Buildings.ThermalZones.Detailed.BaseClasses

Package with base classes for Buildings.ThermalZones.Detailed

Information

This package contains base classes that are used to construct the models in Buildings.ThermalZones.Detailed.

Extends from Modelica.Icons.BasesPackage (Icon for packages containing base classes).

Package Content

Name Description
Buildings.ThermalZones.Detailed.BaseClasses.CFDAirHeatMassBalance CFDAirHeatMassBalance Heat and mass balance of the air based on computational fluid dynamics
Buildings.ThermalZones.Detailed.BaseClasses.CFDExchange CFDExchange Block that exchanges data with the CFD code
Buildings.ThermalZones.Detailed.BaseClasses.CFDFluidInterface CFDFluidInterface  
Buildings.ThermalZones.Detailed.BaseClasses.CFDSurfaceInterface CFDSurfaceInterface  
Buildings.ThermalZones.Detailed.BaseClasses.CFDThread CFDThread class used to handle CFD thread
Buildings.ThermalZones.Detailed.BaseClasses.ExteriorBoundaryConditions ExteriorBoundaryConditions Model for convection and radiation bounary condition of exterior constructions
Buildings.ThermalZones.Detailed.BaseClasses.ExteriorBoundaryConditionsWithWindow ExteriorBoundaryConditionsWithWindow Model for exterior boundary conditions for constructions with a window
Buildings.ThermalZones.Detailed.BaseClasses.HeatGain HeatGain Model to convert internal heat gain signals
Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationExchange InfraredRadiationExchange Infrared radiation heat exchange between the room facing surfaces
Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationGainDistribution InfraredRadiationGainDistribution Infrared radiative heat gain distribution between the room facing surfaces
Buildings.ThermalZones.Detailed.BaseClasses.MixedAirHeatMassBalance MixedAirHeatMassBalance Heat and mass balance of the air, assuming completely mixed air
Buildings.ThermalZones.Detailed.BaseClasses.PartialAirHeatMassBalance PartialAirHeatMassBalance Partial model for heat and mass balance of the air
Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterface PartialSurfaceInterface Partial model that is used for infrared radiation balance
Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterfaceRadiative PartialSurfaceInterfaceRadiative Partial model that is used for infrared radiation balance
Buildings.ThermalZones.Detailed.BaseClasses.RadiationAdapter RadiationAdapter Model to connect between signals and heat port for radiative gains of the room
Buildings.ThermalZones.Detailed.BaseClasses.RadiationTemperature RadiationTemperature Radiative temperature of the room
Buildings.ThermalZones.Detailed.BaseClasses.RoomHeatMassBalance RoomHeatMassBalance Base model for a room
Buildings.ThermalZones.Detailed.BaseClasses.SkyRadiationExchange SkyRadiationExchange Radiative heat exchange with the sky and the ambient
Buildings.ThermalZones.Detailed.BaseClasses.SolarRadiationExchange SolarRadiationExchange Solar radiation heat exchange between the room facing surfaces
Buildings.ThermalZones.Detailed.BaseClasses.cfdExchangeData cfdExchangeData Exchange data between CFD and Modelica
Buildings.ThermalZones.Detailed.BaseClasses.cfdStartCosimulation cfdStartCosimulation Start the coupled simulation with CFD
Buildings.ThermalZones.Detailed.BaseClasses.to_W to_W Add unit [W] to data
Buildings.ThermalZones.Detailed.BaseClasses.CFDSurfaceIdentifier CFDSurfaceIdentifier Data record to identify surfaces in the CFD code
Buildings.ThermalZones.Detailed.BaseClasses.ConstructionNumbers ConstructionNumbers Data records for construction data
Buildings.ThermalZones.Detailed.BaseClasses.ConstructionRecords ConstructionRecords Data records for construction data
Buildings.ThermalZones.Detailed.BaseClasses.OpaqueSurface OpaqueSurface Record for exterior constructions that have no window
Buildings.ThermalZones.Detailed.BaseClasses.Overhang Overhang Record for window overhang
Buildings.ThermalZones.Detailed.BaseClasses.ParameterConstruction ParameterConstruction Record for exterior constructions that have no window
Buildings.ThermalZones.Detailed.BaseClasses.ParameterConstructionWithWindow ParameterConstructionWithWindow Record for exterior constructions that have a window
Buildings.ThermalZones.Detailed.BaseClasses.PartialParameterConstruction PartialParameterConstruction Partial record for constructions
Buildings.ThermalZones.Detailed.BaseClasses.SideFins SideFins Record for window side fins
Buildings.ThermalZones.Detailed.BaseClasses.Examples Examples Collection of models that illustrate model use and test models

Buildings.ThermalZones.Detailed.BaseClasses.CFDAirHeatMassBalance Buildings.ThermalZones.Detailed.BaseClasses.CFDAirHeatMassBalance

Heat and mass balance of the air based on computational fluid dynamics

Buildings.ThermalZones.Detailed.BaseClasses.CFDAirHeatMassBalance

Information

This model computes the heat and mass balance of the air using Computational Fluid Dynamics program.

For a documentation of the exchange parameters and variables, see Buildings.ThermalZones.Detailed.UsersGuide.CFD.

Extends from Buildings.ThermalZones.Detailed.BaseClasses.PartialAirHeatMassBalance (Partial model for heat and mass balance of the air).

Parameters

TypeNameDefaultDescription
ParameterConstructiondatConExt[NConExt] Data for exterior construction
ParameterConstructionWithWindowdatConExtWin[NConExtWin] Data for exterior construction with window
ParameterConstructiondatConPar[NConPar] Data for partition construction
ParameterConstructiondatConBou[NConBou] Data for construction boundary
OpaqueSurfacesurBou[NSurBou] Record for data of surfaces whose heat conduction is modeled outside of this room
Brick120dummyCon Dummy construction to assign a parameter to the instance
SingleClear3dummyGlaSys Dummy construction to assign a parameter to the instance
replaceable package MediumPartialMediumMedium in the component
BooleanhaveShade Set to true if at least one window has an interior or exterior shade
VolumeV Volume [m3]
StringcfdFilNam CFD input file name
BooleanuseCFDtrueSet to false to deactivate the CFD interface and use instead yFixed as output
BooleanhaveSensor Flag, true if the model has at least one sensor
IntegernSen Number of sensors that are connected to CFD output
StringsensorName[nSen] Names of sensors as declared in the CFD input file
StringportName[nPorts] Names of fluid ports as declared in the CFD input file
RealuSha_fixed[nConExtWin] Constant control signal for the shading device (0: unshaded; 1: fully shaded)
Exterior constructions
IntegernConExt Number of exterior constructions
IntegernConExtWin Number of window constructions
Partition constructions
IntegernConPar Number of partition constructions
Boundary constructions
IntegernConBou Number of constructions that have their outside surface exposed to the boundary of this room
IntegernSurBou Number of surface heat transfer models that connect to constructions that are modeled outside of this room
Sampling
TimesamplePeriod Sample period of component [s]
Dynamics
Equations
DynamicsmassDynamics Formulation of mass balance
Initialization
AbsolutePressurep_start Start value of pressure [Pa]

Connectors

TypeNameDescription
input RealInputuSha[NConExtWin]Input connector, used to scale the surface area to take into account an operable shading device, 0: unshaded; 1: fully shaded
input RealInputQRadAbs_flow[NConExtWin]Total net radiation that is absorbed by the shade (positive if absorbed) [W]
input RealInputQCon_flowConvective sensible heat gains of the room
input RealInputQLat_flowLatent heat gains for the room
output RealOutputTSha[NConExtWin]Shade temperature [K]
VesselFluidPorts_bports[nPorts]Fluid inlets and outlets
HeatPort_aheaPorAirHeat port to air volume
HeatPort_aconExt[NConExt]Heat port that connects to room-side surface of exterior constructions
HeatPort_aconExtWin[NConExtWin]Heat port that connects to room-side surface of exterior constructions that contain a window
HeatPort_aglaUns[NConExtWin]Heat port that connects to room-side surface of unshaded glass
HeatPort_aglaSha[NConExtWin]Heat port that connects to room-side surface of shaded glass
HeatPort_aconExtWinFra[NConExtWin]Heat port that connects to room-side surface of window frame
HeatPort_aconPar_a[NConPar]Heat port that connects to room-side surface a of partition constructions
HeatPort_aconPar_b[NConPar]Heat port that connects to room-side surface b of partition constructions
HeatPort_aconBou[NConBou]Heat port that connects to room-side surface of constructions that expose their other surface to the outside
HeatPort_aconSurBou[NSurBou]Heat port to surfaces of models that compute the heat conduction outside of this room
replaceable package MediumMedium in the component
output RealOutputyCFD[nSen]Sensor for output from CFD

