_Vanes | ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes |
ElectricEIRChiller_Carrier_19XR_742kW_5_42COP_VSD | ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD |
ElectricEIRChiller_McQuay_WSC_816kW_6_74COP_Vanes | ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes |
ElectricEIRChiller_McQuay_PEH_819kW_8_11COP_Vanes | ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes |
ElectricEIRChiller_Carrier_19XR_823kW_6_28COP_Vanes | ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes |
ElectricEIRChiller_Carrier_19XR_869kW_5_57COP_VSD | ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD |
ElectricEIRChiller_Carrier_19XR_897kW_7_23COP_VSD | ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD |
ElectricEIRChiller_Carrier_19XR_897kW_6_50COP_Vanes | ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes |
ElectricEIRChiller_York_YT_897kW_7_60COP_VSD | ElectricEIRChiller York YT 897kW/7.60COP/VSD |
ElectricEIRChiller_York_YT_897kW_6_27COP_VSD | ElectricEIRChiller York YT 897kW/6.27COP/VSD |
ElectricEIRChiller_Carrier_19XR_897kW_6_23COP_VSD | ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD |
ElectricEIRChiller_McQuay_PFH_932kW_5_09COP_Vanes | ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes |
ElectricEIRChiller_York_YT_960kW_4_64COP_Vanes | ElectricEIRChiller York YT 960kW/4.64COP/Vanes |
ElectricEIRChiller_York_YT_1023kW_5_81COP_Vanes | ElectricEIRChiller York YT 1023kW/5.81COP/Vanes |
ElectricEIRChiller_McQuay_PEH_1030kW_8_58COP_Vanes | ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes |
ElectricEIRChiller_York_YT_1048kW_6_06COP_Vanes | ElectricEIRChiller York YT 1048kW/6.06COP/Vanes |
ElectricEIRChiller_York_YT_1055kW_5_96COP_Vanes | ElectricEIRChiller York YT 1055kW/5.96COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1076kW_5_52COP_Vanes | ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes |
ElectricEIRChiller_Trane_CVHE_1080kW_7_39COP_Vanes | ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes |
ElectricEIRChiller_York_YT_1090kW_7_57COP_VSD | ElectricEIRChiller York YT 1090kW/7.57COP/VSD |
ElectricEIRChiller_McQuay_PEH_1104kW_8_00COP_Vanes | ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes |
ElectricEIRChiller_Trane_CVHE_1125kW_4_89COP_Vanes | ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes |
ElectricEIRChiller_York_YT_1125kW_7_92COP_VSD | ElectricEIRChiller York YT 1125kW/7.92COP/VSD |
ElectricEIRChiller_Trane_CVHE_1129kW_7_19COP_Vanes | ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1143kW_6_57COP_VSD | ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD |
ElectricEIRChiller_Carrier_19XR_1157kW_5_62COP_VSD | ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD |
ElectricEIRChiller_Carrier_19XR_1196kW_6_50COP_Vanes | ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1213kW_7_78COP_Vanes | ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes |
ElectricEIRChiller_McQuay_PEH_1231kW_6_18COP_Vanes | ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1234kW_5_39COP_VSD | ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD |
ElectricEIRChiller_Carrier_19XR_1259kW_6_26COP_Vanes | ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes |
ElectricEIRChiller_York_YK_1259kW_6_45COP_Vanes | ElectricEIRChiller York YK 1259kW/6.45COP/Vanes |
ElectricEIRChiller_York_YT_1266kW_4_39COP_Vanes | ElectricEIRChiller York YT 1266kW/4.39COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1284kW_6_20COP_Vanes | ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1294kW_7_61COP_Vanes | ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes |
ElectricEIRChiller_Trane_CVHE_1329kW_5_38COP_Vanes | ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1350kW_7_90COP_VSD | ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD |
ElectricEIRChiller_York_YT_1368kW_7_35COP_VSD | ElectricEIRChiller York YT 1368kW/7.35COP/VSD |
ElectricEIRChiller_Trane_CVHE_1372kW_7_49COP_Vanes | ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes |
ElectricEIRChiller_York_YT_1396kW_7_35COP_Vanes | ElectricEIRChiller York YT 1396kW/7.35COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1403kW_7_09COP_VSD | ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD |
ElectricEIRChiller_York_YT_1403kW_6_94COP_VSD | ElectricEIRChiller York YT 1403kW/6.94COP/VSD |
ElectricEIRChiller_Trane_CVHE_1407kW_7_14COP_VSD | ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD |
ElectricEIRChiller_McQuay_PFH_1407kW_6_60COP_Vanes | ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1407kW_6_04COP_VSD | ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD |
ElectricEIRChiller_Carrier_19XR_1410kW_8_54COP_VSD | ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD |
ElectricEIRChiller_Trane_CVHE_1442kW_6_61COP_VSD | ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD |
ElectricEIRChiller_York_YT_1459kW_6_40COP_VSD | ElectricEIRChiller York YT 1459kW/6.40COP/VSD |
ElectricEIRChiller_Trane_CVHE_1484kW_9_96COP_VSD | ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD |
ElectricEIRChiller_York_YT_1495kW_7_51COP_VSD | ElectricEIRChiller York YT 1495kW/7.51COP/VSD |
ElectricEIRChiller_McQuay_WSC_1519kW_7_10COP_Vanes | ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1558kW_5_81COP_VSD | ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD |
ElectricEIRChiller_Carrier_19XR_1586kW_5_53COP_VSD | ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD |
ElectricEIRChiller_McQuay_PEH_1635kW_7_47COP_Vanes | ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1635kW_6_36COP_Vanes | ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1656kW_8_24COP_VSD | ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD |
ElectricEIRChiller_York_YT_1663kW_9_34COP_Vanes | ElectricEIRChiller York YT 1663kW/9.34COP/Vanes |
ElectricEIRChiller_Carrier_19XL_1674kW_7_89COP_Vanes | ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes |
ElectricEIRChiller_Trane_CVHF_1681kW_6_59COP_Vanes | ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1723kW_8_32COP_VSD | ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD |
ElectricEIRChiller_Carrier_19XR_1727kW_9_04COP_Vanes | ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes |
ElectricEIRChiller_McQuay_WSC_1751kW_6_73COP_Vanes | ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes |
ElectricEIRChiller_Trane_CVHF_1758kW_5_96COP_Vanes | ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes |
ElectricEIRChiller_York_YT_1758kW_5_76COP_VSD | ElectricEIRChiller York YT 1758kW/5.76COP/VSD |
ElectricEIRChiller_York_YT_1758kW_6_26COP_Vanes | ElectricEIRChiller York YT 1758kW/6.26COP/Vanes |
ElectricEIRChiller_York_YT_1758kW_5_96COP_Vanes | ElectricEIRChiller York YT 1758kW/5.96COP/Vanes |
ElectricEIRChiller_Trane_CVHE_1758kW_5_96COP_Vanes | ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes |
ElectricEIRChiller_York_YT_1758kW_6_28COP_Vanes | ElectricEIRChiller York YT 1758kW/6.28COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1758kW_5_86COP_VSD | ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD |
ElectricEIRChiller_Trane_CVHF_1758kW_6_46COP_VSD | ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD |
ElectricEIRChiller_Trane_CVHF_1758kW_6_87COP_Vanes | ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1776kW_8_00COP_Vanes | ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes |
ElectricEIRChiller_Carrier_19XL_1779kW_6_18COP_Vanes | ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes |
ElectricEIRChiller_Trane_CVHF_1779kW_6_18COP_Vanes | ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes |
ElectricEIRChiller_York_YT_1794kW_8_11COP_Vanes | ElectricEIRChiller York YT 1794kW/8.11COP/Vanes |
ElectricEIRChiller_York_YT_1794kW_7_90COP_VSD | ElectricEIRChiller York YT 1794kW/7.90COP/VSD |
ElectricEIRChiller_Carrier_19XL_1797kW_5_69COP_Vanes | ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes |
ElectricEIRChiller_Carrier_19XR_1801kW_6_34COP_VSD | ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD |
ElectricEIRChiller_York_YT_1867kW_10_09COP_Vanes | ElectricEIRChiller York YT 1867kW/10.09COP/Vanes |
ElectricEIRChiller_Carrier_19XL_1871kW_6_49COP_Vanes | ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes |
ElectricEIRChiller_York_YT_1881kW_6_77COP_VSD | ElectricEIRChiller York YT 1881kW/6.77COP/VSD |
ElectricEIRChiller_York_YK_1881kW_6_53COP_Vanes | ElectricEIRChiller York YK 1881kW/6.53COP/Vanes |
ElectricEIRChiller_McQuay_PEH_1895kW_6_42COP_Vanes | ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes |
ElectricEIRChiller_York_YT_1934kW_7_55COP_Vanes | ElectricEIRChiller York YT 1934kW/7.55COP/Vanes |
ElectricEIRChiller_McQuay_PEH_1934kW_6_01COP_Vanes | ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes |
ElectricEIRChiller_McQuay_WDC_1973kW_6_28COP_Vanes | ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes |
ElectricEIRChiller_York_YK_1997kW_7_24COP_Vanes | ElectricEIRChiller York YK 1997kW/7.24COP/Vanes |
ElectricEIRChiller_McQuay_PFH_2043kW_8_44COP_Vanes | ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes |
ElectricEIRChiller_Trane_CVHF_2043kW_9_08COP_Vanes | ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes |
ElectricEIRChiller_Carrier_19XL_2057kW_6_05COP_Vanes | ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes |
ElectricEIRChiller_York_YT_2110kW_7_15COP_Vanes | ElectricEIRChiller York YT 2110kW/7.15COP/Vanes |
ElectricEIRChiller_McQuay_PFH_2124kW_6_03COP_Vanes | ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes |
ElectricEIRChiller_York_YK_2159kW_6_85COP_Vanes | ElectricEIRChiller York YK 2159kW/6.85COP/Vanes |
ElectricEIRChiller_Trane_CVHF_2184kW_6_78COP_Vanes | ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes |
ElectricEIRChiller_York_YK_2201kW_6_69COP_Vanes | ElectricEIRChiller York YK 2201kW/6.69COP/Vanes |
ElectricEIRChiller_York_YT_2233kW_9_54COP_VSD | ElectricEIRChiller York YT 2233kW/9.54COP/VSD |
ElectricEIRChiller_York_YK_2237kW_6_41COP_Vanes | ElectricEIRChiller York YK 2237kW/6.41COP/Vanes |
ElectricEIRChiller_York_YK_2275kW_6_32COP_Vanes | ElectricEIRChiller York YK 2275kW/6.32COP/Vanes |
ElectricEIRChiller_Trane_CVHF_2300kW_8_10COP_Vanes | ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes |
ElectricEIRChiller_Trane_CVHF_2317kW_6_33COP_VSD | ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD |
ElectricEIRChiller_Carrier_19XR_2391kW_6_77COP_Vanes | ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes |
ElectricEIRChiller_Carrier_19XR_2391kW_6_44COP_VSD | ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD |
ElectricEIRChiller_York_YK_2412kW_5_58COP_Vanes | ElectricEIRChiller York YK 2412kW/5.58COP/Vanes |
ElectricEIRChiller_McQuay_PFH_2462kW_6_67COP_Vanes | ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes |
ElectricEIRChiller_Trane_CVHF_2567kW_11_77COP_VSD | ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD |
ElectricEIRChiller_York_YK_2771kW_6_84COP_VSD | ElectricEIRChiller York YK 2771kW/6.84COP/VSD |
ElectricEIRChiller_Trane_CVHF_2799kW_6_40COP_Vanes | ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes |
ElectricEIRChiller_York_YT_3133kW_9_16COP_Vanes | ElectricEIRChiller York YT 3133kW/9.16COP/Vanes |
ElectricEIRChiller_McQuay_PFH_3165kW_6_48COP_Vanes | ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes |
ElectricEIRChiller_McQuay_PFH_4020kW_7_35COP_Vanes | ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes |
ElectricEIRChiller_York_YK_4396kW_6_63COP_Vanes | ElectricEIRChiller York YK 4396kW/6.63COP/Vanes |
ElectricEIRChiller_York_YK_4477kW_6_64COP_Vanes | ElectricEIRChiller York YK 4477kW/6.64COP/Vanes |
ElectricEIRChiller_York_YK_4515kW_6_22COP_Vanes | ElectricEIRChiller York YK 4515kW/6.22COP/Vanes |
ElectricEIRChiller_York_YK_4537kW_6_28COP_Vanes | ElectricEIRChiller York YK 4537kW/6.28COP/Vanes |
ElectricEIRChiller_Trane_CVHF_4610kW_6_34COP_Vanes | ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes |
ElectricEIRChiller_Carrier_19EX_4667kW_6_16COP_Vanes | ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes |
ElectricEIRChiller_Trane_CVHF_4677kW_6_27COP_Vanes | ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes |
ElectricEIRChiller_York_YK_4966kW_6_05COP_Vanes | ElectricEIRChiller York YK 4966kW/6.05COP/Vanes |
ElectricEIRChiller_York_YK_4969kW_7_14COP_Vanes | ElectricEIRChiller York YK 4969kW/7.14COP/Vanes |
ElectricEIRChiller_York_YK_4969kW_7_07COP_Vanes | ElectricEIRChiller York YK 4969kW/7.07COP/Vanes |
ElectricEIRChiller_Carrier_19EX_4997kW_6_40COP_Vanes | ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes |
ElectricEIRChiller_Carrier_19EX_5148kW_6_34COP_Vanes | ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes |
ElectricEIRChiller_York_YK_5170kW_7_15COP_Vanes | ElectricEIRChiller York YK 5170kW/7.15COP/Vanes |
ElectricEIRChiller_Carrier_19EX_5208kW_6_88COP_Vanes | ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes |
ElectricEIRChiller_York_YK_5465kW_6_94COP_Vanes | ElectricEIRChiller York YK 5465kW/6.94COP/Vanes |
ElectricEIRChiller_York_YK_5549kW_6_50COP_Vanes | ElectricEIRChiller York YK 5549kW/6.50COP/Vanes |
ElectricEIRChiller_Carrier_19FA_5651kW_5_50COP_Vanes | ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes |
DOE_2_Centrifugal_5_50COP | DOE-2 Centrifugal/5.50COP |
ElectricEIRChiller_Multistack_MS_172kW_3_67COP_None | ElectricEIRChiller Multistack MS 172kW/3.67COP/None |
DOE_2_Reciprocating_3_67COP | DOE-2 Reciprocating/3.67COP |
ElectricEIRChiller_Trane_RTWA_383kW_4_17COP_Valve | ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve |
ElectricEIRChiller_Trane_RTHB_531kW_4_83COP_Valve | ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve |
ElectricEIRChiller_Trane_RTHB_538kW_5_12COP_Valve | ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve |
ElectricEIRChiller_Trane_RTHB_542kW_5_26COP_Valve | ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve |
ElectricEIRChiller_York_YS_672kW_7_90COP_Valve | ElectricEIRChiller York YS 672kW/7.90COP/Valve |
ElectricEIRChiller_Carrier_23XL_686kW_5_91COP_Valve | ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve |
ElectricEIRChiller_Trane_RTHC_707kW_7_77COP_Valve | ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve |
ElectricEIRChiller_York_YS_756kW_7_41COP_Valve | ElectricEIRChiller York YS 756kW/7.41COP/Valve |
ElectricEIRChiller_York_YS_781kW_5_42COP_Valve | ElectricEIRChiller York YS 781kW/5.42COP/Valve |
ElectricEIRChiller_Carrier_23XL_830kW_6_97COP_Valve | ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve |
ElectricEIRChiller_Carrier_23XL_862kW_6_11COP_Valve | ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve |
ElectricEIRChiller_Carrier_23XL_862kW_6_84COP_Valve | ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve |
ElectricEIRChiller_Carrier_23XL_865kW_6_05COP_Valve | ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve |
ElectricEIRChiller_York_YS_879kW_5_82COP_Valve | ElectricEIRChiller York YS 879kW/5.82COP/Valve |
ElectricEIRChiller_Trane_RTHC_1009kW_5_37COP_Valve | ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve |
ElectricEIRChiller_Trane_RTHB_1051kW_5_05COP_Valve | ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve |
ElectricEIRChiller_Carrier_23XL_1062kW_5_50COP_Valve | ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve |
ElectricEIRChiller_Trane_RTHC_1066kW_5_73COP_Valve | ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve |
ElectricEIRChiller_Trane_RTHC_1094kW_6_55COP_Valve | ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve |
ElectricEIRChiller_Carrier_23XL_1108kW_6_92COP_Valve | ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve |
ElectricEIRChiller_York_YS_1171kW_9_15COP_Valve | ElectricEIRChiller York YS 1171kW/9.15COP/Valve |
ElectricEIRChiller_Carrier_23XL_1196kW_6_39COP_Valve | ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve |
ElectricEIRChiller_York_YS_1554kW_9_31COP_Valve | ElectricEIRChiller York YS 1554kW/9.31COP/Valve |
ElectricEIRChiller_York_YS_1758kW_5_84COP_Valve | ElectricEIRChiller York YS 1758kW/5.84COP/Valve |
ElectricEIRChiller_Trane_CGWD_207kW_3_99COP_None | ElectricEIRChiller Trane CGWD 207kW/3.99COP/None |
ElectricEIRChiller_York_YCAL0033EE_101kW_3_1COP_AirCooled | ElectricEIRChiller York YCAL0033EE 100.6 kW/3.1 COP Air Cooled |
Buildings.Fluid.Chillers.Data.ElectricEIR.Generic
Generic data record for chiller ElectricEIR
Information
This record is used as a template for performance data for the chiller model Buildings.Fluid.Chillers.ElectricEIR.
Extends from Buildings.Fluid.Chillers.Data.BaseClasses.Chiller (Base classes for chiller models).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | Maximum part load ratio | |
Real | PLRMinUnl | Minimum part unload ratio | |
Real | PLRMin | Minimum part load ratio | |
Real | etaMotor | Fraction of compressor motor heat entering refrigerant | |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | Reference capacity (negative number) [W] | |
Real | COP_nominal | Reference coefficient of performance | |
MassFlowRate | mEva_flow_nominal | Nominal mass flow at evaporator [kg/s] | |
MassFlowRate | mCon_flow_nominal | Nominal mass flow at condenser [kg/s] | |
Temperature | TEvaLvg_nominal | Temperature of fluid leaving evaporator at nominal condition [K] | |
Temperature | TConEnt_nominal | Temperature of fluid entering condenser at nominal condition [K] | |
Performance curves | |||
Integer | nCapFunT | 6 | Number of coefficients for capFunT |
Integer | nEIRFunT | 6 | Number of coefficients for EIRFunT |
Integer | nEIRFunPLR | 3 | Number of coefficients for EIRFunPLR |
Real | capFunT[nCapFunT] | Biquadratic coefficients for capFunT | |
Real | EIRFunT[nEIRFunT] | Biquadratic coefficients for EIRFunT | |
Real | EIRFunPLR[nEIRFunPLR] | Coefficients for EIRFunPLR | |
Temperature | TEvaLvgMin | Minimum value for leaving evaporator temperature [K] | |
Temperature | TEvaLvgMax | Maximum value for leaving evaporator temperature [K] | |
Temperature | TConEntMin | Minimum value for entering condenser temperature [K] | |
Temperature | TConEntMax | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_WSC_471kW_5_89COP_Vanes
ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes, !- Name 471200, !- Reference Capacity {W} 5.89, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.01035, !- Reference Chilled Water Flow Rate {m3/s} 0.01924, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 471kW/5.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.15, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.15 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -471200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.89 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01035 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01924 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.521130E-01,1.324053E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.475238E-01,-2.588210E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.778889E-01,2.338363E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_563kW_10_61COP_Vanes
ElectricEIRChiller York YT 563kW/10.61COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 563kW/10.61COP/Vanes, !- Name 562600, !- Reference Capacity {W} 10.61, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.01514, !- Reference Chilled Water Flow Rate {m3/s} 0.0241, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 563kW/10.61COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 563kW/10.61COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 563kW/10.61COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -562600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 10.61 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01514 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0241 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.288612E-01,-8.919540E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-5.781003E-01,-1.169130E-01... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.203969E-01,-7.775900E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_703kW_7_03COP_Vanes
ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes, !- Name 703300, !- Reference Capacity {W} 7.03, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.02019, !- Reference Chilled Water Flow Rate {m3/s} 0.02902, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 703kW/7.03COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -703300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.03 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02019 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02902 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.779439E-01,1.073486E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.234029E-01,-1.171542E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.864389E-01,-2.522595E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_724kW_6_04COP_Vanes
ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes, !- Name 724400, !- Reference Capacity {W} 6.04, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 21.11, !- Reference Entering Condenser Fluid Temperature {C} 0.01779, !- Reference Chilled Water Flow Rate {m3/s} 0.01956, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 724kW/6.04COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -724400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.04 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01779 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.418712E-01,-8.384251E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.059102E-01,-1.621557E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.879418E-01,3.562862E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 13.75 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_742kW_5_42COP_VSD
ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD, !- Name 742000, !- Reference Capacity {W} 5.42, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 21.11, !- Reference Entering Condenser Fluid Temperature {C} 0.01779, !- Reference Chilled Water Flow Rate {m3/s} 0.01956, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 742kW/5.42COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -742000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.42 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01779 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.797101E-01,-2.895701E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.946139E-01,-4.829399E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.202277E-01,1.396384E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 11.25 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_WSC_816kW_6_74COP_Vanes
ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes, !- Name 815800, !- Reference Capacity {W} 6.74, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.01748, !- Reference Chilled Water Flow Rate {m3/s} 0.04164, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 816kW/6.74COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -815800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.74 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01748 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04164 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.862590E-01,5.799373E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.335321E-01,4.465107E-04,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.070136E-01,8.654874E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_819kW_8_11COP_Vanes
ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes, !- Name 819300, !- Reference Capacity {W} 8.11, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.02524, !- Reference Chilled Water Flow Rate {m3/s} 0.03785, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 819kW/8.11COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -819300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.11 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02524 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03785 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.392673E-01,4.328784E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.925176E-01,-1.908391E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.830681E-01,2.254147E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_823kW_6_28COP_Vanes
ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes, !- Name 822900, !- Reference Capacity {W} 6.28, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.04744, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 823kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -822900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.573150E-01,8.714616E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.029134E-01,2.171359E-02,2... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.965419E-01,4.689744E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_869kW_5_57COP_VSD
ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD, !- Name 868600, !- Reference Capacity {W} 5.57, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.01754, !- Reference Chilled Water Flow Rate {m3/s} 0.02593, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 869kW/5.57COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -868600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.57 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01754 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02593 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.406799E-01,1.253709E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.943721E-01,1.079147E-01,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.501042E-01,-6.804336E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_897kW_7_23COP_VSD
ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD, !- Name 896700, !- Reference Capacity {W} 7.23, !- Reference COP {W/W} 9.82, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.0436, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 897kW/7.23COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.23 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0436 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.82 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.559679E-01,7.630860E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.511011E-01,4.948557E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.036380E-01,-3.913200E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_897kW_6_50COP_Vanes
ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes, !- Name 896700, !- Reference Capacity {W} 6.50, !- Reference COP {W/W} 9.82, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.04423, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 897kW/6.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04423 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.82 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.009156E-01,2.151274E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.527749E-01,-4.336881E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.323416E-01,2.561103E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_897kW_7_60COP_VSD
ElectricEIRChiller York YT 897kW/7.60COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 897kW/7.60COP/VSD, !- Name 896700, !- Reference Capacity {W} 7.60, !- Reference COP {W/W} 9.83, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 897kW/7.60COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 897kW/7.60COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 897kW/7.60COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.60 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.83 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.699948E-01,2.961470E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.526128E-01,3.299472E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.708628E-02,7.070062E-02,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_897kW_6_27COP_VSD
ElectricEIRChiller York YT 897kW/6.27COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 897kW/6.27COP/VSD, !- Name 896700, !- Reference Capacity {W} 6.27, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 897kW/6.27COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 897kW/6.27COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 897kW/6.27COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.27 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.197991E-01,1.568955E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.530767E-01,-5.683068E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.836320E-02,-1.638320E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_897kW_6_23COP_VSD
ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD, !- Name 896700, !- Reference Capacity {W} 6.23, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.04442, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 897kW/6.23COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -896700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.23 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04442 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.862185E-01,3.144947E-02,2... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.606461E-01,-1.202294E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.075556E-01,-2.126466E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_932kW_5_09COP_Vanes
ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes, !- Name 931900, !- Reference Capacity {W} 5.09, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.03785, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 932kW/5.09COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -931900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.09 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.182278E+00,3.259490E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.053491E-01,-1.089778E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.823245E-02,6.672421E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_960kW_4_64COP_Vanes
ElectricEIRChiller York YT 960kW/4.64COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 960kW/4.64COP/Vanes, !- Name 960000, !- Reference Capacity {W} 4.64, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.03785, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 960kW/4.64COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 960kW/4.64COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 960kW/4.64COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.09, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.09 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -960000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.64 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-2.278537E-01,4.055945E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.735924E-01,2.270414E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.737941E-01,3.141127E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1023kW_5_81COP_Vanes
ElectricEIRChiller York YT 1023kW/5.81COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1023kW/5.81COP/Vanes, !- Name 1023300, !- Reference Capacity {W} 5.81, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.02366, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1023kW/5.81COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1023kW/5.81COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1023kW/5.81COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1023300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.81 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02366 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.571195E-01,-1.571421E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.254964E-01,-1.972389E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.368399E-01,3.286421E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_1030kW_8_58COP_Vanes
ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes, !- Name 1030300, !- Reference Capacity {W} 8.58, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.02378, !- Reference Chilled Water Flow Rate {m3/s} 0.03407, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1030kW/8.58COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.08, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.08, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1030300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.58 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02378 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03407 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.736028E-01,5.571395E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.125878E-01,1.388940E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.215320E-01,-9.188416E-03,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1048kW_6_06COP_Vanes
ElectricEIRChiller York YT 1048kW/6.06COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1048kW/6.06COP/Vanes, !- Name 1047900, !- Reference Capacity {W} 6.06, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.04542, !- Reference Chilled Water Flow Rate {m3/s} 0.05678, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1048kW/6.06COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1048kW/6.06COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1048kW/6.06COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1047900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.06 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04542 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05678 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.238221E-01,1.747548E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.255594E-01,-3.502968E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.543796E-01,7.276121E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1055kW_5_96COP_Vanes
ElectricEIRChiller York YT 1055kW/5.96COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1055kW/5.96COP/Vanes, !- Name 1055000, !- Reference Capacity {W} 5.96, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.02839, !- Reference Chilled Water Flow Rate {m3/s} 0.05678, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1055kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1055kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1055kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1055000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02839 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05678 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.785912E-01,-5.900023E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.245110E-01,-2.850126E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.619878E-01,2.393605E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1076kW_5_52COP_Vanes
ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes, !- Name 1076100, !- Reference Capacity {W} 5.52, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.89, !- Reference Entering Condenser Fluid Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.04744, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1076kW/5.52COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1076100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.52 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 24.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.187704E-01,4.509452E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.511044E-01,2.415573E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.315760E-01,-3.004087E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1080kW_7_39COP_Vanes
ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes, !- Name 1079600, !- Reference Capacity {W} 7.39, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.61, !- Reference Entering Condenser Fluid Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.06416, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1080kW/7.39COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1079600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06416 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.61 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.365583E-01,-3.677215E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.608716E-01,-5.637178E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.789841E-01,2.976513E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 16.24 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.61 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1090kW_7_57COP_VSD
ElectricEIRChiller York YT 1090kW/7.57COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1090kW/7.57COP/VSD, !- Name 1090100, !- Reference Capacity {W} 7.57, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1090kW/7.57COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1090kW/7.57COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1090kW/7.57COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1090100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.57 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.769028E-01,5.711844E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.241019E-01,-4.961574E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.431969E-01,-4.920686E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_1104kW_8_00COP_Vanes
ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes, !- Name 1104200, !- Reference Capacity {W} 8.00, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.02423, !- Reference Chilled Water Flow Rate {m3/s} 0.03028, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1104kW/8.00COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.08, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.08, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1104200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.00 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02423 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03028 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.210185E-01,4.386152E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.655242E-01,-3.808337E-04,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.091150E-01,-1.089639E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1125kW_4_89COP_Vanes
ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes, !- Name 1125300, !- Reference Capacity {W} 4.89, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.02776, !- Reference Chilled Water Flow Rate {m3/s} 0.02618, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1125kW/4.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1125300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.89 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02776 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02618 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.151549E-01,-1.181250E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.810580E-01,-4.344257E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.807198E-01,-1.469686E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1125kW_7_92COP_VSD
ElectricEIRChiller York YT 1125kW/7.92COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1125kW/7.92COP/VSD, !- Name 1125300, !- Reference Capacity {W} 7.92, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03243, !- Reference Chilled Water Flow Rate {m3/s} 0.05173, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1125kW/7.92COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1125kW/7.92COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1125kW/7.92COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1125300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.92 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05173 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.034212E-01,2.327078E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.542286E-01,-2.451604E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.147453E-01,4.231235E-02,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1129kW_7_19COP_Vanes
ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes, !- Name 1128800, !- Reference Capacity {W} 7.19, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.02776, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1129kW/7.19COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.15, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.15, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.15 | Minimum part unload ratio |
Real | PLRMin | 0.15 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1128800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.19 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02776 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.922479E-01,-4.388411E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.742142E-01,-5.536709E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.693841E-01,2.475201E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1143kW_6_57COP_VSD
ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD, !- Name 1142900, !- Reference Capacity {W} 6.57, !- Reference COP {W/W} 10.00, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.02593, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1143kW/6.57COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1142900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.57 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 10.00 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.939538E-01,4.096493E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.475580E-01,-1.187942E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.408822E-01,-1.578153E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1157kW_5_62COP_VSD
ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD, !- Name 1156900, !- Reference Capacity {W} 5.62, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 21.11, !- Reference Entering Condenser Fluid Temperature {C} 0.02801, !- Reference Chilled Water Flow Rate {m3/s} 0.03186, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1157kW/5.62COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1156900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.62 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02801 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03186 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.076248E+00,5.436724E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.075567E+00,-3.893571E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.608589E-01,-2.058215E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 11.25 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1196kW_6_50COP_Vanes
ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes, !- Name 1195600, !- Reference Capacity {W} 6.50, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.03426, !- Reference Chilled Water Flow Rate {m3/s} 0.04252, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1196kW/6.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1195600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03426 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04252 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.126801E+00,-4.220591E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.514432E-01,-2.252147E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.724491E-01,2.710369E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1213kW_7_78COP_Vanes
ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes, !- Name 1213200, !- Reference Capacity {W} 7.78, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03243, !- Reference Chilled Water Flow Rate {m3/s} 0.04782, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1213kW/7.78COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1213200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.78 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04782 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.070437E-01,-7.437456E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.002142E+00,-2.505239E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.847744E-01,4.027863E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_1231kW_6_18COP_Vanes
ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes, !- Name 1230800, !- Reference Capacity {W} 6.18, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03533, !- Reference Chilled Water Flow Rate {m3/s} 0.0511, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1231kW/6.18COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1230800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.18 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03533 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0511 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.152795E+00,9.770474E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.067591E-01,1.868314E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.117054E-01,4.263662E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1234kW_5_39COP_VSD
ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD, !- Name 1234300, !- Reference Capacity {W} 5.39, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.02593, !- Reference Chilled Water Flow Rate {m3/s} 0.03861, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1234kW/5.39COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1234300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03861 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.905815E-01,1.190927E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.771659E-01,1.144965E-01,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.495681E-01,-1.449639E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1259kW_6_26COP_Vanes
ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes, !- Name 1258900, !- Reference Capacity {W} 6.26, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.02593, !- Reference Chilled Water Flow Rate {m3/s} 0.03823, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1259kW/6.26COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1258900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.26 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02593 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03823 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.082071E+00,3.200888E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.582035E-01,6.896017E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.226232E-01,5.199282E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_1259kW_6_45COP_Vanes
ElectricEIRChiller York YK 1259kW/6.45COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 1259kW/6.45COP/Vanes, !- Name 1258900, !- Reference Capacity {W} 6.45, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.02631, !- Reference Chilled Water Flow Rate {m3/s} 0.06246, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 1259kW/6.45COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 1259kW/6.45COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 1259kW/6.45COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1258900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.45 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.02631 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06246 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.609200E-01,7.223733E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.991536E-01,6.305932E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.014593E-01,6.216537E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1266kW_4_39COP_Vanes
ElectricEIRChiller York YT 1266kW/4.39COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1266kW/4.39COP/Vanes, !- Name 1266000, !- Reference Capacity {W} 4.39, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 35.00, !- Reference Entering Condenser Fluid Temperature {C} 0.03533, !- Reference Chilled Water Flow Rate {m3/s} 0.05773, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1266kW/4.39COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1266kW/4.39COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1266kW/4.39COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.11, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.11, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1266000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03533 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05773 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 35.00 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.285663E-01,-2.860032E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.284925E-02,4.206167E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.326942E-01,-7.962527E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1284kW_6_20COP_Vanes
ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes, !- Name 1283500, !- Reference Capacity {W} 6.20, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03684, !- Reference Chilled Water Flow Rate {m3/s} 0.05337, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1284kW/6.20COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1283500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.20 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03684 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.119245E+00,-1.524417E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.815645E-01,-2.448971E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.324812E-01,7.690691E-01,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1294kW_7_61COP_Vanes
ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes, !- Name 1294100, !- Reference Capacity {W} 7.61, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03243, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1294kW/7.61COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.16, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.16, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.16 | Minimum part unload ratio |
Real | PLRMin | 0.16 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1294100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.61 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03243 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.274222E-01,1.278683E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.085249E+00,-9.441252E-04,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.344563E-02,3.993002E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1329kW_5_38COP_Vanes
ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes, !- Name 1329300, !- Reference Capacity {W} 5.38, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.04732, !- Reference Chilled Water Flow Rate {m3/s} 0.07098, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1329kW/5.38COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.29, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.29, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.29 | Minimum part unload ratio |
Real | PLRMin | 0.29 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1329300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.38 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04732 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07098 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.339754E-01,1.016009E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.074052E-01,3.355495E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.079777E-02,1.174456E+00,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 21.11 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1350kW_7_90COP_VSD
ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD, !- Name 1350400, !- Reference Capacity {W} 7.90, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03684, !- Reference Chilled Water Flow Rate {m3/s} 0.05337, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1350kW/7.90COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1350400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.90 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03684 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.063866E+00,-1.448990E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.953536E-01,-3.118863E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.336374E-01,-4.098166E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1368kW_7_35COP_VSD
ElectricEIRChiller York YT 1368kW/7.35COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1368kW/7.35COP/VSD, !- Name 1367900, !- Reference Capacity {W} 7.35, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1368kW/7.35COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1368kW/7.35COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1368kW/7.35COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1367900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.35 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.832184E-01,-3.265439E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.227543E-01,-1.415418E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.483562E-02,1.521114E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1372kW_7_49COP_Vanes
ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes, !- Name 1371500, !- Reference Capacity {W} 7.49, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1372kW/7.49COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.41, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.41, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1371500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.49 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.993784E-01,6.523380E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.123765E-01,1.616509E-02,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.154478E-02,9.635713E-01,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1396kW_7_35COP_Vanes
ElectricEIRChiller York YT 1396kW/7.35COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1396kW/7.35COP/Vanes, !- Name 1396100, !- Reference Capacity {W} 7.35, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1396kW/7.35COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1396kW/7.35COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1396kW/7.35COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1396100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.35 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.167863E-01,-2.788454E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.207500E-01,-9.073869E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.043032E-01,3.720107E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1403kW_7_09COP_VSD
ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD, !- Name 1403100, !- Reference Capacity {W} 7.09, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03426, !- Reference Chilled Water Flow Rate {m3/s} 0.04252, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1403kW/7.09COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1403100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.09 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03426 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04252 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.601814E-01,-3.596494E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.098641E+00,-2.485880E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.788698E-02,2.678891E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1403kW_6_94COP_VSD
ElectricEIRChiller York YT 1403kW/6.94COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1403kW/6.94COP/VSD, !- Name 1403100, !- Reference Capacity {W} 6.94, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.05047, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1403kW/6.94COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1403kW/6.94COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1403kW/6.94COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.1, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.1 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1403100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.94 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-3.447077E-02,1.273138E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.983846E-01,2.396665E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.272242E-02,3.873540E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1407kW_7_14COP_VSD
ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD, !- Name 1406600, !- Reference Capacity {W} 7.14, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1407kW/7.14COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.14 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.521342E-01,5.248142E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.674858E-01,4.461513E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.963988E-02,3.503067E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_1407kW_6_60COP_Vanes
ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes, !- Name 1406600, !- Reference Capacity {W} 6.60, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04038, !- Reference Chilled Water Flow Rate {m3/s} 0.05804, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 1407kW/6.60COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.60 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04038 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05804 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.191784E+00,2.070584E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.929709E-01,3.424884E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.700603E-02,5.414789E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1407kW_6_04COP_VSD
ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD, !- Name 1406600, !- Reference Capacity {W} 6.04, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06057, !- Reference Chilled Water Flow Rate {m3/s} 0.07571, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1407kW/6.04COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1406600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.04 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06057 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07571 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.042261E+00,2.644821E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.026340E+00,-1.612819E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.188880E-01,6.723542E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 32.22 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1410kW_8_54COP_VSD
ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD, !- Name 1410100, !- Reference Capacity {W} 8.54, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04, !- Reference Chilled Water Flow Rate {m3/s} 0.05861, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1410kW/8.54COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1410100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.54 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05861 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.597856E-01,-6.247187E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.131014E+00,-6.735406E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.662908E-02,7.475978E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1442kW_6_61COP_VSD
ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD, !- Name 1441800, !- Reference Capacity {W} 6.61, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.05047, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1442kW/6.61COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1441800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.61 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.007341E-01,1.148568E-03,1... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.287646E-01,-3.024605E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.299787E-02,3.244475E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1459kW_6_40COP_VSD
ElectricEIRChiller York YT 1459kW/6.40COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1459kW/6.40COP/VSD, !- Name 1459400, !- Reference Capacity {W} 6.40, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05047, !- Reference Chilled Water Flow Rate {m3/s} 0.05047, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1459kW/6.40COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1459kW/6.40COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1459kW/6.40COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.13, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.13 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1459400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.40 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05047 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05047 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.665585E-01,2.211580E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.438935E-01,9.821191E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.999642E-02,2.509430E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1484kW_9_96COP_VSD
ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD, !- Name 1484000, !- Reference Capacity {W} 9.96, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1484kW/9.96COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.24, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.24, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.24 | Minimum part unload ratio |
Real | PLRMin | 0.24 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1484000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-4.544480E-01,-3.615933E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {-3.693940E-01,-6.387787E-02... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.353827E-01,1.385983E-02,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1495kW_7_51COP_VSD
ElectricEIRChiller York YT 1495kW/7.51COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1495kW/7.51COP/VSD, !- Name 1494500, !- Reference Capacity {W} 7.51, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.0429, !- Reference Chilled Water Flow Rate {m3/s} 0.06719, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1495kW/7.51COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1495kW/7.51COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1495kW/7.51COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.11, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.11, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1494500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.51 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0429 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06719 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.051921E+00,-1.632255E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.106985E-01,-2.087623E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.517470E-01,-1.577252E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_WSC_1519kW_7_10COP_Vanes
ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes, !- Name 1519200, !- Reference Capacity {W} 7.10, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.08139, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 1519kW/7.10COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1519200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.10 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.08139 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.265889E+00,3.401563E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.981236E-01,-1.060763E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.563837E-01,4.894381E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1558kW_5_81COP_VSD
ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD, !- Name 1557800, !- Reference Capacity {W} 5.81, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 21.11, !- Reference Entering Condenser Fluid Temperature {C} 0.03785, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1558kW/5.81COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1557800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.81 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.034307E+00,2.390635E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.099343E+00,-3.132676E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.620909E-01,-2.553890E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 11.94 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1586kW_5_53COP_VSD
ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD, !- Name 1586000, !- Reference Capacity {W} 5.53, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.03388, !- Reference Chilled Water Flow Rate {m3/s} 0.04669, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1586kW/5.53COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1586000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.53 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03388 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04669 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.119233E+00,1.130501E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.110611E+00,-3.795765E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.996379E-01,-1.612021E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_1635kW_7_47COP_Vanes
ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes, !- Name 1635200, !- Reference Capacity {W} 7.47, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04416, !- Reference Chilled Water Flow Rate {m3/s} 0.06624, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1635kW/7.47COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.08, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.08, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1635200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.47 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04416 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06624 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.894188E-01,2.983148E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.040733E+00,-7.118888E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.836695E-01,5.781685E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1635kW_6_36COP_Vanes
ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes, !- Name 1635200, !- Reference Capacity {W} 6.36, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.03432, !- Reference Chilled Water Flow Rate {m3/s} 0.05035, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1635kW/6.36COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1635200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.36 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03432 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05035 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.639212E-01,1.160405E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.355981E-01,-1.083354E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.581595E-01,2.707154E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1656kW_8_24COP_VSD
ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD, !- Name 1656300, !- Reference Capacity {W} 8.24, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04322, !- Reference Chilled Water Flow Rate {m3/s} 0.06296, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1656kW/8.24COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1656300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.24 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04322 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06296 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.611706E-01,-2.867067E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.730916E-01,-8.073559E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.982584E-01,4.414042E-02,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1663kW_9_34COP_Vanes
ElectricEIRChiller York YT 1663kW/9.34COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1663kW/9.34COP/Vanes, !- Name 1663300, !- Reference Capacity {W} 9.34, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04139, !- Reference Chilled Water Flow Rate {m3/s} 0.0776, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1663kW/9.34COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1663kW/9.34COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1663kW/9.34COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1663300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04139 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0776 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.112226E-01,-4.546497E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.028094E+00,-6.127553E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.127966E-01,3.131004E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XL_1674kW_7_89COP_Vanes
ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes, !- Name 1673900, !- Reference Capacity {W} 7.89, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1674kW/7.89COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.32, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.32, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.32 | Minimum part unload ratio |
Real | PLRMin | 0.32 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1673900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.89 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.925408E-01,-4.406182E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.868510E-01,-6.325526E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.386410E-01,2.621224E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_1681kW_6_59COP_Vanes
ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes, !- Name 1680900, !- Reference Capacity {W} 6.59, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.04366, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1681kW/6.59COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1680900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.59 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04366 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.792987E-01,-5.291217E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.344630E-01,-5.781149E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.619116E-01,2.362420E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1723kW_8_32COP_VSD
ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD, !- Name 1723100, !- Reference Capacity {W} 8.32, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04757, !- Reference Chilled Water Flow Rate {m3/s} 0.06934, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1723kW/8.32COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1723100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.32 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06934 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.742518E-01,-5.109937E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.950574E-01,-1.036684E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.374010E-01,-1.796745E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1727kW_9_04COP_Vanes
ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes, !- Name 1726600, !- Reference Capacity {W} 9.04, !- Reference COP {W/W} 7.78, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.03912, !- Reference Chilled Water Flow Rate {m3/s} 0.07192, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1727kW/9.04COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1726600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.04 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03912 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07192 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.509915E-01,2.567642E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.072553E+00,-8.058631E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.465824E-01,4.494453E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_WSC_1751kW_6_73COP_Vanes
ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes, !- Name 1751300, !- Reference Capacity {W} 6.73, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.04145, !- Reference Chilled Water Flow Rate {m3/s} 0.09337, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay WSC 1751kW/6.73COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1751300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.73 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04145 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.923045E-01,1.003672E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.089395E-01,2.628482E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.250725E-01,2.648297E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_1758kW_5_96COP_Vanes
ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 5.96, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1758kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.074211E+00,7.710761E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.910329E-01,-9.895115E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.694797E-01,9.551656E-02,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1758kW_5_76COP_VSD
ElectricEIRChiller York YT 1758kW/5.76COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1758kW/5.76COP/VSD, !- Name 1758300, !- Reference Capacity {W} 5.76, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1758kW/5.76COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/5.76COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/5.76COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.76 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.575085E-01,1.313508E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.794525E-01,6.694756E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {7.859908E-02,1.950291E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.51 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1758kW_6_26COP_Vanes
ElectricEIRChiller York YT 1758kW/6.26COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1758kW/6.26COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 6.26, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1758kW/6.26COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/6.26COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/6.26COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.14, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.14 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.26 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.975936E-01,-1.459740E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.311197E-01,9.581517E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.720545E-01,5.598164E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1758kW_5_96COP_Vanes
ElectricEIRChiller York YT 1758kW/5.96COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1758kW/5.96COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 5.96, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1758kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.492365E-01,5.551947E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.949320E-01,9.099785E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.236154E-01,2.590053E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHE_1758kW_5_96COP_Vanes
ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 5.96, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHE 1758kW/5.96COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.96 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.566057E-02,-2.457943E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.243313E+00,-3.031784E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.871377E-01,5.849639E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1758kW_6_28COP_Vanes
ElectricEIRChiller York YT 1758kW/6.28COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1758kW/6.28COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 6.28, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1758kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1758kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.079149E-01,-2.006276E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.605391E-01,-1.377994E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.861223E-01,5.482049E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1758kW_5_86COP_VSD
ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD, !- Name 1758300, !- Reference Capacity {W} 5.86, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06303, !- Reference Chilled Water Flow Rate {m3/s} 0.07337, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1758kW/5.86COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.86 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.677279E-01,-3.175504E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.743365E-01,-5.054806E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.784580E-01,-5.498632E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_1758kW_6_46COP_VSD
ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD, !- Name 1758300, !- Reference Capacity {W} 6.46, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1758kW/6.46COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.46 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.066671E+00,5.889240E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.989434E-02,2.062907E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.268954E-01,3.297771E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_1758kW_6_87COP_Vanes
ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes, !- Name 1758300, !- Reference Capacity {W} 6.87, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.44, !- Reference Entering Condenser Fluid Temperature {C} 0.06309, !- Reference Chilled Water Flow Rate {m3/s} 0.06309, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1758kW/6.87COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.87 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06309 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06309 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 24.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.085529E-01,3.412026E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.329473E-01,5.521802E-03,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.401900E-01,5.090345E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1776kW_8_00COP_Vanes
ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes, !- Name 1775900, !- Reference Capacity {W} 8.00, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04757, !- Reference Chilled Water Flow Rate {m3/s} 0.07003, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1776kW/8.00COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.17, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.17, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.17 | Minimum part unload ratio |
Real | PLRMin | 0.17 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1775900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.00 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07003 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.841535E-01,-3.584260E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.006719E-01,-3.137026E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.276235E-01,2.787167E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XL_1779kW_6_18COP_Vanes
ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes, !- Name 1779400, !- Reference Capacity {W} 6.18, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.06303, !- Reference Chilled Water Flow Rate {m3/s} 0.08858, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1779kW/6.18COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1779400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.18 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.08858 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.703515E-01,-4.051337E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.872331E-01,-3.907248E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.090532E-01,2.641442E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.11 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_1779kW_6_18COP_Vanes
ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes, !- Name 1779400, !- Reference Capacity {W} 6.18, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.04454, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 1779kW/6.18COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1779400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.18 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04454 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.331346E-01,-5.678656E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.137523E-01,-1.879556E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.699409E-01,1.874304E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1794kW_8_11COP_Vanes
ElectricEIRChiller York YT 1794kW/8.11COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1794kW/8.11COP/Vanes, !- Name 1793500, !- Reference Capacity {W} 8.11, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05148, !- Reference Chilled Water Flow Rate {m3/s} 0.09653, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1794kW/8.11COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1794kW/8.11COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1794kW/8.11COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.08, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.08 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1793500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.11 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05148 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09653 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.536140E+00,-1.630760E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.546274E-01,2.456473E-01,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.187543E-02,8.272483E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1794kW_7_90COP_VSD
ElectricEIRChiller York YT 1794kW/7.90COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1794kW/7.90COP/VSD, !- Name 1793500, !- Reference Capacity {W} 7.90, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05148, !- Reference Chilled Water Flow Rate {m3/s} 0.09653, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1794kW/7.90COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1794kW/7.90COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1794kW/7.90COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1793500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.90 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05148 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09653 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.552268E-01,-1.553435E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.984829E-01,-1.552700E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.445880E-01,1.059293E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XL_1797kW_5_69COP_Vanes
ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes, !- Name 1797000, !- Reference Capacity {W} 5.69, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.07737, !- Reference Chilled Water Flow Rate {m3/s} 0.09672, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1797kW/5.69COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.39, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.39, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.39 | Minimum part unload ratio |
Real | PLRMin | 0.39 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1797000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.69 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07737 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09672 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.084596E-01,4.671596E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.084290E+00,-4.318103E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.926251E-01,-2.657314E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 21.11 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_1801kW_6_34COP_VSD
ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD, !- Name 1800500, !- Reference Capacity {W} 6.34, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05161, !- Reference Chilled Water Flow Rate {m3/s} 0.06385, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 1801kW/6.34COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1800500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05161 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06385 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.174861E-01,-7.299051E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.931082E-01,-1.885558E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.040764E-01,2.818752E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1867kW_10_09COP_Vanes
ElectricEIRChiller York YT 1867kW/10.09COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1867kW/10.09COP/Vanes, !- Name 1867300, !- Reference Capacity {W} 10.09, !- Reference COP {W/W} 7.78, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1867kW/10.09COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1867kW/10.09COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1867kW/10.09COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1867300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 10.09 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.451516E-01,-1.252382E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.668391E-01,1.506485E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.157002E-01,2.251016E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XL_1871kW_6_49COP_Vanes
ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes, !- Name 1870800, !- Reference Capacity {W} 6.49, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.06303, !- Reference Chilled Water Flow Rate {m3/s} 0.0877, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 1871kW/6.49COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1870800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.49 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06303 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0877 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.658630E-03,-3.836575E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.029608E+00,-7.149045E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.984908E-01,2.906868E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1881kW_6_77COP_VSD
ElectricEIRChiller York YT 1881kW/6.77COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1881kW/6.77COP/VSD, !- Name 1881400, !- Reference Capacity {W} 6.77, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1881kW/6.77COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1881kW/6.77COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1881kW/6.77COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1881400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.065247E-01,-4.158206E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.175311E-01,-3.913241E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.087656E-02,4.842164E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_1881kW_6_53COP_Vanes
ElectricEIRChiller York YK 1881kW/6.53COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 1881kW/6.53COP/Vanes, !- Name 1881400, !- Reference Capacity {W} 6.53, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.04397, !- Reference Chilled Water Flow Rate {m3/s} 0.1041, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 1881kW/6.53COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 1881kW/6.53COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 1881kW/6.53COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1881400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.53 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04397 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.1041 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.561286E-01,4.130164E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.434989E-01,4.361264E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.272116E-02,4.176382E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 9.44 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_1895kW_6_42COP_Vanes
ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes, !- Name 1895400, !- Reference Capacity {W} 6.42, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1895kW/6.42COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.09, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.09 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1895400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.42 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.573195E-01,-1.131937E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.915073E-01,-4.399727E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.592598E-01,1.425462E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_1934kW_7_55COP_Vanes
ElectricEIRChiller York YT 1934kW/7.55COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 1934kW/7.55COP/Vanes, !- Name 1934100, !- Reference Capacity {W} 7.55, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 13.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05552, !- Reference Chilled Water Flow Rate {m3/s} 0.08675, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 1934kW/7.55COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 1934kW/7.55COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 1934kW/7.55COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1934100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.55 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.08675 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 13.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.420318E-02,1.103599E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.173674E+00,-1.301647E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.706237E-01,6.063362E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PEH_1934kW_6_01COP_Vanes
ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes, !- Name 1934100, !- Reference Capacity {W} 6.01, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.05552, !- Reference Chilled Water Flow Rate {m3/s} 0.07981, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PEH 1934kW/6.01COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.08, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.08 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1934100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.01 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07981 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.893111E-01,-3.834949E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.885371E-01,-5.877829E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.849256E-01,-2.369152E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_WDC_1973kW_6_28COP_Vanes
ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes, !- Name 1972800, !- Reference Capacity {W} 6.28, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.04145, !- Reference Chilled Water Flow Rate {m3/s} 0.09337, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay WDC 1973kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1972800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04145 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09337 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.110884E+00,7.376077E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.097378E+00,-3.018324E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.282891E-01,2.722981E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_1997kW_7_24COP_Vanes
ElectricEIRChiller York YK 1997kW/7.24COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 1997kW/7.24COP/Vanes, !- Name 1997400, !- Reference Capacity {W} 7.24, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.04397, !- Reference Chilled Water Flow Rate {m3/s} 0.1041, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 1997kW/7.24COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 1997kW/7.24COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 1997kW/7.24COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.18, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.18, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.18 | Minimum part unload ratio |
Real | PLRMin | 0.18 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1997400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.24 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04397 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.1041 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.058272E-01,1.309175E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.188194E-01,8.769791E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.359332E-02,5.873752E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 7.22 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_2043kW_8_44COP_Vanes
ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes, !- Name 2043100, !- Reference Capacity {W} 8.44, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.04757, !- Reference Chilled Water Flow Rate {m3/s} 0.06814, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 2043kW/8.44COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.08, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.08, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.08 | Minimum part unload ratio |
Real | PLRMin | 0.08 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2043100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.44 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04757 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.06814 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.383569E-01,4.716323E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.891693E-01,1.168677E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.225600E-01,3.070007E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_2043kW_9_08COP_Vanes
ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes, !- Name 2043100, !- Reference Capacity {W} 9.08, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 18.33, !- Reference Entering Condenser Fluid Temperature {C} 0.09085, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2043kW/9.08COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.28, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.28, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.28 | Minimum part unload ratio |
Real | PLRMin | 0.28 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2043100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.08 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 18.33 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.340241E+00,7.634284E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.065177E-01,1.178669E-02,2... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.173752E-01,4.394720E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XL_2057kW_6_05COP_Vanes
ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes, !- Name 2057200, !- Reference Capacity {W} 6.05, !- Reference COP {W/W} 7.78, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.08322, !- Reference Chilled Water Flow Rate {m3/s} 0.09722, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XL 2057kW/6.05COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.28, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.28, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.28 | Minimum part unload ratio |
Real | PLRMin | 0.28 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2057200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.08322 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09722 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.737452E-01,-1.249478E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.623086E-01,-5.844490E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.041274E-01,-3.861525E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_2110kW_7_15COP_Vanes
ElectricEIRChiller York YT 2110kW/7.15COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 2110kW/7.15COP/Vanes, !- Name 2110000, !- Reference Capacity {W} 7.15, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06057, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 2110kW/7.15COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 2110kW/7.15COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 2110kW/7.15COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2110000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.15 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06057 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.359238E-01,1.785857E-02,1... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.270855E-01,-4.119654E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.469187E-01,1.862690E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_2124kW_6_03COP_Vanes
ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes, !- Name 2124000, !- Reference Capacity {W} 6.03, !- Reference COP {W/W} 8.89, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.05552, !- Reference Chilled Water Flow Rate {m3/s} 0.07981, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 2124kW/6.03COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2124000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.03 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05552 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07981 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.89 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.040134E+00,-1.745650E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {1.157799E+00,-3.621524E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.051419E-01,2.033679E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2159kW_6_85COP_Vanes
ElectricEIRChiller York YK 2159kW/6.85COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 2159kW/6.85COP/Vanes, !- Name 2159200, !- Reference Capacity {W} 6.85, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 2159kW/6.85COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 2159kW/6.85COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 2159kW/6.85COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2159200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.85 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.322235E-01,1.553954E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.106730E-01,-3.786410E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.595694E-01,1.889684E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_2184kW_6_78COP_Vanes
ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes, !- Name 2183800, !- Reference Capacity {W} 6.78, !- Reference COP {W/W} 7.78, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.04883, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2184kW/6.78COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2183800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.78 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04883 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.78 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.235680E+00,2.213527E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.877947E-01,-1.334886E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.942647E-02,5.249540E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2201kW_6_69COP_Vanes
ElectricEIRChiller York YK 2201kW/6.69COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 2201kW/6.69COP/Vanes, !- Name 2201400, !- Reference Capacity {W} 6.69, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 2201kW/6.69COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 2201kW/6.69COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 2201kW/6.69COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2201400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.69 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.474968E-01,-4.800356E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.234137E-01,1.308264E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.653493E-01,1.444620E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_2233kW_9_54COP_VSD
ElectricEIRChiller York YT 2233kW/9.54COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 2233kW/9.54COP/VSD, !- Name 2233000, !- Reference Capacity {W} 9.54, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.06107, !- Reference Chilled Water Flow Rate {m3/s} 0.11451, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 2233kW/9.54COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 2233kW/9.54COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 2233kW/9.54COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2233000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.54 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06107 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11451 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.585741E-01,-5.127829E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.563409E-01,-1.966623E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {6.917141E-02,1.743339E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2237kW_6_41COP_Vanes
ElectricEIRChiller York YK 2237kW/6.41COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 2237kW/6.41COP/Vanes, !- Name 2236600, !- Reference Capacity {W} 6.41, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 2237kW/6.41COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 2237kW/6.41COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 2237kW/6.41COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.13, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.13, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.13 | Minimum part unload ratio |
Real | PLRMin | 0.13 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2236600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.41 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.899710E-01,-1.413334E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.567950E-01,3.354557E-03,1... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.605354E-01,2.125571E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2275kW_6_32COP_Vanes
ElectricEIRChiller York YK 2275kW/6.32COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 2275kW/6.32COP/Vanes, !- Name 2275200, !- Reference Capacity {W} 6.32, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 2275kW/6.32COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 2275kW/6.32COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 2275kW/6.32COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.13, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.13, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.13 | Minimum part unload ratio |
Real | PLRMin | 0.13 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2275200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.32 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.034673E+00,-1.091064E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.326094E-01,-6.056615E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.735485E-01,2.163041E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_2300kW_8_10COP_Vanes
ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes, !- Name 2299900, !- Reference Capacity {W} 8.10, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09085, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2300kW/8.10COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.23, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.23, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.23 | Minimum part unload ratio |
Real | PLRMin | 0.23 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2299900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 8.10 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09085 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.268137E-01,3.920902E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.178121E-01,6.561784E-03,8... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.161399E-01,4.347344E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_2317kW_6_33COP_VSD
ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD, !- Name 2317400, !- Reference Capacity {W} 6.33, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.09085, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2317kW/6.33COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2317400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.33 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.277716E-01,1.018101E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {3.502330E-01,-2.301510E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.861441E-02,5.297727E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_2391kW_6_77COP_Vanes
ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes, !- Name 2391300, !- Reference Capacity {W} 6.77, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06858, !- Reference Chilled Water Flow Rate {m3/s} 0.0846, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 2391kW/6.77COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2391300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06858 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0846 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.676388E-01,-5.087680E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.266646E-01,-2.367443E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.036386E-01,2.524850E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19XR_2391kW_6_44COP_VSD
ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD, !- Name 2391300, !- Reference Capacity {W} 6.44, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06858, !- Reference Chilled Water Flow Rate {m3/s} 0.0846, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19XR 2391kW/6.44COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2391300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.44 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06858 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0846 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.676388E-01,-5.087680E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.230142E-01,-2.371649E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.774812E-02,2.490111E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2412kW_5_58COP_Vanes
ElectricEIRChiller York YK 2412kW/5.58COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 2412kW/5.58COP/Vanes, !- Name 2412400, !- Reference Capacity {W} 5.58, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.09085, !- Reference Chilled Water Flow Rate {m3/s} 0.11356, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 2412kW/5.58COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 2412kW/5.58COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 2412kW/5.58COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.12, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.12, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.12 | Minimum part unload ratio |
Real | PLRMin | 0.12 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2412400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.58 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.11356 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.473817E-01,8.069214E-03,8... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.626807E-01,-2.305674E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.472427E-01,7.531481E-01,8... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_2462kW_6_67COP_Vanes
ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes, !- Name 2461600, !- Reference Capacity {W} 6.67, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.07066, !- Reference Chilled Water Flow Rate {m3/s} 0.10157, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 2462kW/6.67COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2461600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.67 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07066 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.10157 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.561527E-01,5.742999E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.462893E-01,2.854651E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {9.222135E-02,5.830980E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_2567kW_11_77COP_VSD
ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD, !- Name 2567100, !- Reference Capacity {W} 11.77, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.12113, !- Reference Chilled Water Flow Rate {m3/s} 0.15142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2567kW/11.77COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.11, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.11, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2567100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 11.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.12113 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.15142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.549428E-01,2.748161E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.561990E-01,-3.333063E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.039419E-01,4.184975E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_2771kW_6_84COP_VSD
ElectricEIRChiller York YK 2771kW/6.84COP/VSD
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 2771kW/6.84COP/VSD, !- Name 2771100, !- Reference Capacity {W} 6.84, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.10094, !- Reference Chilled Water Flow Rate {m3/s} 0.15142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 2771kW/6.84COP/VSD CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 2771kW/6.84COP/VSD EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 2771kW/6.84COP/VSD EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2771100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.84 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.10094 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.15142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.734286E-01,4.848829E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.203736E-01,1.030460E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {8.653354E-02,1.737382E-01,7... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_2799kW_6_40COP_Vanes
ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes, !- Name 2799200, !- Reference Capacity {W} 6.40, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.09893, !- Reference Chilled Water Flow Rate {m3/s} 0.13761, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 2799kW/6.40COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -2799200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.40 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09893 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.13761 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.210324E-01,-2.752320E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.267558E-01,-7.615857E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.023576E-01,-2.893592E-02,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YT_3133kW_9_16COP_Vanes
ElectricEIRChiller York YT 3133kW/9.16COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YT 3133kW/9.16COP/Vanes, !- Name 3133300, !- Reference Capacity {W} 9.16, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.08076, !- Reference Chilled Water Flow Rate {m3/s} 0.12618, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YT 3133kW/9.16COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YT 3133kW/9.16COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YT 3133kW/9.16COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.07, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.07, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.07 | Minimum part unload ratio |
Real | PLRMin | 0.07 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -3133300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.16 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.08076 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.12618 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.607419E-01,1.323998E-02,6... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.150153E-01,-3.956395E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.387579E-01,6.435208E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_3165kW_6_48COP_Vanes
ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes, !- Name 3165000, !- Reference Capacity {W} 6.48, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 22.78, !- Reference Entering Condenser Fluid Temperature {C} 0.09085, !- Reference Chilled Water Flow Rate {m3/s} 0.13627, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 3165kW/6.48COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -3165000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.48 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.09085 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.13627 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 22.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.342558E+00,7.520735E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.347904E-01,6.551597E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.054110E-01,4.090646E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_McQuay_PFH_4020kW_7_35COP_Vanes
ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes, !- Name 4019500, !- Reference Capacity {W} 7.35, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 12.78, !- Reference Entering Condenser Fluid Temperature {C} 0.07874, !- Reference Chilled Water Flow Rate {m3/s} 0.09842, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller McQuay PFH 4020kW/7.35COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4019500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.35 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07874 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09842 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 12.78 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.958422E-01,3.762768E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.322623E-01,-2.157964E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {5.763566E-02,5.964012E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4396kW_6_63COP_Vanes
ElectricEIRChiller York YK 4396kW/6.63COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 4396kW/6.63COP/Vanes, !- Name 4395800, !- Reference Capacity {W} 6.63, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4396kW/6.63COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4396kW/6.63COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4396kW/6.63COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.41, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.41, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4395800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.63 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.693621E-01,-7.284715E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.913358E-01,-5.974145E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.021070E-01,3.103971E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4477kW_6_64COP_Vanes
ElectricEIRChiller York YK 4477kW/6.64COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 4477kW/6.64COP/Vanes, !- Name 4476700, !- Reference Capacity {W} 6.64, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4477kW/6.64COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4477kW/6.64COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4477kW/6.64COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.41, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.41, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4476700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.64 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.844230E-01,-9.879643E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.264570E-01,-3.391606E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.767206E-01,1.074393E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4515kW_6_22COP_Vanes
ElectricEIRChiller York YK 4515kW/6.22COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 4515kW/6.22COP/Vanes, !- Name 4515400, !- Reference Capacity {W} 6.22, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4515kW/6.22COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4515kW/6.22COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4515kW/6.22COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4515400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.22 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.732405E-01,-7.176618E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.908290E-01,1.028668E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.870815E-01,3.951784E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4537kW_6_28COP_Vanes
ElectricEIRChiller York YK 4537kW/6.28COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 4537kW/6.28COP/Vanes, !- Name 4536500, !- Reference Capacity {W} 6.28, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4537kW/6.28COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4537kW/6.28COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4537kW/6.28COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4536500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.28 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.418253E-01,8.142292E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.709829E-01,-2.257680E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.528426E-01,2.920280E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_4610kW_6_34COP_Vanes
ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes, !- Name 4610300, !- Reference Capacity {W} 6.34, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.19129, !- Reference Chilled Water Flow Rate {m3/s} 0.24757, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 4610kW/6.34COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4610300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19129 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24757 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.614836E-01,-3.988130E-03,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.415078E-01,-4.779029E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.026691E-01,2.922585E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19EX_4667kW_6_16COP_Vanes
ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes, !- Name 4666600, !- Reference Capacity {W} 6.16, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 4667kW/6.16COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4666600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.16 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {4.084496E-01,-4.396326E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.214788E-01,-8.218594E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.771252E-01,2.854188E-02,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CVHF_4677kW_6_27COP_Vanes
ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes, !- Name 4677100, !- Reference Capacity {W} 6.27, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.20138, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CVHF 4677kW/6.27COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.41, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.41, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.41 | Minimum part unload ratio |
Real | PLRMin | 0.41 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4677100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.27 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.20138 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.449416E-01,-2.116553E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.283132E-01,-3.030491E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.531562E-01,-2.126229E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4966kW_6_05COP_Vanes
ElectricEIRChiller York YK 4966kW/6.05COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 4966kW/6.05COP/Vanes, !- Name 4965500, !- Reference Capacity {W} 6.05, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.21198, !- Reference Chilled Water Flow Rate {m3/s} 0.26498, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4966kW/6.05COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4966kW/6.05COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4966kW/6.05COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.12, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.12, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.12 | Minimum part unload ratio |
Real | PLRMin | 0.12 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4965500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.21198 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.746486E-01,-3.051134E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {8.229769E-01,-8.128614E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.416463E-01,1.947185E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4969kW_7_14COP_Vanes
ElectricEIRChiller York YK 4969kW/7.14COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 4969kW/7.14COP/Vanes, !- Name 4969000, !- Reference Capacity {W} 7.14, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.17665, !- Reference Chilled Water Flow Rate {m3/s} 0.26498, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4969kW/7.14COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4969kW/7.14COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4969kW/7.14COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.16, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.16, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.16 | Minimum part unload ratio |
Real | PLRMin | 0.16 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4969000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.14 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.817577E-01,-1.012013E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.382162E-01,-5.847442E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.259512E-01,2.320151E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_4969kW_7_07COP_Vanes
ElectricEIRChiller York YK 4969kW/7.07COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 4969kW/7.07COP/Vanes, !- Name 4969000, !- Reference Capacity {W} 7.07, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.17665, !- Reference Chilled Water Flow Rate {m3/s} 0.26498, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 4969kW/7.07COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 4969kW/7.07COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 4969kW/7.07COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.16, !- Minimum Part Load Ratio 1.06, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.16, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.06 | Maximum part load ratio |
Real | PLRMinUnl | 0.16 | Minimum part unload ratio |
Real | PLRMin | 0.16 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4969000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.07 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.803605E-01,-9.685535E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.220087E-01,-4.480691E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.308102E-01,1.802734E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19EX_4997kW_6_40COP_Vanes
ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes, !- Name 4997200, !- Reference Capacity {W} 6.40, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.67, !- Reference Entering Condenser Fluid Temperature {C} 0.19558, !- Reference Chilled Water Flow Rate {m3/s} 0.24605, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 4997kW/6.40COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -4997200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.40 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.19558 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.24605 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.67 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {7.122762E-02,2.550937E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.685097E-01,-2.541433E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.364887E-01,2.122607E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.67 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19EX_5148kW_6_34COP_Vanes
ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes, !- Name 5148400, !- Reference Capacity {W} 6.34, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.18283, !- Reference Chilled Water Flow Rate {m3/s} 0.25526, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 5148kW/6.34COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5148400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.34 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18283 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.25526 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {3.564454E-01,2.020689E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.426449E-01,3.961314E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.883602E-01,5.018646E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_5170kW_7_15COP_Vanes
