Buildings.Experimental.DHC.Loads.Combined
Package with models for loads
Information
This package contains models of building loads that are used to build example models of DHC systems.
Extends from Modelica.Icons.VariantsPackage (Icon for package containing variants).
Package Content
Name | Description |
---|---|
BuildingTimeSeriesWithETS | Model of a building with loads provided as time series, connected to an ETS |
BaseClasses | Package with base classes that are used by multiple models |
Buildings.Experimental.DHC.Loads.Combined.BuildingTimeSeriesWithETS
Model of a building with loads provided as time series, connected to an ETS
Information
This model is composed of a heat pump based energy transfer station model Buildings.Experimental.DHC.EnergyTransferStations.Combined.HeatPumpHeatExchanger connected to a simplified building model where the space heating, cooling and hot water loads are provided as time series.
Extends from Buildings.Experimental.DHC.Loads.Combined.BaseClasses.PartialBuildingWithETS (Partial model with ETS model and partial building model).
Parameters
Type | Name | Default | Description |
---|---|---|---|
replaceable package MediumSer | Water | Service side medium | |
replaceable package MediumSerHea_a | Water | Service side medium at heating inlet | |
replaceable package MediumBui | Water | Building side medium | |
String | filNam | Library path of the file with thermal loads as time series | |
Configuration | |||
Integer | nPorts_heaWat | 1 | Number of heating water fluid ports |
Integer | nPorts_chiWat | 1 | Number of chilled water fluid ports |
Scaling | |||
Real | facMul | 1 | Multiplier factor |
ETS model parameters | |||
TemperatureDifference | dT_nominal | 4 | Water temperature drop/increase accross load and source-side HX (always positive) [K] |
Temperature | TChiWatSup_nominal | 18 + 273.15 | Chilled water supply temperature [K] |
Temperature | THeaWatSup_nominal | 38 + 273.15 | Heating water supply temperature [K] |
Pressure | dp_nominal | 50000 | Pressure difference at nominal flow rate (for each flow leg) [Pa] |
Real | COPHeaWat_nominal | 4.0 | COP of heat pump for heating water production [1] |
Real | COPHotWat_nominal | 2.3 | COP of heat pump for hot water production [1] |
Assumptions | |||
Boolean | allowFlowReversalSer | false | Set to true to allow flow reversal on service side |
Boolean | allowFlowReversalBui | false | Set to true to allow flow reversal on building side |
Connectors
Type | Name | Description |
---|---|---|
FluidPort_a | port_aSerAmb | Fluid connector for ambient water service supply line |
FluidPort_b | port_bSerAmb | Fluid connector for ambient water service return line |
FluidPort_a | port_aSerHea | Fluid connector for heating service supply line |
FluidPort_b | port_bSerHea | Fluid connector for heating service return line |
FluidPort_a | port_aSerCoo | Fluid connector for cooling service supply line |
FluidPort_b | port_bSerCoo | Fluid connector for cooling service return line |
Bus | weaBus | Weather data bus |
output RealOutput | QHea_flow | Total heating heat flow rate transferred to the loads (>=0) [W] |
output RealOutput | QCoo_flow | Total cooling heat flow rate transferred to the loads (<=0) [W] |
output RealOutput | PHea | Power drawn by heating system [W] |
output RealOutput | PCoo | Power drawn by cooling system [W] |
output RealOutput | PFan | Power drawn by fan motors [W] |
output RealOutput | PPum | Power drawn by pump motors [W] |
output RealOutput | QFue_flow[nFue] | Fuel energy input rate [W] |
input RealInput | TChiWatSupSet | Chilled water supply temperature set point [K] |
input RealInput | THeaWatSupMaxSet | Heating water supply temperature set point - Maximum value [K] |
input RealInput | THeaWatSupMinSet | Heating water supply temperature set point - Minimum value [K] |
output RealOutput | PPumETS | ETS pump power [W] |
input RealInput | THotWatSupSet | Service hot water supply temperature set point [K] |
input RealInput | TColWat | Cold water temperature [K] |
Modelica definition
model BuildingTimeSeriesWithETS
"Model of a building with loads provided as time series, connected to an ETS"
extends Buildings.Experimental.DHC.Loads.Combined.BaseClasses.PartialBuildingWithETS
(
redeclare Buildings.Experimental.DHC.Loads.BaseClasses.Examples.BaseClasses.BuildingTimeSeries
bui(
final filNam=filNam,
have_hotWat=true,
T_aHeaWat_nominal=ets.THeaWatSup_nominal,
T_bHeaWat_nominal=ets.THeaWatRet_nominal,
T_aChiWat_nominal=ets.TChiWatSup_nominal,
T_bChiWat_nominal=ets.TChiWatRet_nominal,
facMulHea=10*QHea_flow_nominal/(1.7E5),
facMulCoo=40*QCoo_flow_nominal/(-1.5E5)),
ets(
have_hotWat=true,
QChiWat_flow_nominal=QCoo_flow_nominal,
QHeaWat_flow_nominal=QHea_flow_nominal,
QHotWat_flow_nominal=QHot_flow_nominal));
parameter String filNam
"Library path of the file with thermal loads as time series";
final parameter Modelica.Units.SI.HeatFlowRate QCoo_flow_nominal(max=-
Modelica.Constants.eps) = bui.facMul*bui.QCoo_flow_nominal
"Space cooling design load (<=0)";
final parameter Modelica.Units.SI.HeatFlowRate QHea_flow_nominal(min=Modelica.Constants.eps)=
bui.facMul*bui.QHea_flow_nominal "Space heating design load (>=0)";
final parameter Modelica.Units.SI.HeatFlowRate QHot_flow_nominal(min=Modelica.Constants.eps)=
bui.facMul*Buildings.Experimental.DHC.Loads.BaseClasses.getPeakLoad(string=
"#Peak water heating load", filNam=Modelica.Utilities.Files.loadResource(
filNam)) "Hot water design load (>=0)";
Buildings.Controls.OBC.CDL.Interfaces.RealInput THotWatSupSet(
final unit="K",
displayUnit="degC")
"Service hot water supply temperature set point";
Buildings.Controls.OBC.CDL.Interfaces.RealInput TColWat(
final unit="K",
displayUnit="degC")
"Cold water temperature";
Buildings.Controls.OBC.CDL.Continuous.MultiplyByParameter loaHeaNor(k=1/
QHea_flow_nominal) "Normalized heating load";
Buildings.Controls.OBC.CDL.Continuous.GreaterThreshold enaHeaCoo[2](each t=1e-4)
"Threshold comparison to enable heating and cooling";
Modelica.Blocks.Sources.BooleanConstant enaSHW(
final k=true) if have_hotWat
"SHW production enable signal";
Buildings.Controls.OBC.CDL.Continuous.MultiplyByParameter loaCooNor(k=1/
QCoo_flow_nominal) "Normalized cooling load";
equation
connect(bui.QReqHotWat_flow, ets.loaSHW);
connect(THotWatSupSet, ets.THotWatSupSet);
connect(TColWat, ets.TColWat);
connect(enaHeaCoo[1].y, ets.uHea);
connect(enaHeaCoo[2].y, ets.uCoo);
connect(enaSHW.y, ets.uSHW);
connect(loaHeaNor.y, enaHeaCoo[1].u);
connect(loaCooNor.y, enaHeaCoo[2].u);
connect(bui.QReqHea_flow, loaHeaNor.u);
connect(bui.QReqCoo_flow, loaCooNor.u);
connect(loaHeaNor.y, resTHeaWatSup.u);
end BuildingTimeSeriesWithETS;