Modelica definition

model CFDAirHeatMassBalance "Heat and mass balance of the air based on computational fluid dynamics" extends Buildings.ThermalZones.Detailed.BaseClasses.PartialAirHeatMassBalance; replaceable package Medium = Modelica.Media.Interfaces.PartialMedium "Medium in the component"; // Assumptions parameter Modelica.Fluid.Types.Dynamics massDynamics "Formulation of mass balance"; // Initialization parameter Medium.AbsolutePressure p_start "Start value of pressure"; parameter String cfdFilNam "CFD input file name"; parameter Boolean useCFD=true "Set to false to deactivate the CFD interface and use instead yFixed as output"; parameter Modelica.SIunits.Time samplePeriod(min=100*Modelica.Constants.eps) "Sample period of component"; parameter Boolean haveSensor "Flag, true if the model has at least one sensor"; parameter Integer nSen(min=0) "Number of sensors that are connected to CFD output"; parameter String sensorName[nSen] "Names of sensors as declared in the CFD input file"; parameter String portName[nPorts] "Names of fluid ports as declared in the CFD input file"; parameter Real uSha_fixed[nConExtWin] "Constant control signal for the shading device (0: unshaded; 1: fully shaded)"; CFDExchange cfd( final cfdFilNam=cfdFilNam, final startTime=startTime, final activateInterface=useCFD, final samplePeriod=if useCFD then samplePeriod else Modelica.Constants.inf, final nWri=kFluIntC_inflow + Medium.nC*nPorts, final nRea=kSen + nSen, final nSur=nSur, final surIde=surIde, final haveShade=haveShade, final haveSensor=haveSensor, final sensorName=sensorName, final portName=portName, final yFixed=yFixed, final nXi=Medium.nXi, final nC=Medium.nC, rho_start=rho_start, nConExtWin=NConExtWin) "Block that exchanges data with the CFD simulation"; Modelica.Blocks.Interfaces.RealOutput yCFD[nSen] if haveSensor "Sensor for output from CFD"; protected parameter Modelica.SIunits.Time startTime(fixed=false) "First sample time instant."; // Values that are used for yFixed parameter Real yFixed[kSen + nSen](each fixed=false) "Values used for yFixed in CFDExchange"; parameter Modelica.SIunits.HeatFlowRate Q_flow_fixed[kSurBou + nSurBou]= fill(0, kSurBou + nSurBou) "Surface heat flow rate used for yFixed"; parameter Modelica.SIunits.Temperature TRooAve_fixed=Medium.T_default "Average room air temperature used for yFixed"; parameter Modelica.SIunits.Temperature TSha_fixed[NConExtWin]= fill(Medium.T_default, NConExtWin) "Shade temperature used for yFixed"; parameter Modelica.SIunits.Temperature T_outflow_fixed[nPorts]= fill(Medium.T_default, nPorts) "Temperature of the fluid that flows into the HVAC system used for yFixed"; parameter Real Xi_outflow_fixed[nPorts*Medium.nXi](each fixed=false) "Species concentration of the fluid that flows into the HVAC system used for yFixed"; parameter Real C_outflow_fixed[nPorts*Medium.nC](each fixed=false) "Trace substances of the fluid that flows into the HVAC system used for yFixed"; parameter Modelica.SIunits.Density rho_start=Medium.density( Medium.setState_pTX( T=Medium.T_default, p=p_start, X=Medium.X_default)) "Density, used to compute fluid mass"; final parameter CFDSurfaceIdentifier surIde[kSurBou + nSurBou]= assignSurfaceIdentifier( nConExt=nConExt, nConExtWin=nConExtWin, nConPar=nConPar, nConBou=nConBou, nSurBou=nSurBou, nSur=nSur, haveShade=haveShade, nameConExt=datConExt.name, AConExt=datConExt.A, tilConExt=datConExt.til, bouConConExt=datConExt.boundaryCondition, nameConExtWin=datConExtWin.name, AConExtWin=datConExtWin.AOpa, tilConExtWin=datConExtWin.til, bouConConExtWin=datConExtWin.boundaryCondition, AGla=datConExtWin.AGla, AFra=datConExtWin.AFra, uSha=uSha_fixed, nameConPar=datConPar.name, AConPar=datConPar.A, tilConPar=datConPar.til, bouConConPar=datConPar.boundaryCondition, nameConBou=datConBou.name, AConBou=datConBou.A, tilConBou=datConBou.til, bouConConBou=datConBou.boundaryCondition, nameSurBou=surBou.name, ASurBou=surBou.A, tilSurBou=surBou.til, bouConSurBou=surBou.boundaryCondition) "Names of all surfaces in the order in which their properties are sent to CFD"; // Interfaces between the CFD block and the heat ports of this model // Here, we directly access datConExt instead of surIde. The reason is // the Dymola thinks that surIde.bouCon is not fixed at translation time // and then refuses to use this parameter to conditionally remove connectors // in CFDSurfaceInterface. CFDSurfaceInterface cfdConExt[NConExt](final bouCon=datConExt[:].boundaryCondition) if haveConExt "Interface to heat port of exterior constructions"; CFDSurfaceInterface cfdConExtWin[NConExtWin](final bouCon=datConExtWin[:].boundaryCondition) if haveConExtWin "Interface to heat port of opaque part of exterior constructions with window"; CFDSurfaceInterface cfdGlaUns[NConExtWin](final bouCon=datConExtWin[:].boundaryCondition) if haveConExtWin "Interface to heat port of unshaded part of glass"; CFDSurfaceInterface cfdGlaSha[NConExtWin](final bouCon=datConExtWin[:].boundaryCondition) if haveShade "Interface to heat port of shaded part of glass"; CFDSurfaceInterface cfdConExtWinFra[NConExtWin](final bouCon=datConExtWin[:].boundaryCondition) if haveConExtWin "Interface to heat port of window frame"; CFDSurfaceInterface cfdConPar_a[NConPar](final bouCon=datConPar[:].boundaryCondition) if haveConPar "Interface to heat port of surface a of partition constructions"; CFDSurfaceInterface cfdConPar_b[NConPar](final bouCon=datConPar[:].boundaryCondition) if haveConPar "Interface to heat port of surface b of partition constructions"; CFDSurfaceInterface cfdConBou[NConBou](final bouCon=datConBou[:].boundaryCondition) if haveConBou "Interface to heat port that connects to room-side surface of constructions that expose their other surface to the outside"; CFDSurfaceInterface cfdSurBou[NSurBou](final bouCon=surBou[:].boundaryCondition) if haveSurBou "Interface to heat port of surfaces of models that compute the heat conduction outside of this room"; Modelica.Thermal.HeatTransfer.Sources.PrescribedTemperature cfdHeaPorAir "Interface to heat port of air node"; CFDFluidInterface fluInt( redeclare final package Medium = Medium, final massDynamics=massDynamics, final nPorts=nPorts, final V=V, final p_start=p_start, rho_start=rho_start) "Fluid interface"; // The following list declares the first index minus 1 // of the input and output signals to the CFD block. // These parameters are then used to loop over the connectors, such // as // for i in kConExt+1:kConExt+nConExt loop // ... // end for; final parameter Integer kConExt=0 "Offset used to connect CFD signals to conExt"; final parameter Integer kConExtWin=kConExt + nConExt "Offset used to connect CFD signals to conExtWin"; final parameter Integer kGlaUns=kConExtWin + nConExtWin "Offset used to connect CFD signals to glaUns"; final parameter Integer kGlaSha=kGlaUns + nConExtWin "Offset used to connect CFD signals to glaSha"; final parameter Integer kConExtWinFra=if haveShade then kGlaSha + nConExtWin else kGlaSha "Offset used to connect CFD signals to glaSha"; final parameter Integer kConPar_a=kConExtWinFra + nConExtWin "Offset used to connect CFD signals to conPar_a"; final parameter Integer kConPar_b=kConPar_a + nConPar "Offset used to connect CFD signals to conPar_b"; final parameter Integer kConBou=kConPar_b + nConPar "Offset used to connect CFD signals to conBou"; final parameter Integer kSurBou=kConBou + nConBou "Offset used to connect CFD signals to surBou"; final parameter Integer kHeaPorAir=kSurBou + nSurBou "Offset used to connect CFD output signal to air heat port (to send average temperature from CFD to Modelica)"; // final parameter Integer kUSha = kHeaPorAir + 1 final parameter Integer kUSha=kSurBou + nSurBou "Offset used to connect CFD signals to input signal of shade"; final parameter Integer kQRadAbs_flow=if haveShade then kUSha + nConExtWin else kUSha "Offset used to connect CFD signals to input signal that contains the radiation absorbed by the shade"; // Because heaPorAir is only receiving T from CFD, but does not send Q_flow to CFD, there is no '+1' increment // for kTSha final parameter Integer kTSha=kHeaPorAir + 1 "Offset used to connect CFD signals to output signal that contains the shade temperature"; final parameter Integer kQConGai_flow=if haveShade then kQRadAbs_flow + nConExtWin else kQRadAbs_flow "Offset used to connect CFD signals to input signal for connect convective sensible heat gain"; final parameter Integer kQLatGai_flow=kQConGai_flow + 1 "Offset used to connect CFD signals to input signal for connect radiative heat gain"; final parameter Integer kFluIntP=kQLatGai_flow + 1 "Offset used to connect CFD signals to input signal for pressure from the fluid ports"; final parameter Integer kFluIntM_flow=kFluIntP + 1 "Offset used to connect CFD signals to input signals for mass flow rate from the fluid ports"; final parameter Integer kFluIntT_inflow=kFluIntM_flow + nPorts "Offset used to connect CFD signals to input signals for inflowing temperature from the fluid ports"; final parameter Integer kFluIntXi_inflow=kFluIntT_inflow + nPorts "Offset used to connect CFD signals to input signals for inflowing species concentration from the fluid ports"; final parameter Integer kFluIntC_inflow=kFluIntXi_inflow + nPorts*Medium.nXi "Offset used to connect CFD signals to input signals for inflowing trace substances from the fluid ports"; // Input signals to fluInt block final parameter Integer kFluIntT_outflow=if haveShade then kTSha + nConExtWin else kTSha "Offset used to connect CFD signals to outgoing temperature for the fluid ports"; final parameter Integer kFluIntXi_outflow=kFluIntT_outflow + nPorts "Offset used to connect CFD signals to outgoing species concentration for the fluid ports"; final parameter Integer kFluIntC_outflow=kFluIntXi_outflow + nPorts*Medium.nXi "Offset used to connect CFD signals to outgoing trace substances for the fluid ports"; final parameter Integer kSen=kFluIntC_outflow + nPorts*Medium.nC "Offset used to connect CFD signals to output sensor"; final parameter Integer nSur=kSurBou + nSurBou "Number of surfaces"; protected function assignSurfaceIdentifier input Integer nConExt(min=0) "Number of exterior constructions"; input Integer nConExtWin(min=0) "Number of window constructions"; input Integer nConPar(min=0) "Number of partition constructions"; input Integer nConBou(min=0) "Number of constructions that have their outside surface exposed to the boundary of this room"; input Integer nSurBou(min=0) "Number of surface heat transfer models that connect to constructions that are modeled outside of this room"; input Integer nSur(min=2) "Total number of surfaces"; input Boolean haveShade "Flag, set to true if any of the window in this room has a shade"; /* // Declaration of counters used in the loop. // This could be computed (again) in this function, but using it // as a function arguments avoids code duplication. input Integer kConExt "Offset used to connect CFD signals to conExt"; input Integer kConExtWin "Offset used to connect CFD signals to conExtWin"; input Integer kGlaUns "Offset used to connect CFD signals to glaUns"; input Integer kGlaSha "Offset used to connect CFD signals to glaSha"; input Integer kConExtWinFra "Offset used to connect CFD signals to glaSha"; input Integer kConPar_a "Offset used to connect CFD signals to conPar_a"; input Integer kConPar_b "Offset used to connect CFD signals to conPar_b"; input Integer kConBou "Offset used to connect CFD signals to conBou"; input Integer kSurBou "Offset used to connect CFD signals to surBou"; */ // Declaration of construction data input String nameConExt[nConExt] "Surface name"; input Modelica.SIunits.Area AConExt[nConExt] "Surface area"; input Modelica.SIunits.Angle tilConExt[nConExt] "Surface tilt"; input Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions bouConConExt[nConExt] "Boundary condition"; input String nameConExtWin[nConExtWin] "Surface name"; input Modelica.SIunits.Area AConExtWin[nConExtWin] "Surface area"; input Modelica.SIunits.Angle tilConExtWin[nConExtWin] "Surface tilt"; input Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions bouConConExtWin[ nConExtWin] "Boundary condition"; input Modelica.SIunits.Area AGla[nConExtWin] "Surface area"; input Modelica.SIunits.Area AFra[nConExtWin] "Surface area"; input Real uSha[nConExtWin] "Shade ratio"; input String nameConPar[nConPar] "Surface name"; input Modelica.SIunits.Area AConPar[nConPar] "Surface area"; input Modelica.SIunits.Angle tilConPar[nConPar] "Surface tilt"; input Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions bouConConPar[nConPar] "Boundary condition"; input String nameConBou[nConBou] "Surface name"; input Modelica.SIunits.Area AConBou[nConBou] "Surface area"; input Modelica.SIunits.Angle tilConBou[nConBou] "Surface tilt"; input Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions bouConConBou[nConBou] "Boundary condition"; input String nameSurBou[nSurBou] "Surface name"; input Modelica.SIunits.Area ASurBou[nSurBou] "Surface area"; input Modelica.SIunits.Angle tilSurBou[nSurBou] "Surface tilt"; input Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions bouConSurBou[nSurBou] "Boundary condition"; output CFDSurfaceIdentifier id[nSur] "Name of all surfaces"; algorithm id := cat( 1, {CFDSurfaceIdentifier( name=nameConExt[i], A=AConExt[i], til=tilConExt[i], bouCon=bouConConExt[i]) for i in 1:nConExt}, {CFDSurfaceIdentifier( name=nameConExtWin[i], A=AConExtWin[i], til=tilConExtWin[i], bouCon=bouConConExtWin[i]) for i in 1:nConExtWin}, {CFDSurfaceIdentifier( name=nameConExtWin[i] + " (glass, unshaded)", A=AGla[i]*(1-uSha[i]), til=tilConExtWin[i], bouCon=bouConConExtWin[i]) for i in 1:nConExtWin}, {CFDSurfaceIdentifier( name=nameConExtWin[i] + " (glass, shaded)", A=AGla[i]*uSha[i], til=tilConExtWin[i], bouCon=bouConConExtWin[i]) for i in 1:(if haveShade then nConExtWin else 0)}, {CFDSurfaceIdentifier( name=nameConExtWin[i] + " (frame)", A=AFra[i], til=tilConExtWin[i], bouCon=bouConConExtWin[i]) for i in 1:nConExtWin}, {CFDSurfaceIdentifier( name=nameConPar[i] + " (surface a)", A=AConPar[i], til=tilConPar[i], bouCon=bouConConPar[i]) for i in 1:nConPar}, {CFDSurfaceIdentifier( name=nameConPar[i] + " (surface b)", A=AConPar[i], til=tilConPar[i] + Modelica.Constants.pi/180, bouCon=bouConConPar[i]) for i in 1:nConPar}, {CFDSurfaceIdentifier( name=nameConBou[i], A=AConBou[i], til=tilConBou[i], bouCon=bouConConBou[i]) for i in 1:nConBou}, {CFDSurfaceIdentifier( name=nameSurBou[i], A=ASurBou[i], til=tilSurBou[i], bouCon=bouConSurBou[i]) for i in 1:nSurBou}); end assignSurfaceIdentifier; public Modelica.Blocks.Math.Add QTotCon_flow "Total sensible convective heat flow rate added to the room"; Modelica.Thermal.HeatTransfer.Sensors.HeatFlowSensor senHeaFlo "Sensor for heat flow added through the port heaPorAir"; to_W QTotCon_flow_W; initial equation startTime = time; for i in 1:nPorts loop for j in 1:Medium.nXi loop Xi_outflow_fixed[(i - 1)*Medium.nXi + j] = Medium.X_default[j]; end for; end for; for i in 1:nPorts loop for j in 1:Medium.nC loop C_outflow_fixed[(i - 1)*Medium.nC + j] = 0; end for; end for; // Assignment of yFixed for i in 1:kSurBou + nSurBou loop yFixed[i] = Q_flow_fixed[i]; end for; yFixed[kHeaPorAir + 1] = TRooAve_fixed; if haveShade then for i in 1:nConExtWin loop yFixed[kTSha + i] = TSha_fixed[i]; end for; end if; for i in 1:nPorts loop yFixed[kFluIntT_outflow + i] = T_outflow_fixed[i]; for j in 1:Medium.nXi loop yFixed[kFluIntXi_outflow + (i - 1)*Medium.nXi + j] = Xi_outflow_fixed[(i - 1)*Medium.nXi + j]; end for; for j in 1:Medium.nC loop yFixed[kFluIntC_outflow + (i - 1)*Medium.nC + j] = C_outflow_fixed[(i - 1) *Medium.nC + j]; end for; end for; for i in 1:nSen loop yFixed[kSen + i] = 0; end for; equation ////////////////////////////////////////////////////////////////////// // Data exchange with CFD block if haveConExt then for i in 1:nConExt loop if datConExt[i].boundaryCondition == Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions.Temperature then connect(cfd.u[kConExt + i], cfdConExt[i].T_out); connect(cfd.y[kConExt + i], cfdConExt[i].Q_flow_in); else connect(cfd.u[kConExt + i], cfdConExt[i].Q_flow_out); connect(cfd.y[kConExt + i], cfdConExt[i].T_in); end if; end for; end if; if haveConExtWin then for i in 1:nConExtWin loop if datConExtWin[i].boundaryCondition == Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions.Temperature then connect(cfd.u[kConExtWin + i], cfdConExtWin[i].T_out); connect(cfd.y[kConExtWin + i], cfdConExtWin[i].Q_flow_in); connect(cfd.u[kGlaUns + i], cfdGlaUns[i].T_out); connect(cfd.y[kGlaUns + i], cfdGlaUns[i].Q_flow_in); connect(cfd.u[kConExtWinFra + i], cfdConExtWinFra[i].T_out); connect(cfd.y[kConExtWinFra + i], cfdConExtWinFra[i].Q_flow_in); else connect(cfd.u[kConExtWin + i], cfdConExtWin[i].Q_flow_out); connect(cfd.y[kConExtWin + i], cfdConExtWin[i].T_in); connect(cfd.u[kGlaUns + i], cfdGlaUns[i].Q_flow_out); connect(cfd.y[kGlaUns + i], cfdGlaUns[i].T_in); connect(cfd.u[kConExtWinFra + i], cfdConExtWinFra[i].Q_flow_out); connect(cfd.y[kConExtWinFra + i], cfdConExtWinFra[i].T_in); end if; end for; end if; if haveShade then for i in 1:nConExtWin loop if datConExtWin[i].boundaryCondition == Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions.Temperature then connect(cfd.u[kGlaSha + i], cfdGlaSha[i].T_out); connect(cfd.y[kGlaSha + i], cfdGlaSha[i].Q_flow_in); else connect(cfd.u[kGlaSha + i], cfdGlaSha[i].Q_flow_out); connect(cfd.y[kGlaSha + i], cfdGlaSha[i].T_in); end if; end for; end if; if haveConPar then for i in 1:nConPar loop if datConPar[i].boundaryCondition == Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions.Temperature then connect(cfd.u[kConPar_a + i], cfdConPar_a[i].T_out); connect(cfd.y[kConPar_a + i], cfdConPar_a[i].Q_flow_in); connect(cfd.u[kConPar_b + i], cfdConPar_b[i].T_out); connect(cfd.y[kConPar_b + i], cfdConPar_b[i].Q_flow_in); else connect(cfd.u[kConPar_a + i], cfdConPar_a[i].Q_flow_out); connect(cfd.y[kConPar_a + i], cfdConPar_a[i].T_in); connect(cfd.u[kConPar_b + i], cfdConPar_b[i].Q_flow_out); connect(cfd.y[kConPar_b + i], cfdConPar_b[i].T_in); end if; end for; end if; if haveConBou then for i in 1:nConBou loop if datConBou[i].boundaryCondition == Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions.Temperature then connect(cfd.u[kConBou + i], cfdConBou[i].T_out); connect(cfd.y[kConBou + i], cfdConBou[i].Q_flow_in); else connect(cfd.u[kConBou + i], cfdConBou[i].Q_flow_out); connect(cfd.y[kConBou + i], cfdConBou[i].T_in); end if; end for; end if; if haveSurBou then for i in 1:nSurBou loop if surBou[i].boundaryCondition == Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions.Temperature then connect(cfd.u[kSurBou + i], cfdSurBou[i].T_out); connect(cfd.y[kSurBou + i], cfdSurBou[i].Q_flow_in); else connect(cfd.u[kSurBou + i], cfdSurBou[i].Q_flow_out); connect(cfd.y[kSurBou + i], cfdSurBou[i].T_in); end if; end for; end if; connect(cfdConExt.port, conExt); connect(cfdConExtWin.port, conExtWin); connect(cfdGlaUns.port, glaUns); connect(cfdGlaSha.port, glaSha); connect(cfdConExtWinFra.port, conExtWinFra); connect(cfdConPar_a.port, conPar_a); connect(cfdConPar_b.port, conPar_b); connect(cfdConBou.port, conBou); connect(cfdSurBou.port, conSurBou); // Connections to heat port of air volume connect(cfd.y[kHeaPorAir + 1], cfdHeaPorAir.T); // Connections to shade if haveShade then for i in 1:nConExtWin loop connect(cfd.u[kUSha + i], uSha[i]); connect(cfd.u[kQRadAbs_flow + i], QRadAbs_flow[i]); connect(cfd.y[kTSha + i], TSha[i]); end for; end if; // Connection for heat gain that is added to the room // (averaged over the whole room air volume) connect(QTotCon_flow_W.y, cfd.u[kQConGai_flow + 1]); connect(QLat_flow, cfd.u[kQLatGai_flow + 1]); // Connections to fluid port connect(ports, fluInt.ports); // Output signals from fluInt block // The pressure of the air volume will be sent from Modelica to CFD connect(cfd.u[kFluIntP + 1], fluInt.p); for i in 1:nPorts loop connect(cfd.u[kFluIntM_flow + i], fluInt.m_flow[i]); connect(cfd.u[kFluIntT_inflow + i], fluInt.T_inflow[i]); for j in 1:Medium.nXi loop connect(cfd.u[kFluIntXi_inflow + (i - 1)*Medium.nXi + j], fluInt.Xi_inflow[ (i - 1)*Medium.nXi + j]); end for; for j in 1:Medium.nC loop connect(cfd.u[kFluIntC_inflow + (i - 1)*Medium.nC + j], fluInt.C_inflow[( i - 1)*Medium.nC + j]); end for; end for; // Input signals to fluInt block // The pressures of ports[2:nPorts] will be sent from CFD to Modelica for i in 1:nPorts loop connect(cfd.y[kFluIntT_outflow + i], fluInt.T_outflow[i]); for j in 1:Medium.nXi loop connect(cfd.y[kFluIntXi_outflow + (i - 1)*Medium.nXi + j], fluInt.Xi_outflow[ (i - 1)*Medium.nXi + j]); end for; for j in 1:Medium.nC loop connect(cfd.y[kFluIntC_outflow + (i - 1)*Medium.nC + j], fluInt.C_outflow[ (i - 1)*Medium.nC + j]); end for; end for; // Connections for sensor signal if haveSensor then for i in 1:nSen loop connect(cfd.y[kSen + i], yCFD[i]); end for; end if; connect(heaPorAir, senHeaFlo.port_a); connect(senHeaFlo.port_b, cfdHeaPorAir.port); connect(senHeaFlo.Q_flow, QTotCon_flow.u1); connect(QCon_flow, QTotCon_flow.u2); connect(QTotCon_flow.y, QTotCon_flow_W.u); end CFDAirHeatMassBalance;