ElectricEIRChiller York YK 5170kW/7.15COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 5170kW/7.15COP/Vanes, !- Name 5169500, !- Reference Capacity {W} 7.15, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.17665, !- Reference Chilled Water Flow Rate {m3/s} 0.26498, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 5170kW/7.15COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 5170kW/7.15COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 5170kW/7.15COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.15, !- Minimum Part Load Ratio 1.08, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.15, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.08 | Maximum part load ratio |
Real | PLRMinUnl | 0.15 | Minimum part unload ratio |
Real | PLRMin | 0.15 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5169500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.15 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.17665 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.26498 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.675697E-01,-1.191228E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.894383E-01,-2.926530E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.497273E-01,1.011288E-01,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19EX_5208kW_6_88COP_Vanes
ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes, !- Name 5208200, !- Reference Capacity {W} 6.88, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.18283, !- Reference Chilled Water Flow Rate {m3/s} 0.25293, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19EX 5208kW/6.88COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5208200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.88 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18283 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.25293 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.563516E-01,-4.106264E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.198204E-01,-1.523340E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.334262E-01,3.926783E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_5465kW_6_94COP_Vanes
ElectricEIRChiller York YK 5465kW/6.94COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 5465kW/6.94COP/Vanes, !- Name 5464900, !- Reference Capacity {W} 6.94, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.18296, !- Reference Chilled Water Flow Rate {m3/s} 0.27444, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 5465kW/6.94COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 5465kW/6.94COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 5465kW/6.94COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.07, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.07 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5464900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.94 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18296 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.27444 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.092441E-01,-1.225892E-01,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.396022E-01,-5.954060E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.795792E-01,7.872758E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YK_5549kW_6_50COP_Vanes
ElectricEIRChiller York YK 5549kW/6.50COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YK 5549kW/6.50COP/Vanes, !- Name 5549300, !- Reference Capacity {W} 6.50, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.18296, !- Reference Chilled Water Flow Rate {m3/s} 0.27444, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YK 5549kW/6.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YK 5549kW/6.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YK 5549kW/6.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.14, !- Minimum Part Load Ratio 1.05, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.14, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.05 | Maximum part load ratio |
Real | PLRMinUnl | 0.14 | Minimum part unload ratio |
Real | PLRMin | 0.14 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5549300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18296 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.27444 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-1.402079E-01,1.836029E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.989980E-01,-8.246157E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.336623E-01,1.901320E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 26.11 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_19FA_5651kW_5_50COP_Vanes
ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes, !- Name 5651300, !- Reference Capacity {W} 5.50, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.18927, !- Reference Chilled Water Flow Rate {m3/s} 0.18927, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 19FA 5651kW/5.50COP/Vanes EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.19, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.19, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.19 | Minimum part unload ratio |
Real | PLRMin | 0.19 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -5651300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.18927 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.18927 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.299676E+00,1.790645E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.853207E-01,-1.652255E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.629327E-01,5.709336E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.DOE_2_Centrifugal_5_50COP
DOE-2 Centrifugal/5.50COP
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, DOE-2 Centrifugal/5.50COP, !- Name Autosize, !- Reference Capacity {W} 5.5, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.4, !- Reference Entering Condenser Fluid Temperature {C} Autosize, !- Reference Chilled Water Flow Rate {m3/s} Autosize, !- Reference Condenser Water Flow Rate {m3/s} DOE-2 Centrifugal/5.50COP CAPFT, !- Cooling Capacity Function of Temperature Curve Name DOE-2 Centrifugal/5.50COP EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name DOE-2 Centrifugal/5.50COP EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.1, !- Minimum Part Load Ratio 1.0, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.2, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow; !- Chiller Flow Mode
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.0 | Maximum part load ratio |
Real | PLRMinUnl | 0.2 | Minimum part unload ratio |
Real | PLRMin | 0.1 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -100000.0 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.5 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0022 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0041 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.4 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {0.257896E+00,0.389016E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {0.933884E+00,-0.582120E-01,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {0.222903,0.313387,0.463710} | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.0 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.0 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 24.0 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.0 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Multistack_MS_172kW_3_67COP_None
ElectricEIRChiller Multistack MS 172kW/3.67COP/None
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Multistack MS 172kW/3.67COP/None, !- Name 172300, !- Reference Capacity {W} 3.67, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 18.33, !- Reference Entering Condenser Fluid Temperature {C} 0.00738, !- Reference Chilled Water Flow Rate {m3/s} 0.00959, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Multistack MS 172kW/3.67COP/None CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Multistack MS 172kW/3.67COP/None EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Multistack MS 172kW/3.67COP/None EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.40, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.40, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.40 | Minimum part unload ratio |
Real | PLRMin | 0.40 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -172300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 3.67 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.00738 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.00959 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 18.33 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.839419E-01,1.094957E-01,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.396181E-01,-5.754225E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.747786E-03,1.072374E+00,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 18.33 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.DOE_2_Reciprocating_3_67COP
DOE-2 Reciprocating/3.67COP
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, DOE-2 Reciprocating/3.67COP, !- Name Autosize, !- Reference Capacity {W} 3.67, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.4, !- Reference Entering Condenser Fluid Temperature {C} Autosize, !- Reference Chilled Water Flow Rate {m3/s} Autosize, !- Reference Condenser Water Flow Rate {m3/s} DOE-2 Reciprocating/3.67COP CAPFT, !- Cooling Capacity Function of Temperature Curve Name DOE-2 Reciprocating/3.67COP EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name DOE-2 Reciprocating/3.67COP EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.1, !- Minimum Part Load Ratio 1.0, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.2, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow; !- Chiller Flow Mode
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.0 | Maximum part load ratio |
Real | PLRMinUnl | 0.2 | Minimum part unload ratio |
Real | PLRMin | 0.1 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -100000.0 | Reference capacity (negative number) [W] |
Real | COP_nominal | 3.67 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0022 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0044 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.4 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {0.507883E+00,0.145228E+00,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {0.103076E+01,-0.103536E+00,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {0.088065,1.137742,-0.225806} | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.0 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.0 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 24.0 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.0 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTWA_383kW_4_17COP_Valve
ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve, !- Name 383300, !- Reference Capacity {W} 4.17, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.0165, !- Reference Chilled Water Flow Rate {m3/s} 0.02063, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTWA 383kW/4.17COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.25, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.25, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.25 | Minimum part unload ratio |
Real | PLRMin | 0.25 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -383300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.17 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0165 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.02063 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.830684E-01,3.676199E-02,5... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.228513E-01,-8.700783E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.295553E-02,9.114398E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHB_531kW_4_83COP_Valve
ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve, !- Name 531000, !- Reference Capacity {W} 4.83, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.0135, !- Reference Chilled Water Flow Rate {m3/s} 0.01577, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 531kW/4.83COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -531000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 4.83 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0135 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01577 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.434012E-01,1.630729E-02,8... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.524778E-01,1.045156E-04,6... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.980020E-01,2.733157E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHB_538kW_5_12COP_Valve
ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve, !- Name 538000, !- Reference Capacity {W} 5.12, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.01375, !- Reference Chilled Water Flow Rate {m3/s} 0.01956, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 538kW/5.12COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -538000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.12 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01375 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01956 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.344780E-01,2.760000E-02,3... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.455087E-01,-9.301201E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.816950E-01,3.731838E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHB_542kW_5_26COP_Valve
ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve, !- Name 541500, !- Reference Capacity {W} 5.26, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 21.11, !- Reference Entering Condenser Fluid Temperature {C} 0.01363, !- Reference Chilled Water Flow Rate {m3/s} 0.01577, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 542kW/5.26COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -541500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.26 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01363 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01577 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 21.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.226438E-01,2.878831E-02,3... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.953775E-01,-1.359340E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.057645E-01,-1.548084E-01,... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_672kW_7_90COP_Valve
ElectricEIRChiller York YS 672kW/7.90COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YS 672kW/7.90COP/Valve, !- Name 671600, !- Reference Capacity {W} 7.90, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 15.56, !- Reference Entering Condenser Fluid Temperature {C} 0.01514, !- Reference Chilled Water Flow Rate {m3/s} 0.0241, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 672kW/7.90COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 672kW/7.90COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 672kW/7.90COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -671600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.90 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01514 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.0241 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.274375E-01,2.846559E-02,4... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.069331E-01,-6.420922E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.936152E-01,3.375574E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_686kW_5_91COP_Valve
ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve, !- Name 685700, !- Reference Capacity {W} 5.91, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 23.74, !- Reference Entering Condenser Fluid Temperature {C} 0.0571, !- Reference Chilled Water Flow Rate {m3/s} 0.03255, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 686kW/5.91COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -685700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.91 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03255 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.74 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {2.903523E-01,-2.676742E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.014060E-01,1.561000E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.113934E-01,4.190226E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHC_707kW_7_77COP_Valve
ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve, !- Name 706800, !- Reference Capacity {W} 7.77, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 15.56, !- Reference Entering Condenser Fluid Temperature {C} 0.04921, !- Reference Chilled Water Flow Rate {m3/s} 0.03268, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 707kW/7.77COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.28, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.28, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.28 | Minimum part unload ratio |
Real | PLRMin | 0.28 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -706800 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.77 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04921 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03268 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.362925E-01,2.940722E-02,5... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.497944E-01,6.883157E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.997099E-01,6.754676E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 11.11 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_756kW_7_41COP_Valve
ElectricEIRChiller York YS 756kW/7.41COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YS 756kW/7.41COP/Valve, !- Name 756000, !- Reference Capacity {W} 7.41, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 16.06, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 756kW/7.41COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 756kW/7.41COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 756kW/7.41COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.11, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.11, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.11 | Minimum part unload ratio |
Real | PLRMin | 0.11 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -756000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 7.41 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 16.06 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.432455E-01,2.794778E-02,2... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.917947E-01,-1.929936E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.929778E-01,1.673799E-02,6... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 16.06 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_781kW_5_42COP_Valve
ElectricEIRChiller York YS 781kW/5.42COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YS 781kW/5.42COP/Valve, !- Name 780700, !- Reference Capacity {W} 5.42, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.01893, !- Reference Chilled Water Flow Rate {m3/s} 0.03785, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 781kW/5.42COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 781kW/5.42COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 781kW/5.42COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -780700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.42 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.01893 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.03785 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.002148E+00,3.300191E-02,3... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.475957E-01,-1.054652E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.519108E-01,2.756914E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_830kW_6_97COP_Valve
ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve, !- Name 829900, !- Reference Capacity {W} 6.97, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.04744, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 830kW/6.97COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -829900 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.97 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04744 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.198506E-01,4.299516E-03,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.610959E-01,-1.560459E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.307464E-01,7.784162E-01,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 14.17 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_862kW_6_11COP_Valve
ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve, !- Name 861500, !- Reference Capacity {W} 6.11, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.04296, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 862kW/6.11COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -861500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.11 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04296 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-3.646458E-02,-6.061334E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.420642E-01,-2.110032E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.292819E-01,3.662723E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_862kW_6_84COP_Valve
ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve, !- Name 861500, !- Reference Capacity {W} 6.84, !- Reference COP {W/W} 9.69, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.06782, !- Reference Chilled Water Flow Rate {m3/s} 0.04296, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 862kW/6.84COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -861500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.84 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.06782 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04296 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 9.69 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-4.535842E-02,-6.253871E-02... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.930611E-01,-2.082914E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.145826E-01,7.340475E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_865kW_6_05COP_Valve
ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve, !- Name 865100, !- Reference Capacity {W} 6.05, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.03716, !- Reference Chilled Water Flow Rate {m3/s} 0.04366, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 865kW/6.05COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -865100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03716 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04366 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.079758E-01,-2.344768E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.437328E-01,7.625344E-03,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.545235E-01,3.104981E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_879kW_5_82COP_Valve
ElectricEIRChiller York YS 879kW/5.82COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YS 879kW/5.82COP/Valve, !- Name 879100, !- Reference Capacity {W} 5.82, !- Reference COP {W/W} 4.44, !- Reference Leaving Chilled Water Temperature {C} 26.11, !- Reference Entering Condenser Fluid Temperature {C} 0.03785, !- Reference Chilled Water Flow Rate {m3/s} 0.04732, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 879kW/5.82COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 879kW/5.82COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 879kW/5.82COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -879100 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.82 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03785 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04732 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 4.44 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 26.11 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.031429E+00,3.364723E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.595308E-01,-1.087985E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.029493E-01,3.223124E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 3.33 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 7.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHC_1009kW_5_37COP_Valve
ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve, !- Name 1009200, !- Reference Capacity {W} 5.37, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 24.86, !- Reference Entering Condenser Fluid Temperature {C} 0.03186, !- Reference Chilled Water Flow Rate {m3/s} 0.04618, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 1009kW/5.37COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1009200 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.37 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03186 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04618 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 24.86 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.134633E+00,3.267210E-02,5... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.383883E-01,7.754235E-03,6... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.316727E-01,1.013111E+00,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 19.97 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 24.86 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHB_1051kW_5_05COP_Valve
ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve, !- Name 1051400, !- Reference Capacity {W} 5.05, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.04527, !- Reference Chilled Water Flow Rate {m3/s} 0.05659, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHB 1051kW/5.05COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1051400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.05 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04527 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05659 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.482157E-01,3.306737E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {4.904181E-01,-5.530317E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.590465E-01,2.148987E-01,5... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_1062kW_5_50COP_Valve
ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve, !- Name 1062000, !- Reference Capacity {W} 5.50, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.04573, !- Reference Chilled Water Flow Rate {m3/s} 0.05716, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 1062kW/5.50COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1062000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.50 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04573 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05716 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.025695E+00,2.327484E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {2.634070E-01,-7.025220E-03,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {2.576261E-01,3.416910E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 21.11 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 29.44 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHC_1066kW_5_73COP_Valve
ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve, !- Name 1065500, !- Reference Capacity {W} 5.73, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 25.28, !- Reference Entering Condenser Fluid Temperature {C} 0.05142, !- Reference Chilled Water Flow Rate {m3/s} 0.04416, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 1066kW/5.73COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.30, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.30, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.30 | Minimum part unload ratio |
Real | PLRMin | 0.30 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1065500 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.73 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.05142 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04416 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 25.28 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.062396E+00,4.575299E-02,2... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {9.003080E-01,3.783201E-03,9... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.007344E-01,1.119205E+00,-... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 20.07 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 25.28 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_RTHC_1094kW_6_55COP_Valve
ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve, !- Name 1093600, !- Reference Capacity {W} 6.55, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 23.33, !- Reference Entering Condenser Fluid Temperature {C} 0.04921, !- Reference Chilled Water Flow Rate {m3/s} 0.04524, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane RTHC 1094kW/6.55COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.25, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.25, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.25 | Minimum part unload ratio |
Real | PLRMin | 0.25 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1093600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.55 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.04921 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04524 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.33 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.643756E-01,3.820069E-02,4... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.579136E-01,-1.133448E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.626466E-01,7.903550E-01,4... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_1108kW_6_92COP_Valve
ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve, !- Name 1107700, !- Reference Capacity {W} 6.92, !- Reference COP {W/W} 8.97, !- Reference Leaving Chilled Water Temperature {C} 23.74, !- Reference Entering Condenser Fluid Temperature {C} 0.0571, !- Reference Chilled Water Flow Rate {m3/s} 0.05142, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 1108kW/6.92COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1107700 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.92 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05142 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 8.97 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.74 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {6.631328E-01,-1.027433E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.668296E-01,-2.800906E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.370745E-01,8.374817E-01,2... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_1171kW_9_15COP_Valve
ElectricEIRChiller York YS 1171kW/9.15COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YS 1171kW/9.15COP/Valve, !- Name 1171000, !- Reference Capacity {W} 9.15, !- Reference COP {W/W} 6.11, !- Reference Leaving Chilled Water Temperature {C} 15.56, !- Reference Entering Condenser Fluid Temperature {C} 0.03249, !- Reference Chilled Water Flow Rate {m3/s} 0.05173, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 1171kW/9.15COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 1171kW/9.15COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 1171kW/9.15COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.09, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.09, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.09 | Minimum part unload ratio |
Real | PLRMin | 0.09 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1171000 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.15 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03249 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.05173 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.11 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.299045E-01,2.350383E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.325834E-01,-2.611733E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.889392E-01,4.684305E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.11 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.78 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Carrier_23XL_1196kW_6_39COP_Valve
ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve, !- Name 1195600, !- Reference Capacity {W} 6.39, !- Reference COP {W/W} 7.22, !- Reference Leaving Chilled Water Temperature {C} 23.89, !- Reference Entering Condenser Fluid Temperature {C} 0.03653, !- Reference Chilled Water Flow Rate {m3/s} 0.04271, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Carrier 23XL 1196kW/6.39COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.03, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.03 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1195600 | Reference capacity (negative number) [W] |
Real | COP_nominal | 6.39 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.03653 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.04271 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 7.22 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 23.89 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {5.775948E-01,2.206074E-02,-... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.077824E-01,-1.608447E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.061065E-01,7.305514E-01,1... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 6.67 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 12.22 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 23.89 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_1554kW_9_31COP_Valve
ElectricEIRChiller York YS 1554kW/9.31COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YS 1554kW/9.31COP/Valve, !- Name 1554300, !- Reference Capacity {W} 9.31, !- Reference COP {W/W} 5.56, !- Reference Leaving Chilled Water Temperature {C} 15.56, !- Reference Entering Condenser Fluid Temperature {C} 0.0424, !- Reference Chilled Water Flow Rate {m3/s} 0.07949, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 1554kW/9.31COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 1554kW/9.31COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 1554kW/9.31COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.02, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.02 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1554300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 9.31 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0424 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.07949 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 5.56 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 15.56 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {1.083027E+00,9.278069E-03,1... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {5.099117E-01,1.379553E-02,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {1.720219E-01,5.084848E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 15.56 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YS_1758kW_5_84COP_Valve
ElectricEIRChiller York YS 1758kW/5.84COP/Valve
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YS 1758kW/5.84COP/Valve, !- Name 1758300, !- Reference Capacity {W} 5.84, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.07571, !- Reference Chilled Water Flow Rate {m3/s} 0.09464, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller York YS 1758kW/5.84COP/Valve CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YS 1758kW/5.84COP/Valve EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YS 1758kW/5.84COP/Valve EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.20, !- Minimum Part Load Ratio 1.04, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.20, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.04 | Maximum part load ratio |
Real | PLRMinUnl | 0.20 | Minimum part unload ratio |
Real | PLRMin | 0.20 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -1758300 | Reference capacity (negative number) [W] |
Real | COP_nominal | 5.84 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.07571 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.09464 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {8.130185E-01,-1.425368E-02,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {6.381264E-01,6.304193E-03,9... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {3.149879E-01,3.171267E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 8.89 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 12.78 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_Trane_CGWD_207kW_3_99COP_None
ElectricEIRChiller Trane CGWD 207kW/3.99COP/None
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller Trane CGWD 207kW/3.99COP/None, !- Name 207400, !- Reference Capacity {W} 3.99, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 29.44, !- Reference Entering Condenser Fluid Temperature {C} 0.00898, !- Reference Chilled Water Flow Rate {m3/s} 0.01122, !- Reference Condenser Water Flow Rate {m3/s} ElectricEIRChiller Trane CGWD 207kW/3.99COP/None CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller Trane CGWD 207kW/3.99COP/None EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller Trane CGWD 207kW/3.99COP/None EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.25, !- Minimum Part Load Ratio 1.01, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.25, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name WaterCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Compressor Motor Efficiency 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.01 | Maximum part load ratio |
Real | PLRMinUnl | 0.25 | Minimum part unload ratio |
Real | PLRMin | 0.25 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -207400 | Reference capacity (negative number) [W] |
Real | COP_nominal | 3.99 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.00898 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1000*0.01122 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 29.44 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {9.441897E-01,3.371079E-02,9... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {7.273870E-01,-1.189276E-02,... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {4.146742E-02,6.543795E-01,3... | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 5.56 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.00 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |
Temperature | TConEntMax | 273.15 + 35.00 | Maximum value for entering condenser temperature [K] |
Modelica definition
Buildings.Fluid.Chillers.Data.ElectricEIR.ElectricEIRChiller_York_YCAL0033EE_101kW_3_1COP_AirCooled
ElectricEIRChiller York YCAL0033EE 100.6 kW/3.1 COP Air Cooled
Information
Performance data for chiller model. This data corresponds to the following EnergyPlus model:Chiller:Electric:EIR, ElectricEIRChiller York YCAL0033EE 100.6kW/3.1COP, !- Name 100582, !- Reference Capacity {W} 3.1, !- Reference COP {W/W} 6.67, !- Reference Leaving Chilled Water Temperature {C} 35, !- Reference Entering Condenser Fluid Temperature {C} 0.0043, !- Reference Chilled Water Flow Rate {m3/s} 0.0011, !- Reference Condenser Fluid Flow Rate {m3/s} ElectricEIRChiller York YCAL0033EE 100.6kW/3.1COP CAPFT, !- Cooling Capacity Function of Temperature Curve Name ElectricEIRChiller York YCAL0033EE 100.6kW/3.1COP EIRFT, !- Electric Input to Cooling Output Ratio Function of Temperature Curve Name ElectricEIRChiller York YCAL0033EE 100.6kW/3.1COP EIRFPLR, !- Electric Input to Cooling Output Ratio Function of Part Load Ratio Curve Name 0.10, !- Minimum Part Load Ratio 1.15, !- Maximum Part Load Ratio 1.0, !- Optimum Part Load Ratio 0.10, !- Minimum Unloading Ratio Chilled Water Side Inlet Node, !- Chilled Water Inlet Node Name Chilled Water Side Outlet Node, !- Chilled Water Outlet Node Name Condenser Side Inlet Node, !- Condenser Inlet Node Name Condenser Side Outlet Node, !- Condenser Outlet Node Name AirCooled, !- Condenser Type , !- Condenser Fan Power Ratio {W/W} 1.0, !- Fraction of Compressor Electric Consumption Rejected by Condenser 2.0, !- Leaving Chilled Water Lower Temperature Limit {C} ConstantFlow, !- Chiller Flow Mode 0.0; !- Design Heat Recovery Water Flow Rate {m3/s}
Note that the reference condenser fluid volumetric flow rate listed in the EnergyPlus performance data is not reasonable. The value obtained from the manufacturer data sheet is used instead. The data sheet is available here . Please see the Section for Physical Data and Nominal Ratings and row for Condender Fans Total Chiller CFM.
Extends from Buildings.Fluid.Chillers.Data.ElectricEIR.Generic (Generic data record for chiller ElectricEIR).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | PLRMax | 1.15 | Maximum part load ratio |
Real | PLRMinUnl | 0.10 | Minimum part unload ratio |
Real | PLRMin | 0.10 | Minimum part load ratio |
Real | etaMotor | 1.0 | Fraction of compressor motor heat entering refrigerant |
Nominal condition | |||
HeatFlowRate | QEva_flow_nominal | -100582 | Reference capacity (negative number) [W] |
Real | COP_nominal | 3.1 | Reference coefficient of performance |
MassFlowRate | mEva_flow_nominal | 1000*0.0043 | Nominal mass flow at evaporator [kg/s] |
MassFlowRate | mCon_flow_nominal | 1.2*9.4389 | Nominal mass flow at condenser [kg/s] |
Temperature | TEvaLvg_nominal | 273.15 + 6.67 | Temperature of fluid leaving evaporator at nominal condition [K] |
Temperature | TConEnt_nominal | 273.15 + 35 | Temperature of fluid entering condenser at nominal condition [K] |
Performance curves | |||
Real | capFunT[nCapFunT] | {-0.2660645697,0.0998714035,... | Biquadratic coefficients for capFunT |
Real | EIRFunT[nEIRFunT] | {0.1807017787,0.0271530312,-... | Biquadratic coefficients for EIRFunT |
Real | EIRFunPLR[nEIRFunPLR] | {0.0,1.0,0.0} | Coefficients for EIRFunPLR |
Temperature | TEvaLvgMin | 273.15 + 4.44 | Minimum value for leaving evaporator temperature [K] |
Temperature | TEvaLvgMax | 273.15 + 10.0 | Maximum value for leaving evaporator temperature [K] |
Temperature | TConEntMin | 273.15 + 23.89 | Minimum value for entering condenser temperature [K] |