Buildings.ThermalZones.Detailed.BaseClasses.CFDExchange Buildings.ThermalZones.Detailed.BaseClasses.CFDExchange

Block that exchanges data with the CFD code

Buildings.ThermalZones.Detailed.BaseClasses.CFDExchange

Information

This block samples interface variables and exchanges data with the CFD code.

For a documentation of the exchange parameters and variables, see Buildings.ThermalZones.Detailed.UsersGuide.CFD.

Extends from Modelica.Blocks.Interfaces.DiscreteBlock (Base class of discrete control blocks).

Parameters

TypeNameDefaultDescription
TimesamplePeriod Sample period of component [s]
TimestartTime0First sample time instant [s]
StringcfdFilNam CFD input file name
BooleanactivateInterfacetrueSet to false to deactivate interface and use instead yFixed as output
IntegernXi Number of independent species concentration of the inflowing medium
IntegernC Number of trace substances of the inflowing medium
IntegernWri Number of values to write to the CFD simulation
IntegernRea Number of double values to be read from the CFD simulation
IntegerflaWri[nWri]ones(nWri)Flag for double values (0: use current value, 1: use average over interval, 2: use integral over interval)
RealyFixed[nRea] Fixed output, used if activateInterface=false
IntegernSur Number of surfaces
IntegernConExtWin number of exterior construction with window
CFDSurfaceIdentifiersurIde[nSur] Surface identifiers
BooleanhaveShade Set to true if at least one window in the room has a shade
BooleanhaveSensor Flag, true if the model has at least one sensor
StringsensorName[:] Names of sensors as declared in the CFD input file
StringportName[:] Names of fluid ports as declared in the CFD input file
BooleanverbosefalseSet to true for verbose output
Densityrho_start Density at initial state [kg/m3]

Connectors

TypeNameDescription
input RealInputu[nWri]Inputs to CFD
output RealOutputy[nRea]Outputs received from CFD

Modelica definition

block CFDExchange "Block that exchanges data with the CFD code" extends Modelica.Blocks.Interfaces.DiscreteBlock( firstTrigger(start=false, fixed=true)); parameter String cfdFilNam "CFD input file name"; parameter Boolean activateInterface=true "Set to false to deactivate interface and use instead yFixed as output"; parameter Integer nXi "Number of independent species concentration of the inflowing medium"; parameter Integer nC "Number of trace substances of the inflowing medium"; parameter Integer nWri(min=0) "Number of values to write to the CFD simulation"; parameter Integer nRea(min=0) "Number of double values to be read from the CFD simulation"; parameter Integer flaWri[nWri] = ones(nWri) "Flag for double values (0: use current value, 1: use average over interval, 2: use integral over interval)"; parameter Real yFixed[nRea] "Fixed output, used if activateInterface=false"; parameter Integer nSur(min=2) "Number of surfaces"; parameter Integer nConExtWin(min=0) "number of exterior construction with window"; parameter CFDSurfaceIdentifier surIde[nSur] "Surface identifiers"; parameter Boolean haveShade "Set to true if at least one window in the room has a shade"; parameter Boolean haveSensor "Flag, true if the model has at least one sensor"; parameter String sensorName[:] "Names of sensors as declared in the CFD input file"; parameter String portName[:] "Names of fluid ports as declared in the CFD input file"; parameter Boolean verbose=false "Set to true for verbose output"; parameter Modelica.SIunits.Density rho_start "Density at initial state"; CFDThread CFDThre = CFDThread() "Allocate memory for cosimulation variables via constructor and send stop command to FFD via destructor"; Modelica.Blocks.Interfaces.RealInput u[nWri] "Inputs to CFD"; discrete Modelica.Blocks.Interfaces.RealOutput y[nRea] "Outputs received from CFD"; Real uInt[nWri] "Value of integral"; discrete Real uIntPre[nWri] "Value of integral at previous sampling instance"; discrete Real uWri[nWri] "Value to be sent to the CFD interface"; protected final parameter Integer nSen(min=0) = size(sensorName, 1) "Number of sensors that are connected to CFD output"; final parameter Integer nPorts=size(portName, 1) "Number of fluid ports for the HVAC inlet and outlets"; discrete Modelica.SIunits.Time modTimRea(fixed=false) "Current model time received from CFD"; discrete Integer retVal(start=0, fixed=true) "Return value from CFD"; /////////////////////////////////////////////////////////////////////////// // Function that sends the parameters of the model from Modelica to CFD function sendParameters input String cfdFilNam "CFD input file name"; input String[nSur] name "Surface names"; input Modelica.SIunits.Area[nSur] A "Surface areas"; input Modelica.SIunits.Angle[nSur] til "Surface tilt"; input Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions[nSur] bouCon "Type of boundary condition"; input Integer nPorts(min=0) "Number of fluid ports for the HVAC inlet and outlets"; input String portName[nPorts] "Names of fluid ports as declared in the CFD input file"; input Boolean haveSensor "Flag, true if the model has at least one sensor"; input String sensorName[nSen] "Names of sensors as declared in the CFD input file"; input Boolean haveShade "Flag, true if the windows have a shade"; input Integer nSur(min=2) "Number of surfaces"; input Integer nSen(min=0) "Number of sensors that are connected to CFD output"; input Integer nConExtWin(min=0) "number of exterior construction with window"; input Boolean verbose "Set to true for verbose output"; input Integer nXi "Number of independent species concentration of the inflowing medium"; input Integer nC "Number of trace substances of the inflowing medium"; input Modelica.SIunits.Density rho_start "Density at initial state"; protected Integer coSimFlag=0; algorithm if verbose then Modelica.Utilities.Streams.print("CFDExchange:sendParameter"); end if; for i in 1:nSur loop assert(A[i] > 0, "Surface must be bigger than zero."); end for; Modelica.Utilities.Streams.print(string="Start cosimulation"); coSimFlag := cfdStartCosimulation( cfdFilNam, name, A, til, bouCon, nPorts, portName, haveSensor, sensorName, haveShade, nSur, nSen, nConExtWin, nXi, nC, rho_start); assert(coSimFlag < 0.5, "Could not start the cosimulation."); end sendParameters; /////////////////////////////////////////////////////////////////////////// // Function that exchanges data during the time stepping between // Modelica and CFD. function exchange input Integer flag "Communication flag to write to CFD"; input Modelica.SIunits.Time t "Current simulation time in seconds to write"; input Modelica.SIunits.Time dt(min=100*Modelica.Constants.eps) "Requested time step length"; input Real[nU] u "Input for CFD"; input Integer nU "Number of inputs for CFD"; input Real[nY] yFixed "Fixed values (used for debugging only)"; input Integer nY "Number of outputs from CFD"; output Modelica.SIunits.Time modTimRea "Current model time in seconds read from CFD"; input Boolean verbose "Set to true for verbose output"; output Real[nY] y "Output computed by CFD"; output Integer retVal "The exit value, which is negative if an error occurred"; algorithm if verbose then Modelica.Utilities.Streams.print("CFDExchange:exchange at t=" + String(t)); end if; (modTimRea,y,retVal) := cfdExchangeData( flag, t, dt, u, nU, nY); end exchange; /////////////////////////////////////////////////////////////////////////// // Function that returns strings that are not unique. function returnNonUniqueStrings input Integer n(min=2) "Number entries"; input Boolean ideNam[n - 1] "Flag that is set to true if the name is used more than once"; input String names[n] "Names"; output String s "String with non-unique names"; algorithm s := ""; for i in 1:n - 1 loop if ideNam[i] then s := s + "\n '" + names[i] + "'"; end if; end for; end returnNonUniqueStrings; // This function does not work because Dymola 2014 has problems with // handling strings in an algorithm section function assertStringsAreUnique input String descriptiveName "Descriptive name of what is tested, such as 'sensor' or 'ports'"; input Integer n(min=2) "Number of strings"; input String names[n] "Names"; protected Boolean ideNam[n-1] "Flag that is set to true if the name is used more than once"; algorithm // Loop over all names to verify that they are unique if n > 1 then for i in 1:n-1 loop for j in i+1:n loop ideNam[i] := Modelica.Utilities.Strings.isEqual(names[i], names[j]); if ideNam[i] then break; end if; end for; // j end for; // i assert( not Modelica.Math.BooleanVectors.anyTrue(ideNam), "For the CFD interface, all " + descriptiveName + " must have a name that is unique within each room. The following " + descriptiveName + " names are used more than once in the room model:" + returnNonUniqueStrings(n, ideNam, names)); else ideNam :=fill(false, max(0, n - 1)); end if; end assertStringsAreUnique; initial equation // Diagnostics output if verbose then Modelica.Utilities.Streams.print(string=" CFDExchange has the following surfaces:"); for i in 1:nSur loop Modelica.Utilities.Streams.print(string=" name = " + surIde[i].name + " A = " + String(surIde[i].A) + " [m2] tilt = " + String(surIde[i].til*180/Modelica.Constants.pi) + " [deg]"); end for; if haveSensor then Modelica.Utilities.Streams.print(string=" CFDExchange has the following sensors:"); for i in 1:nSen loop Modelica.Utilities.Streams.print(string=" " + sensorName[i]); end for; else Modelica.Utilities.Streams.print(string="CFDExchange has no sensors."); end if; end if; // Assert that the surface, sensor and ports have a name, // and that that name is unique. // Otherwise, stop with an error. assertStringsAreUnique(descriptiveName="surface", n=nSur, names={surIde[i].name for i in 1:nSur}); assertStringsAreUnique(descriptiveName="sensor", n=nSen, names=sensorName); assertStringsAreUnique(descriptiveName="ports", n=nPorts, names=portName); // Send parameters to the CFD interface sendParameters( cfdFilNam=cfdFilNam, name=surIde[:].name, A=surIde[:].A, til=surIde[:].til, bouCon=surIde[:].bouCon, haveSensor=haveSensor, portName=portName, sensorName=sensorName, haveShade=haveShade, nSur=nSur, nSen=nSen, nConExtWin=nConExtWin, nPorts=nPorts, nXi=nXi, nC=nC, rho_start=rho_start, verbose=verbose); // Assignment of parameters and start values uInt = zeros(nWri); uIntPre = zeros(nWri); for i in 1:nWri loop assert(flaWri[i] >= 0 and flaWri[i] <= 2, "Parameter flaWri out of range for " + String(i) + "-th component."); end for; // Assign uWri and y. This avoids a translation warning in Dymola // as otherwise, not all initial values are specified. // However, uWri and y are only used below in the body of the 'when' // block after they have been assigned. uWri = u; y=yFixed; modTimRea = time; equation for i in 1:nWri loop der(uInt[i]) = if (flaWri[i] > 0) then u[i] else 0; end for; when sampleTrigger then // Compute value that will be sent to the CFD interface for i in 1:nWri loop if (flaWri[i] == 0) then uWri[i] = pre(u[i]); elseif (flaWri[i] == 1) then if (time<startTime+0.1*samplePeriod) then uWri[i] = pre(u[i]); // Set the correct initial data else uWri[i] = (uInt[i] - pre(uIntPre[i]))/samplePeriod; // Average value over the sampling interval end if; else uWri[i] = uInt[i] - pre(uIntPre[i]); // Integral over the sampling interval end if; end for; // Store current value of integral uIntPre = uInt; end when; algorithm when sampleTrigger then // Exchange data if activateInterface then (modTimRea,y,retVal) := exchange( flag=0, t=time, dt=samplePeriod, u=uWri, nU=size(u, 1), yFixed=yFixed, nY=size(y, 1), verbose=verbose); else modTimRea := time; y := yFixed; retVal := 0; end if; // Check for valid return flags assert(retVal >= 0, "Obtained negative return value during data transfer with CFD.\n" + " Aborting simulation. Check CFD log file.\n" + " Received: retVal = " + String(retVal)); end when; end CFDExchange;

Buildings.ThermalZones.Detailed.BaseClasses.CFDFluidInterface Buildings.ThermalZones.Detailed.BaseClasses.CFDFluidInterface


Buildings.ThermalZones.Detailed.BaseClasses.CFDFluidInterface

Information

This model is used to connect the fluid port with the block that communicates with the CFD program.

This model also implements the pressure balance of the medium, as the FFD implementation uses a constant pressure that is independent of the pressure of the Modelica model. If the parameter massDynamics == Modelica.Fluid.Types.Dynamics.SteadyState, then there is a steady-state mass balance and the pressure of the room is an algebraic variable. Otherwise, the time derivative of the pressure is

dp⁄dt = p_start   ∑ ṁi ⁄ mstart,

where p_start is the initial pressure, ∑ ṁi is the sum of the mass flow rates over all ports, and mstart is the initial mass of the room.

Extends from Buildings.BaseClasses.BaseIcon (Base icon).

Parameters

TypeNameDefaultDescription
replaceable package MediumModelica.Media.Interfaces.Pa...Medium in the component
Densityrho_start Density, used to compute fluid mass [kg/m3]
VolumeV Volume [m3]
Dynamics
Equations
DynamicsmassDynamicsModelica.Fluid.Types.Dynamic...Formulation of mass balance
Initialization
AbsolutePressurep_startMedium.p_defaultStart value of pressure [Pa]

Connectors

TypeNameDescription
replaceable package MediumMedium in the component
input RealInputT_outflow[nPorts]Temperature if m_flow < 0 [K]
input RealInputXi_outflow[nPorts*Medium.nXi]Species concentration if m_flow < 0 [1]
input RealInputC_outflow[nPorts*Medium.nC]Trace substances if m_flow < 0
output RealOutputpRoom-averaged total pressure [Pa]
output RealOutputm_flow[nPorts]Mass flow rates [kg/s]
output RealOutputT_inflow[nPorts]Temperature if m_flow >= 0 [K]
output RealOutputXi_inflow[nPorts*Medium.nXi]Species concentration if m_flow >= 0 [1]
output RealOutputC_inflow[nPorts*Medium.nC]Trace substances if m_flow >= 0
VesselFluidPorts_bports[nPorts]Fluid inlets and outlets

Modelica definition

model CFDFluidInterface extends Buildings.BaseClasses.BaseIcon; replaceable package Medium = Modelica.Media.Interfaces.PartialMedium "Medium in the component"; // Assumptions parameter Modelica.Fluid.Types.Dynamics massDynamics=Modelica.Fluid.Types.Dynamics.DynamicFreeInitial "Formulation of mass balance"; // Initialization parameter Medium.AbsolutePressure p_start = Medium.p_default "Start value of pressure"; // Parameters for the model parameter Integer nPorts(min=0)=0 "Number of ports"; parameter Modelica.SIunits.Density rho_start "Density, used to compute fluid mass"; parameter Modelica.SIunits.Volume V "Volume"; final parameter Modelica.SIunits.Mass m_start = rho_start * V "Initial mass of air inside the room."; Modelica.Blocks.Interfaces.RealInput T_outflow[nPorts]( each start=Medium.T_default, each nominal=300, each unit="K", each displayUnit="degC") "Temperature if m_flow < 0"; Modelica.Blocks.Interfaces.RealInput Xi_outflow[nPorts*Medium.nXi]( each min=0, each max=1, each unit="1") if Medium.nXi > 0 "Species concentration if m_flow < 0"; Modelica.Blocks.Interfaces.RealInput C_outflow[nPorts*Medium.nC]( each min=0) if Medium.nC > 0 "Trace substances if m_flow < 0"; Modelica.Blocks.Interfaces.RealOutput p( start=p_start, min=80000, nominal=100000, max=120000, unit="Pa") "Room-averaged total pressure"; Modelica.Blocks.Interfaces.RealOutput m_flow[nPorts]( each quantity="MassFlowRate", each unit="kg/s") "Mass flow rates"; Modelica.Blocks.Interfaces.RealOutput T_inflow[nPorts]( each start=Medium.T_default, each min=200, each max=373.15, each nominal=300, each unit="K", each displayUnit="degC") "Temperature if m_flow >= 0"; Modelica.Blocks.Interfaces.RealOutput Xi_inflow[nPorts*Medium.nXi]( each min=0, each max=1, each unit="1") if Medium.nXi > 0 "Species concentration if m_flow >= 0"; Modelica.Blocks.Interfaces.RealOutput C_inflow[nPorts*Medium.nC]( each min=0) if Medium.nC > 0 "Trace substances if m_flow >= 0"; // Fluid port Modelica.Fluid.Vessels.BaseClasses.VesselFluidPorts_b ports[nPorts]( redeclare each final package Medium = Medium) "Fluid inlets and outlets"; protected Modelica.Blocks.Interfaces.RealOutput Xi_inflow_internal[max(nPorts, nPorts*Medium.nXi)]( each min=0, each max=1, each unit="1") "Species concentration if m_flow >= 0"; Modelica.Blocks.Interfaces.RealOutput C_inflow_internal[max(nPorts, nPorts*Medium.nC)]( each min=0) "Trace substances if m_flow >= 0"; Modelica.Blocks.Interfaces.RealInput Xi_outflow_internal[max(nPorts, nPorts*Medium.nXi)]( each min=0, each max=1, each unit="1") "Species concentration if m_flow < 0"; Modelica.Blocks.Interfaces.RealInput C_outflow_internal[max(nPorts, nPorts*Medium.nC)]( each min=0) "Trace substances if m_flow < 0"; Modelica.SIunits.MassFlowRate[Medium.nXi] mbXi_flow "Substance mass flows across boundaries"; Modelica.SIunits.MassFlowRate ports_mXi_flow[nPorts,Medium.nXi]; initial equation //Disable it for shoebox model test //assert(nPorts >= 2, "The CFD model requires at least two fluid connections."); if massDynamics == Modelica.Fluid.Types.Dynamics.FixedInitial then p = p_start; else if massDynamics == Modelica.Fluid.Types.Dynamics.SteadyStateInitial then der(p) = 0; end if; end if; equation // Internal connectors if Medium.nXi > 0 then connect(Xi_inflow_internal, Xi_inflow); connect(Xi_outflow_internal, Xi_outflow); else Xi_inflow_internal = fill(0, nPorts); Xi_outflow_internal = fill(0, nPorts); end if; if Medium.nC > 0 then connect(C_inflow_internal, C_inflow); connect(C_outflow_internal, C_outflow); else C_inflow_internal = fill(0, nPorts); C_outflow_internal = fill(0, nPorts); end if; // Mass and pressure balance of bulk volume. // The assumption is that change in temperature does not change the pressure. // Otherwise, we would need to use the BaseProperties of the medium model. for i in 1:nPorts loop ports_mXi_flow[i,:] = ports[i].m_flow * actualStream(ports[i].Xi_outflow); end for; for i in 1:Medium.nXi loop mbXi_flow[i] = sum(ports_mXi_flow[:,i]); end for; if massDynamics == Modelica.Fluid.Types.Dynamics.SteadyState then 0 = sum(ports.m_flow) + sum(mbXi_flow); else // For the change in pressure, we neglect the term sum(mbXi_flow) // as this term is small compared to sum(ports.m_flow) but it // introduces a nonlinear equation // der(p) = p_start*(sum(ports.m_flow) + sum(mbXi_flow))/m_start; der(p) = p_start*(sum(ports.m_flow))/m_start; end if; // Connection of input signals to ports. // Connect pressures. for i in 1:nPorts loop ports[i].p = p; end for; // Connect enthalpy, mass fraction and trace substances. for i in 1:nPorts loop ports[i].h_outflow = Medium.specificEnthalpy_pTX( p=p, T=T_outflow[i], X=Xi_outflow_internal[(i-1)*Medium.nXi+1:i*Medium.nXi]); ports[i].Xi_outflow = Xi_outflow_internal[(i-1)*Medium.nXi+1:i*Medium.nXi]; ports[i].C_outflow = C_outflow_internal[ (i-1)*Medium.nC +1:i*Medium.nC]; end for; // Connection of ports to output signals. for i in 1:nPorts loop m_flow[i] = ports[i].m_flow; T_inflow[i] = Medium.temperature(Medium.setState_phX( p = p, h = inStream(ports[i].h_outflow), X = inStream(ports[i].Xi_outflow))); for j in 1:Medium.nXi loop Xi_inflow_internal[(i-1)*Medium.nXi+j] = inStream(ports[i].Xi_outflow[j]); end for; for j in 1:Medium.nC loop C_inflow_internal[(i-1)*Medium.nC+j] = inStream(ports[i].C_outflow[j]); end for; end for; end CFDFluidInterface;

Buildings.ThermalZones.Detailed.BaseClasses.CFDSurfaceInterface Buildings.ThermalZones.Detailed.BaseClasses.CFDSurfaceInterface


Buildings.ThermalZones.Detailed.BaseClasses.CFDSurfaceInterface

Information

This model is used to connect temperatures and heat flow rates between the block that communicates with the CFD program and the heat port of the model that encapsulates the air heat and mass balance.

Extends from Buildings.BaseClasses.BaseIcon (Base icon).

Parameters

TypeNameDefaultDescription
CFDBoundaryConditionsbouCon Boundary condition used in the CFD simulation

Connectors

TypeNameDescription
input RealInputQ_flow_inSurface heat flow rate, used for temperature boundary condition
output RealOutputT_outSurface temperature, used for temperature boundary condition
output RealOutputQ_flow_outSurface heat flow rate, used for temperature boundary condition
input RealInputT_inSurface temperature, used for temperature boundary condition
HeatPort_aportHeat ports

Modelica definition

model CFDSurfaceInterface extends Buildings.BaseClasses.BaseIcon; parameter Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions bouCon "Boundary condition used in the CFD simulation"; Modelica.Blocks.Interfaces.RealInput Q_flow_in if bouCon == Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions.Temperature "Surface heat flow rate, used for temperature boundary condition"; Modelica.Blocks.Interfaces.RealOutput T_out if bouCon == Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions.Temperature "Surface temperature, used for temperature boundary condition"; Modelica.Blocks.Interfaces.RealOutput Q_flow_out if bouCon == Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions.HeatFlowRate "Surface heat flow rate, used for temperature boundary condition"; Modelica.Blocks.Interfaces.RealInput T_in if bouCon == Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions.HeatFlowRate "Surface temperature, used for temperature boundary condition"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a port "Heat ports"; // Internal connectors to change causality depending on the specifie // boundary condition protected Modelica.Blocks.Interfaces.RealInput Q_flow_internal "Surface heat flow rate"; Modelica.Blocks.Interfaces.RealOutput T_internal "Surface temperature"; equation connect(T_internal, T_out); connect(Q_flow_internal, Q_flow_in); connect(T_internal, T_in); connect(Q_flow_internal, Q_flow_out); T_internal = port.T; Q_flow_internal = port.Q_flow; end CFDSurfaceInterface;

Buildings.ThermalZones.Detailed.BaseClasses.CFDThread

class used to handle CFD thread

Information

Class derived from ExternalObject having two local external function definition, named destructor and constructor respectively. To fix the issue FFD fails in JModelica tests due to unsupported OS #612.

Extends from ExternalObject.

Modelica definition

class CFDThread "class used to handle CFD thread" extends ExternalObject; // constructor function constructor "allocate memeory for cosimulation variables" extends Modelica.Icons.Function; output CFDThread FFDThre "the handler of FFD thread"; external"C" FFDThre = cfdcosim(); end constructor; // destructor function destructor "release ffd.dll or ffd.so" extends Modelica.Icons.Function; input CFDThread FFDThre "the handler of FFD thread"; external"C" cfdSendStopCommand(FFDThre); end destructor; end CFDThread;

Buildings.ThermalZones.Detailed.BaseClasses.ExteriorBoundaryConditions Buildings.ThermalZones.Detailed.BaseClasses.ExteriorBoundaryConditions

Model for convection and radiation bounary condition of exterior constructions

Buildings.ThermalZones.Detailed.BaseClasses.ExteriorBoundaryConditions

Information

This model computes the boundary conditions for the outside-facing surface of opaque constructions.

The model computes the infrared, solar, and convective heat exchange between these surfaces and the exterior temperature and the sky temperature. Input into this model are weather data that may be obtained from Buildings.BoundaryConditions.WeatherData.

In this model, the solar radiation data are converted from horizontal irradiation to irradiation on tilted surfaces using models from the package Buildings.BoundaryConditions.SolarIrradiation. The convective heat transfer between the exterior surface of the opaque constructions is computed using Buildings.HeatTransfer.Convection.

The heat transfer of windows are not computed in this model. They are implemented in Buildings.ThermalZones.Detailed.BaseClasses.ExteriorBoundaryConditionsWithWindow.

Parameters

TypeNameDefaultDescription
Anglelat Latitude [rad]
BooleanlinearizeRadiation Set to true to linearize emissive power
ParameterConstructionconPar[nCon]redeclare parameter Paramete...Records for construction
Exterior constructions
IntegernCon Number of exterior constructions
Convective heat transfer
ExteriorConvectionconModBuildings.HeatTransfer.Types...Convective heat transfer model for opaque part of the constructions
CoefficientOfHeatTransferhFixed10.0Constant convection coefficient for opaque part of the constructions [W/(m2.K)]

Connectors

TypeNameDescription
HeatPort_aopa_a[nCon]Heat port at surface a of opaque construction
BusweaBus 

Modelica definition

model ExteriorBoundaryConditions "Model for convection and radiation bounary condition of exterior constructions" parameter Integer nCon(min=1) "Number of exterior constructions"; parameter Modelica.SIunits.Angle lat "Latitude"; parameter Boolean linearizeRadiation "Set to true to linearize emissive power"; replaceable parameter ParameterConstruction conPar[nCon] constrainedby ParameterConstruction "Records for construction"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a opa_a[nCon] "Heat port at surface a of opaque construction"; parameter Buildings.HeatTransfer.Types.ExteriorConvection conMod= Buildings.HeatTransfer.Types.ExteriorConvection.TemperatureWind "Convective heat transfer model for opaque part of the constructions"; parameter Modelica.SIunits.CoefficientOfHeatTransfer hFixed=10.0 "Constant convection coefficient for opaque part of the constructions"; // The convection coefficients are not final to allow a user to individually // assign them. // We reassign the tilt since a roof has been declared in the room model as the // ceiling (of the room) HeatTransfer.Convection.Exterior conOpa[nCon]( A=AOpa, final til=Modelica.Constants.pi*ones(nCon) .- conPar[:].til, final azi=conPar[:].azi, each conMod=conMod, each hFixed=hFixed) "Convection model for opaque part of the wall"; SkyRadiationExchange skyRadExc( final n=nCon, final A=AOpa, final absIR=conPar[:].layers.absIR_a, vieFacSky={(Modelica.Constants.pi - conPar[i].til)./Modelica.Constants.pi for i in 1:nCon}) "Infrared radiative heat exchange with sky"; BoundaryConditions.WeatherData.Bus weaBus; BoundaryConditions.SolarIrradiation.DirectTiltedSurface HDirTil[ nCon]( each final lat=lat, final til=conPar[:].til, final azi=conPar[:].azi) "Direct solar irradiation on the surface"; BoundaryConditions.SolarIrradiation.DiffusePerez HDifTil[nCon]( each final lat=lat, final til=conPar[:].til, final azi=conPar[:].azi) "Diffuse solar irradiation"; Modelica.Blocks.Math.Add HTotConExt[nCon]( final k1=conPar[:].layers.absSol_a .* AOpa, final k2=conPar[:].layers.absSol_a .* AOpa) "Total solar irradiation"; Buildings.HeatTransfer.Sources.PrescribedHeatFlow solHeaGaiConExt[nCon] "Total solar heat gain of the surface"; protected parameter Modelica.SIunits.Area AOpa[nCon]=conPar[:].A "Area of opaque construction"; Buildings.HeatTransfer.Sources.PrescribedTemperature TAirConExt[ nCon] "Outside air temperature for exterior constructions"; Modelica.Blocks.Routing.Replicator repConExt(nout=nCon) "Signal replicator"; Modelica.Blocks.Routing.Replicator repConExt1( nout=nCon) "Signal replicator"; Modelica.Blocks.Routing.Replicator repConExt2( nout=nCon) "Signal replicator"; equation connect(conOpa.solid, opa_a); connect(skyRadExc.port, opa_a); connect(TAirConExt.port, conOpa.fluid); connect(repConExt.y, TAirConExt.T); connect(repConExt.u, weaBus.TDryBul); connect(skyRadExc.TOut, weaBus.TDryBul); connect(skyRadExc.TBlaSky, weaBus.TBlaSky); for i in 1:nCon loop connect(weaBus, HDirTil[i].weaBus); connect(HDifTil[i].weaBus, weaBus); end for; connect(HTotConExt.y, solHeaGaiConExt.Q_flow); connect(solHeaGaiConExt.port, opa_a); connect(HDirTil.H, HTotConExt.u1); connect(HDifTil.H, HTotConExt.u2); connect(repConExt2.u, weaBus.winDir); connect(repConExt1.u, weaBus.winSpe); connect(repConExt1.y, conOpa.v); connect(repConExt2.y, conOpa.dir); end ExteriorBoundaryConditions;

Buildings.ThermalZones.Detailed.BaseClasses.ExteriorBoundaryConditionsWithWindow Buildings.ThermalZones.Detailed.BaseClasses.ExteriorBoundaryConditionsWithWindow

Model for exterior boundary conditions for constructions with a window

Buildings.ThermalZones.Detailed.BaseClasses.ExteriorBoundaryConditionsWithWindow

Information

This model computes the boundary conditions for the outside-facing surface of opaque constructions and of windows.

The model computes the infrared, solar, and convective heat exchange between these surfaces and the exterior temperature and the sky temperature. Input into this model are weather data that may be obtained from Buildings.BoundaryConditions.WeatherData.

This model extends Buildings.ThermalZones.Detailed.BaseClasses.ExteriorBoundaryConditions, which models the boundary conditions for the opaque constructions, and then implements the boundary condition for windows by using the model Buildings.HeatTransfer.Windows.ExteriorHeatTransfer.

Extends from Buildings.ThermalZones.Detailed.BaseClasses.ExteriorBoundaryConditions (Model for convection and radiation bounary condition of exterior constructions).

Parameters

TypeNameDefaultDescription
Anglelat Latitude [rad]
BooleanlinearizeRadiation Set to true to linearize emissive power
Exterior constructions
IntegernCon Number of exterior constructions
Convective heat transfer
ExteriorConvectionconModBuildings.HeatTransfer.Types...Convective heat transfer model for opaque part of the constructions
CoefficientOfHeatTransferhFixed10.0Constant convection coefficient for opaque part of the constructions [W/(m2.K)]

Connectors

TypeNameDescription
HeatPort_aopa_a[nCon]Heat port at surface a of opaque construction
BusweaBus 
input RealInputuSha[nCon]Control signal for the shading device, 0: unshaded; 1: fully shaded
input RealInputQAbsSolSha_flow[nCon]Solar radiation absorbed by shade [W]
output RadiosityOutflowJOutUns[nCon]Outgoing radiosity that connects to unshaded part of glass at exterior side [W]
input RadiosityInflowJInUns[nCon]Incoming radiosity that connects to unshaded part of glass at exterior side [W]
output RadiosityOutflowJOutSha[nCon]Outgoing radiosity that connects to shaded part of glass at exterior side [W]
input RadiosityInflowJInSha[nCon]Incoming radiosity that connects to shaded part of glass at exterior side [W]
HeatPort_aglaUns[nCon]Heat port at unshaded glass of exterior-facing surface
HeatPort_aglaSha[nCon]Heat port at shaded glass of exterior-facing surface
HeatPort_afra[nCon]Heat port at frame of exterior-facing surface
output RealOutputHDir[nCon]Direct solar irradition on tilted surface [W/m2]
output RealOutputHDif[nCon]Diffuse solar irradiation on tilted surface [W/m2]
output RealOutputinc[nCon]Incidence angle [rad]

Modelica definition

model ExteriorBoundaryConditionsWithWindow "Model for exterior boundary conditions for constructions with a window" extends Buildings.ThermalZones.Detailed.BaseClasses.ExteriorBoundaryConditions ( final AOpa=conPar[:].AOpa, redeclare Buildings.ThermalZones.Detailed.BaseClasses.ParameterConstructionWithWindow conPar); final parameter Modelica.SIunits.Area AWin[nCon] = conPar[:].hWin .* conPar[:].wWin "Window area"; final parameter Boolean haveExteriorShade[nCon] = conPar[:].glaSys.haveExteriorShade "Set to true if window has exterior shade (at surface a)"; final parameter Boolean haveInteriorShade[nCon] = conPar[:].glaSys.haveInteriorShade "Set to true if window has interior shade (at surface b)"; final parameter Boolean haveShade= Modelica.Math.BooleanVectors.anyTrue(haveExteriorShade) or Modelica.Math.BooleanVectors.anyTrue(haveInteriorShade) "Set to true if window system has a shade"; final parameter Boolean haveOverhangOrSideFins= Modelica.Math.BooleanVectors.anyTrue(conPar.haveOverhangOrSideFins) "Flag, true if the room has at least one window with either an overhang or side fins"; Buildings.HeatTransfer.Windows.FixedShade sha[nCon]( final conPar=conPar, each lat=lat, azi=conPar.azi) if haveOverhangOrSideFins "Shade due to overhang or side fins"; Modelica.Blocks.Interfaces.RealInput uSha[nCon]( each min=0, each max=1) if haveShade "Control signal for the shading device, 0: unshaded; 1: fully shaded"; Modelica.Blocks.Interfaces.RealInput QAbsSolSha_flow[nCon]( each final unit="W", each quantity="Power") "Solar radiation absorbed by shade"; HeatTransfer.Windows.ExteriorHeatTransfer conExtWin[nCon]( final A=conPar[:].AWin, final fFra=conPar[:].fFra, each final linearizeRadiation = linearizeRadiation, final vieFacSky={(Modelica.Constants.pi - conPar[i].til) ./ Modelica.Constants.pi for i in 1:nCon}, final absIRSha_air=conPar[:].glaSys.shade.absIR_a, final absIRSha_glass=conPar[:].glaSys.shade.absIR_b, final tauIRSha_air=conPar[:].glaSys.shade.tauIR_a, final tauIRSha_glass=conPar[:].glaSys.shade.tauIR_b, final haveExteriorShade=haveExteriorShade, final haveInteriorShade=haveInteriorShade) "Exterior convection of the window"; SkyRadiationExchange skyRadExcWin( final n=nCon, final absIR=conPar[:].glaSys.absIRFra, vieFacSky={(Modelica.Constants.pi - conPar[i].til) ./ Modelica.Constants.pi for i in 1:nCon}, final A=conPar[:].AWin .* conPar[:].fFra) "Infrared radiative heat exchange between window frame and sky"; HeatTransfer.Interfaces.RadiosityOutflow JOutUns[nCon] "Outgoing radiosity that connects to unshaded part of glass at exterior side"; HeatTransfer.Interfaces.RadiosityInflow JInUns[nCon] "Incoming radiosity that connects to unshaded part of glass at exterior side"; HeatTransfer.Interfaces.RadiosityOutflow JOutSha[nCon] if haveShade "Outgoing radiosity that connects to shaded part of glass at exterior side"; HeatTransfer.Interfaces.RadiosityInflow JInSha[nCon] if haveShade "Incoming radiosity that connects to shaded part of glass at exterior side"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a glaUns[nCon] "Heat port at unshaded glass of exterior-facing surface"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a glaSha[nCon] if haveShade "Heat port at shaded glass of exterior-facing surface"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a fra[nCon]( each T(nominal=300, start=283.15)) "Heat port at frame of exterior-facing surface"; Modelica.Blocks.Math.Add HTotConExtWinFra[nCon]( final k1=conPar[:].fFra .* conPar[:].glaSys.absSolFra .* conPar[:].AWin, final k2=conPar[:].fFra .* conPar[:].glaSys.absSolFra .* conPar[:].AWin) "Total solar irradiation on window frame"; Buildings.HeatTransfer.Sources.PrescribedHeatFlow solHeaGaiConWin[nCon] "Total solar heat gain of the window frame"; Modelica.Blocks.Interfaces.RealOutput HDir[nCon]( each final quantity="RadiantEnergyFluenceRate", each final unit="W/m2") "Direct solar irradition on tilted surface"; Modelica.Blocks.Interfaces.RealOutput HDif[nCon]( each final quantity="RadiantEnergyFluenceRate", each final unit="W/m2") "Diffuse solar irradiation on tilted surface"; Modelica.Blocks.Interfaces.RealOutput inc[nCon]( each final quantity="Angle", each final unit="rad", each displayUnit="deg") "Incidence angle"; protected Buildings.HeatTransfer.Sources.PrescribedTemperature TAirConExtWin[ nCon] "Outside air temperature for window constructions"; Modelica.Blocks.Routing.Replicator repConExtWin(final nout=nCon) "Signal replicator"; Modelica.Blocks.Routing.Replicator repConExtWinVWin(final nout=nCon) "Signal replicator"; Modelica.Blocks.Routing.Replicator repConExtWinTSkyBla(final nout=nCon) "Signal replicator"; equation connect(uSha, conExtWin.uSha); connect(JInUns,conExtWin. JInUns); connect(conExtWin.JOutUns,JOutUns); connect(conExtWin.glaUns,glaUns); connect(conExtWin.glaSha,glaSha); connect(conExtWin.JOutSha,JOutSha); connect(conExtWin.JInSha,JInSha); connect(conExtWin.frame,fra); connect(TAirConExtWin.port,conExtWin. air); connect(TAirConExtWin.T,repConExtWin. y); connect(repConExtWin.u, weaBus.TDryBul); connect(repConExtWinVWin.y,conExtWin. vWin); connect(repConExtWinVWin.u, weaBus.winSpe); connect(HTotConExtWinFra.y, solHeaGaiConWin.Q_flow); connect(solHeaGaiConWin.port, fra); connect(HDifTil.H, HDif); connect(HDirTil.inc, inc); connect(HTotConExtWinFra.u2, HDifTil.H); connect(skyRadExcWin.TOut, weaBus.TDryBul); connect(skyRadExcWin.TBlaSky, weaBus.TBlaSky); connect(skyRadExcWin.port, fra); connect(repConExtWin.y, conExtWin.TOut); connect(repConExtWinTSkyBla.y, conExtWin.TBlaSky); connect(repConExtWinTSkyBla.u, weaBus.TBlaSky); for i in 1:nCon loop connect(sha[i].weaBus, weaBus); end for; connect(HDirTil.inc, sha.incAng); // OpenModelica does not remove the connect statement if conExtWin.QSolAbs_flow // is removed. if haveShade then connect(QAbsSolSha_flow, conExtWin.QSolAbs_flow); end if; connect(sha.HDirTilUns, HDirTil.H); if haveOverhangOrSideFins then connect(sha.HDirTil, HTotConExtWinFra.u1); connect(sha.HDirTil, HDir); else connect(HDirTil.H, HTotConExtWinFra.u1); connect(HDirTil.H, HDir); end if; end ExteriorBoundaryConditionsWithWindow;

Buildings.ThermalZones.Detailed.BaseClasses.HeatGain Buildings.ThermalZones.Detailed.BaseClasses.HeatGain

Model to convert internal heat gain signals

Buildings.ThermalZones.Detailed.BaseClasses.HeatGain

Information

This model computes the radiant, convective sensible and latent heat flow rate. Input into this model are these three components in units of [W/m2]. The inputs need to be positive quantities if heat or moisture is added to the room. The outputs are

Extends from Buildings.BaseClasses.BaseIcon (Base icon).

Parameters

TypeNameDefaultDescription
AreaAFlo Floor area [m2]

Connectors

TypeNameDescription
input RealInputqGai_flow[3]Radiant, convective sensible and latent heat input into room (positive if heat gain)
output RealOutputQRad_flowRadiant heat input into room (positive if heat gain) [W]
output RealOutputQCon_flowConvective sensible heat input into room (positive if heat gain) [W]
output RealOutputQLat_flowLatent heat input into room (positive if heat gain) [W]

Modelica definition

model HeatGain "Model to convert internal heat gain signals" extends Buildings.BaseClasses.BaseIcon; parameter Modelica.SIunits.Area AFlo "Floor area"; Modelica.Blocks.Interfaces.RealInput qGai_flow[3] "Radiant, convective sensible and latent heat input into room (positive if heat gain)"; Modelica.Blocks.Interfaces.RealOutput QRad_flow(unit="W") "Radiant heat input into room (positive if heat gain)"; Modelica.Blocks.Interfaces.RealOutput QCon_flow(unit="W") "Convective sensible heat input into room (positive if heat gain)"; Modelica.Blocks.Interfaces.RealOutput QLat_flow(unit="W") "Latent heat input into room (positive if heat gain)"; equation {QRad_flow, QCon_flow, QLat_flow} = AFlo .* qGai_flow; end HeatGain;

Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationExchange Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationExchange

Infrared radiation heat exchange between the room facing surfaces

Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationExchange

Information

This model computes the infrared radiative heat transfer between the interior surfaces of a room. Each opaque surface emits radiation according to

Ei = σ   Ai   εi   (Ti)4,

where σ is the Stefan-Boltzmann constant, Ai is the surface area, εi is the absorptivity in the infrared spectrum, and Ti is the surface temperature. If the parameter linearizeRadidation is set to true, then the term (Ti)4 is replaced with T03 Ti, where T0 = 20°C is a parameter.

The incoming radiation at surface i is

Gi = -∑j   Fj,i   Jj

where Fj,i is the view factor from surface j to surface i, Jj is the radiosity leaving surface j and the sum is over all surfaces. For opaque surfaces, it follows from the first law that the radiosity Ji is

Ji = -Ei - (1-εi)   Gi.

For windows, the outgoing radiosity is an input into this model because the window model computes this quantity directly.

For each surface i, the heat balance is

0 = Qi + Ji + Gi.

For opaque surfaces, the heat flow rate Qi is set to be equal to the heat flow rate at the heat port. For the glass of the windows, the radiosity outflow at the connector is set to the radiosity Gi that is leaving the surface.

The view factor from surface i to j is approximated as

Fi,j = Aj ⁄ ∑k Ak.

Extends from Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterfaceRadiative (Partial model that is used for infrared radiation balance).

Parameters

TypeNameDefaultDescription
ParameterConstructiondatConExt[NConExt] Data for exterior construction
ParameterConstructionWithWindowdatConExtWin[NConExtWin] Data for exterior construction with window
ParameterConstructiondatConPar[NConPar] Data for partition construction
ParameterConstructiondatConBou[NConBou] Data for construction boundary
OpaqueSurfacesurBou[NSurBou] Record for data of surfaces whose heat conduction is modeled outside of this room
Brick120dummyCon Dummy construction to assign a parameter to the instance
SingleClear3dummyGlaSys Dummy construction to assign a parameter to the instance
BooleanlinearizeRadiation Set to true to linearize emissive power
Exterior constructions
IntegernConExt Number of exterior constructions
IntegernConExtWin Number of window constructions
Partition constructions
IntegernConPar Number of partition constructions
Boundary constructions
IntegernConBou Number of constructions that have their outside surface exposed to the boundary of this room
IntegernSurBou Number of surface heat transfer models that connect to constructions that are modeled outside of this room
Experimental (may be changed in future releases)
BooleansampleModelfalseSet to true to time-sample the model, which can give shorter simulation time if there is already time sampling in the system model

Connectors

TypeNameDescription
HeatPort_aconExt[NConExt]Heat port that connects to room-side surface of exterior constructions
HeatPort_aconExtWin[NConExtWin]Heat port that connects to room-side surface of exterior constructions that contain a window
HeatPort_aconExtWinFra[NConExtWin]Heat port that connects to room-side surface of window frame
HeatPort_aconPar_a[NConPar]Heat port that connects to room-side surface a of partition constructions
HeatPort_aconPar_b[NConPar]Heat port that connects to room-side surface b of partition constructions
HeatPort_aconBou[NConBou]Heat port that connects to room-side surface of constructions that expose their other surface to the outside
HeatPort_aconSurBou[NSurBou]Heat port to surfaces of models that compute the heat conduction outside of this room
input RadiosityInflowJInConExtWin[NConExtWin]Incoming radiosity that connects to non-frame part of the window [W]
output RadiosityOutflowJOutConExtWin[NConExtWin]Outgoing radiosity that connects to non-frame part of the window [W]

Modelica definition

model InfraredRadiationExchange "Infrared radiation heat exchange between the room facing surfaces" extends Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterfaceRadiative; constant Boolean homotopyInitialization = true "= true, use homotopy method"; parameter Boolean linearizeRadiation "Set to true to linearize emissive power"; parameter Boolean sampleModel=false "Set to true to time-sample the model, which can give shorter simulation time if there is already time sampling in the system model"; HeatTransfer.Interfaces.RadiosityInflow JInConExtWin[NConExtWin] if haveConExtWin "Incoming radiosity that connects to non-frame part of the window"; HeatTransfer.Interfaces.RadiosityOutflow JOutConExtWin[NConExtWin] "Outgoing radiosity that connects to non-frame part of the window"; protected constant Real T30(unit="K3") = 293.15^3 "Nominal temperature"; constant Real T40(unit="K4") = 293.15^4 "Nominal temperature"; final parameter Integer NOpa=NConExt + 2*NConExtWin + 2*NConPar + NConBou + NSurBou "Number of opaque surfaces, including the window frame"; final parameter Integer nOpa=nConExt + 2*nConExtWin + 2*nConPar + nConBou + nSurBou "Number of opaque surfaces, including the window frame"; final parameter Integer NWin=NConExtWin "Number of window surfaces"; final parameter Integer nWin=nConExtWin "Number of window surfaces"; final parameter Integer NTot=NOpa + NWin "Total number of surfaces"; final parameter Integer nTot=nOpa + nWin "Total number of surfaces"; final parameter Real epsOpa[nOpa]( each min=0, each max=1, each fixed=false) "Absorptivity of opaque surfaces"; final parameter Real rhoOpa[nOpa]( each min=0, each max=1, each fixed=false) "Reflectivity of opaque surfaces"; final parameter Modelica.SIunits.Area AOpa[nOpa](each fixed=false) "Surface area of opaque surfaces"; final parameter Modelica.SIunits.Area A[nTot](each fixed=false) "Surface areas"; final parameter Real kOpa[nOpa](each unit="W/K4", each fixed=false) "Product sigma*epsilon*A for opaque surfaces"; final parameter Real kOpaInv[nOpa](each unit="K4/W", each fixed=false) "Inverse of kOpa, used to avoid having to use a safe division"; final parameter Real F[nTot, nTot]( each min=0, each max=1, each fixed=false) "View factor from surface i to j"; parameter Modelica.SIunits.Time t0(fixed=false) "First sample time instant"; Buildings.HeatTransfer.Interfaces.RadiosityInflow JInConExtWin_internal[ NConExtWin](start=AConExtWinGla*0.8*Modelica.Constants.sigma*293.15^4, each fixed=sampleModel and nConExtWin > 0) "Incoming radiosity that connects to non-frame part of the window"; Modelica.SIunits.HeatFlowRate J[nTot]( each max=0, start=-A .* 0.8*Modelica.Constants.sigma*293.15^4, fixed={sampleModel and (i <= nOpa or i > nOpa + nWin) for i in 1:nTot}, each nominal=10*0.8*Modelica.Constants.sigma*293.15^4) "Radiosity leaving the surface"; Modelica.SIunits.HeatFlowRate G[nTot]( each min=0, start=A .* 0.8*Modelica.Constants.sigma*293.15^4, each nominal=10*0.8*Modelica.Constants.sigma*293.15^4) "Radiosity entering the surface"; Modelica.SIunits.Temperature TOpa[nOpa](each start=293.15, each nominal= 293.15) "Temperature of opaque surfaces"; Real T4Opa[nOpa]( each unit="K4", each start=T40, each nominal=293.15^4) "Forth power of temperature of opaque surfaces"; Modelica.SIunits.HeatFlowRate Q_flow[nTot](each start=0, each fixed= sampleModel) "Heat flow rate at surfaces"; parameter Modelica.SIunits.Temperature T0=293.15 "Temperature used to linearize radiative heat transfer"; final parameter Real T03( min=0, unit="K3") = T0^3 "3rd power of temperature T0"; Modelica.SIunits.HeatFlowRate sumEBal(start=0, fixed=sampleModel) "Sum of energy balance, should be zero"; initial equation assert(homotopyInitialization, "In " + getInstanceName() + ": The constant homotopyInitialization has been modified from its default value. This constant will be removed in future releases.", level = AssertionLevel.warning); // The next loops build the array epsOpa, AOpa and kOpa that simplify // the model equations. // These arrays store the values of the constructios in the following order // [x[1:NConExt] x[1:NConPar] x[1: NConPar] x[1: NConBou] x[1: NSurBou] x[1: NConExtWin] x[1: NConExtWin]] // where x is epsOpa, AOpa or kOpa. // The last two entries are for the opaque wall that contains a window, and for the window frame. for i in 1:nConExt loop epsOpa[i] = epsConExt[i]; AOpa[i] = AConExt[i]; kOpa[i] = Modelica.Constants.sigma*epsConExt[i]*AOpa[i]; end for; for i in 1:nConPar loop epsOpa[i + nConExt] = epsConPar_a[i]; AOpa[i + nConExt] = AConPar[i]; kOpa[i + nConExt] = Modelica.Constants.sigma*epsConPar_a[i]*AOpa[i + nConExt]; epsOpa[i + nConExt + nConPar] = epsConPar_b[i]; AOpa[i + nConExt + nConPar] = AConPar[i]; kOpa[i + nConExt + nConPar] = Modelica.Constants.sigma*epsConPar_b[i]*AOpa[ i + nConExt + nConPar]; end for; for i in 1:nConBou loop epsOpa[i + nConExt + 2*nConPar] = epsConBou[i]; AOpa[i + nConExt + 2*nConPar] = AConBou[i]; kOpa[i + nConExt + 2*nConPar] = Modelica.Constants.sigma*epsConBou[i]*AOpa[ i + nConExt + 2*nConPar]; end for; for i in 1:nSurBou loop epsOpa[i + nConExt + 2*nConPar + nConBou] = epsSurBou[i]; AOpa[i + nConExt + 2*nConPar + nConBou] = ASurBou[i]; kOpa[i + nConExt + 2*nConPar + nConBou] = Modelica.Constants.sigma* epsSurBou[i]*AOpa[i + nConExt + 2*nConPar + nConBou]; end for; for i in 1:nConExtWin loop // Opaque part of construction that has a window embedded epsOpa[i + nConExt + 2*nConPar + nConBou + nSurBou] = epsConExtWinOpa[i]; AOpa[i + nConExt + 2*nConPar + nConBou + nSurBou] = AConExtWinOpa[i]; kOpa[i + nConExt + 2*nConPar + nConBou + nSurBou] = Modelica.Constants.sigma *epsConExtWinOpa[i]*AOpa[i + nConExt + 2*nConPar + nConBou + nSurBou]; // Window frame epsOpa[i + nConExt + 2*nConPar + nConBou + nSurBou + nConExtWin] = epsConExtWinFra[i]; AOpa[i + nConExt + 2*nConPar + nConBou + nSurBou + nConExtWin] = AConExtWinFra[i]; kOpa[i + nConExt + 2*nConPar + nConBou + nSurBou + nConExtWin] = Modelica.Constants.sigma *epsConExtWinFra[i]*AOpa[i + nConExt + 2*nConPar + nConBou + nSurBou + nConExtWin]; end for; // Vector with all surface areas. // The next loops build the array A that simplifies // the model equations. // These array stores the values of the constructios in the following order // [AOpa[1:nConExt] AOpa[1:nConPar] AOpa[1: nConPar] AOpa[1: nConBou] AOpa[1: nSurBou] // AOpa[1: nConExtWin] AOpa[1: nConExtWin] AGla[1: nConExtWin]] // since nWin=nConExtWin. for i in 1:nOpa loop A[i] = AOpa[i]; end for; for i in 1:nWin loop A[i + nOpa] = AConExtWinGla[i]; end for; // Reflectivity for opaque surfaces rhoOpa = 1 .- epsOpa; // View factors from surface i to surface j for i in 1:nTot loop for j in 1:nTot loop F[i, j] = A[j]/sum((A[k]) for k in 1:nTot); end for; end for; for i in 1:nOpa loop kOpaInv[i] = 1/kOpa[i]; end for; // Test whether the view factors add up to one, or the sum is zero in case there // is only one construction for i in 1:nTot loop assert((abs(1 - sum(F[i, j] for j in 1:nTot))) < 1E-10, "Program error: Sum 1 of view factors is " + String(sum(F[i, j] for j in 1:nTot))); end for; t0 = time; //////////////////////////////////////////////////////////////////// equation // Conditional connector connect(JInConExtWin, JInConExtWin_internal); if not haveConExtWin then JInConExtWin_internal = fill(0, NConExtWin); end if; // Assign temperature of opaque surfaces for i in 1:nConExt loop TOpa[i] = conExt[i].T; end for; for i in 1:nConPar loop TOpa[i + nConExt] = conPar_a[i].T; TOpa[i + nConExt + nConPar] = conPar_b[i].T; end for; for i in 1:nConBou loop TOpa[i + nConExt + 2*nConPar] = conBou[i].T; end for; for i in 1:nSurBou loop TOpa[i + nConExt + 2*nConPar + nConBou] = conSurBou[i].T; end for; for i in 1:nConExtWin loop TOpa[i + nConExt + 2*nConPar + nConBou + nSurBou] = conExtWin[i].T; TOpa[i + nConExt + 2*nConPar + nConBou + nConExtWin + nSurBou] = conExtWinFra[i].T; end for; // Incoming radiosity at each surface // is equal to the negative of the outgoing radiosity of // all other surfaces times the view factor if sampleModel then // experimental mode to sample the model which can give shorter // simulation time if there is already a sampling in the system model when sample(t0, 2*60) then G = -transpose(F)*pre(J); // Net heat exchange Q_flow = -pre(J) - G; // Outgoing radiosity // Sum of energy balance // Remove sumEBal and assert statement for final release sumEBal = sum(conExt.Q_flow) + sum(conPar_a.Q_flow) + sum(conPar_b.Q_flow) + sum(conBou.Q_flow) + sum(conSurBou.Q_flow) + sum(conExtWin.Q_flow) + sum(conExtWinFra.Q_flow) + (sum(JInConExtWin_internal) - sum( JOutConExtWin)); end when; else G = -transpose(F)*J; // Net heat exchange Q_flow = -J - G; // Outgoing radiosity // Sum of energy balance // Remove sumEBal and assert statement for final release sumEBal = sum(conExt.Q_flow) + sum(conPar_a.Q_flow) + sum(conPar_b.Q_flow) + sum(conBou.Q_flow) + sum(conSurBou.Q_flow) + sum(conExtWin.Q_flow) + sum(conExtWinFra.Q_flow) + (sum(JInConExtWin_internal) - sum( JOutConExtWin)); assert(abs(sumEBal) < 1E-1, "Program error: Energy is not conserved in InfraredRadiationExchange. Sum of all energy is " + String(sumEBal)); end if; // Opaque surfaces. // If kOpa[j]=absIR[j]*A[j] < 1E-28, then A < 1E-20 and the surface is // from a dummy construction. In this situation, we set T40=293.15^4 to // avoid a singularity. for j in 1:nOpa loop // T4Opa[j] = if (kOpa[j] > 1E-28) then (Q_flow[j]-epsOpa[j] * G[j])/kOpa[j] else T40; T4Opa[j] = (-J[j] - rhoOpa[j]*G[j])*kOpaInv[j]; end for; // 4th power of temperature if linearizeRadiation then TOpa = (T4Opa .+ 3*T40)/(4*T30); // Based on T4 = 4*T30*T-3*T40 else if homotopyInitialization then TOpa = homotopy(actual=Buildings.Utilities.Math.Functions.powerLinearized( x=T4Opa, x0=243.15^4, n=0.25), simplified=(T4Opa .+ 3*T40)/(4*T30)); else TOpa = Buildings.Utilities.Math.Functions.powerLinearized( x=T4Opa, x0=243.15^4, n=0.25); end if; end if; // Assign radiosity that comes from window // and that leaves window. // J < 0 because it leaves the surface // G > 0 because it strikes the surface for j in 1:nWin loop J[j + nOpa] = -JInConExtWin_internal[j]; G[j + nOpa] = +JOutConExtWin[j]; end for; // Assign heat exchange to connectors for i in 1:nConExt loop Q_flow[i] = conExt[i].Q_flow; end for; if nConExt == 0 then conExt[1].T = T0; end if; for i in 1:nConPar loop Q_flow[i + nConExt] = conPar_a[i].Q_flow; Q_flow[i + nConExt + nConPar] = conPar_b[i].Q_flow; end for; if nConPar == 0 then conPar_a[1].T = T0; conPar_b[1].T = T0; end if; for i in 1:nConBou loop Q_flow[i + nConExt + 2*nConPar] = conBou[i].Q_flow; end for; if nConBou == 0 then conBou[1].T = T0; end if; for i in 1:nSurBou loop Q_flow[i + nConExt + 2*nConPar + nConBou] = conSurBou[i].Q_flow; end for; if nSurBou == 0 then conSurBou[1].T = T0; end if; for i in 1:nConExtWin loop Q_flow[i + nConExt + 2*nConPar + nConBou + nSurBou] = conExtWin[i].Q_flow; Q_flow[i + nConExt + 2*nConPar + nConBou + nSurBou + nConExtWin] = conExtWinFra[i].Q_flow; end for; if nConExtWin == 0 then conExtWin[1].T = T0; conExtWinFra[1].T = T0; JOutConExtWin[1] = 0; end if; end InfraredRadiationExchange;

Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationGainDistribution Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationGainDistribution

Infrared radiative heat gain distribution between the room facing surfaces

Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationGainDistribution

Information

This model computes the distribution of the infrared radiant heat gain to the room surfaces. The infrared radiant heat gain Q is an input to this model. It is distributed to the individual surfaces according to

Qi = Q   Ai   εi ⁄ ∑k Ak   εk.

For opaque surfaces, the heat flow rate Qi is set to be equal to the heat flow rate at the heat port. For the glass of the windows, the heat flow rate Qi is set to the radiosity Ji that will strike the glass or the window shade.

Extends from Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterfaceRadiative (Partial model that is used for infrared radiation balance).

Parameters

TypeNameDefaultDescription
ParameterConstructiondatConExt[NConExt] Data for exterior construction
ParameterConstructionWithWindowdatConExtWin[NConExtWin] Data for exterior construction with window
ParameterConstructiondatConPar[NConPar] Data for partition construction
ParameterConstructiondatConBou[NConBou] Data for construction boundary
OpaqueSurfacesurBou[NSurBou] Record for data of surfaces whose heat conduction is modeled outside of this room
Brick120dummyCon Dummy construction to assign a parameter to the instance
SingleClear3dummyGlaSys Dummy construction to assign a parameter to the instance
BooleanhaveShade Set to true if a shade is present
Exterior constructions
IntegernConExt Number of exterior constructions
IntegernConExtWin Number of window constructions
Partition constructions
IntegernConPar Number of partition constructions
Boundary constructions
IntegernConBou Number of constructions that have their outside surface exposed to the boundary of this room
IntegernSurBou Number of surface heat transfer models that connect to constructions that are modeled outside of this room

Connectors

TypeNameDescription
HeatPort_aconExt[NConExt]Heat port that connects to room-side surface of exterior constructions
HeatPort_aconExtWin[NConExtWin]Heat port that connects to room-side surface of exterior constructions that contain a window
HeatPort_aconExtWinFra[NConExtWin]Heat port that connects to room-side surface of window frame
HeatPort_aconPar_a[NConPar]Heat port that connects to room-side surface a of partition constructions
HeatPort_aconPar_b[NConPar]Heat port that connects to room-side surface b of partition constructions
HeatPort_aconBou[NConBou]Heat port that connects to room-side surface of constructions that expose their other surface to the outside
HeatPort_aconSurBou[NSurBou]Heat port to surfaces of models that compute the heat conduction outside of this room
input RealInputuSha[NConExtWin]Control signal for the shading device (removed if no shade is present)
input RealInputQ_flowRadiative heat input into room (positive if heat gain)
output RadiosityOutflowJOutConExtWin[NConExtWin]Outgoing radiosity that connects to shaded and unshaded part of glass [W]

Modelica definition

model InfraredRadiationGainDistribution "Infrared radiative heat gain distribution between the room facing surfaces" extends Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterfaceRadiative; parameter Boolean haveShade "Set to true if a shade is present"; Modelica.Blocks.Interfaces.RealInput uSha[NConExtWin](each min=0, each max=1) if haveShade "Control signal for the shading device (removed if no shade is present)"; Modelica.Blocks.Interfaces.RealInput Q_flow "Radiative heat input into room (positive if heat gain)"; Buildings.HeatTransfer.Interfaces.RadiosityOutflow[NConExtWin] JOutConExtWin "Outgoing radiosity that connects to shaded and unshaded part of glass"; protected Real fraConExt[NConExt] = AEpsConExt*sumAEpsInv "Fraction of infrared radiant heat gain absorbed by exterior constructions"; Real fraConExtWinOpa[NConExtWin] = AEpsConExtWinOpa*sumAEpsInv "Fraction of infrared radiant heat gain absorbed by opaque part of exterior constructions that have a window"; Real fraConExtWinGla[NConExtWin] = (AEpsConExtWinSha + AEpsConExtWinUns)*sumAEpsInv "Fraction of infrared radiant heat gain absorbed by opaque part of glass constructions that have a window"; Real fraConExtWinFra[NConExtWin] = AEpsConExtWinFra*sumAEpsInv "Fraction of infrared radiant heat gain absorbed by window frame of exterior constructions that have a window"; Real fraConPar_a[NConPar] = AEpsConPar_a*sumAEpsInv "Fraction of infrared radiant heat gain absorbed by partition constructions surface a"; Real fraConPar_b[NConPar] = AEpsConPar_b*sumAEpsInv "Fraction of infrared radiant heat gain absorbed by partition constructions surface b"; Real fraConBou[NConBou] = AEpsConBou*sumAEpsInv "Fraction of infrared radiant heat gain absorbed by constructions with exterior boundary conditions exposed to outside of room model"; Real fraSurBou[NSurBou] = AEpsSurBou*sumAEpsInv "Fraction of infrared radiant heat gain absorbed by surface models of constructions that are modeled outside of this room"; parameter Real AEpsConExt[NConExt] = {AConExt[i]*epsConExt[i] for i in 1:NConExt} "Absorptivity times area of exterior constructions"; parameter Real AEpsConExtWinOpa[NConExtWin] = {AConExtWinOpa[i]*epsConExtWinOpa[i] for i in 1:NConExtWin} "Absorptivity times area of opaque part of exterior constructions that contain a window"; Real AEpsConExtWinUns[NConExtWin] = {shaSig[i].yCom * AConExtWinGla[i]*epsConExtWinUns[i] for i in 1:NConExtWin} "Absorptivity times area of unshaded window constructions"; Real AEpsConExtWinSha[NConExtWin] = {shaSig[i].y * AConExtWinGla[i]*epsConExtWinSha[i] for i in 1:NConExtWin} "Absorptivity times area of shaded window constructions"; parameter Real AEpsConExtWinFra[NConExtWin] = {AConExtWinFra[i]*epsConExtWinFra[i] for i in 1:NConExtWin} "Absorptivity times area of window frame"; parameter Real AEpsConPar_a[NConPar] = {AConPar[i]*epsConPar_a[i] for i in 1:NConPar} "Absorptivity times area of partition constructions surface a"; parameter Real AEpsConPar_b[NConPar] = {AConPar[i]*epsConPar_b[i] for i in 1:NConPar} "Absorptivity times area of partition constructions surface b"; parameter Real AEpsConBou[NConBou] = {AConBou[i]*epsConBou[i] for i in 1:NConBou} "Absorptivity times area of constructions with exterior boundary conditions exposed to outside of room model"; parameter Real AEpsSurBou[NSurBou] = {ASurBou[i]*epsSurBou[i] for i in 1:NSurBou} "Absorptivity times area of surface models of constructions that are modeled outside of this room"; parameter Real sumAEpsNoWin(fixed=false) "Sum of absorptivity times area of all constructions except for windows"; Real sumAEpsInv "Inverse of sum of absorptivity times area of all constructions including windows"; Buildings.HeatTransfer.Windows.BaseClasses.ShadingSignal shaSig[NConExtWin]( each final haveShade=haveShade) "Block to constrain the shading control signal to be strictly within (0, 1) if a shade is present"; initial equation sumAEpsNoWin = sum(AEpsConExt)+sum(AEpsConExtWinOpa)+sum(AEpsConExtWinFra) +sum(AEpsConPar_a)+sum(AEpsConPar_b)+sum(AEpsConBou)+sum(AEpsSurBou); equation connect(uSha, shaSig.u); sumAEpsInv = 1.0/(sumAEpsNoWin + sum(AEpsConExtWinUns) + sum(AEpsConExtWinSha)); // Infrared radiative heat flow // If a construction is not present, we assign the temperature of the connector to 20 degC. if haveConExt then conExt.Q_flow = -fraConExt*Q_flow; else conExt[1].T = 293.15; end if; if haveConExtWin then conExtWin.Q_flow = -fraConExtWinOpa*Q_flow; else conExtWin[1].T = 293.15; end if; if haveConPar then conPar_a.Q_flow = -fraConPar_a*Q_flow; conPar_b.Q_flow = -fraConPar_b*Q_flow; else conPar_a[1].T = 293.15; conPar_b[1].T = 293.15; end if; if haveConBou then conBou.Q_flow = -fraConBou*Q_flow; else conBou[1].T = 293.15; end if; if haveSurBou then conSurBou.Q_flow = -fraSurBou*Q_flow; else conSurBou[1].T = 293.15; end if; // This model makes the simplification that the shade, the glass and the frame have // the same absorptivity in the infrared region JOutConExtWin = +fraConExtWinGla*Q_flow; if haveConExtWin then conExtWinFra.Q_flow = -fraConExtWinFra*Q_flow; else conExtWinFra[1].T = 293.15; end if; // Check for conservation of energy assert(abs(1 - sum(fraConExt) - sum(fraConExtWinOpa)- sum(fraConExtWinGla) - sum(fraConExtWinFra) - sum(fraConPar_a) - sum(fraConPar_b) - sum(fraConBou) - sum(fraSurBou)) < 1E-5, "Programming error: Radiation balance is wrong. Check equations."); end InfraredRadiationGainDistribution;

Buildings.ThermalZones.Detailed.BaseClasses.MixedAirHeatMassBalance Buildings.ThermalZones.Detailed.BaseClasses.MixedAirHeatMassBalance

Heat and mass balance of the air, assuming completely mixed air

Buildings.ThermalZones.Detailed.BaseClasses.MixedAirHeatMassBalance

Information

This model computes the heat and mass balance of the air. The model assumes a completely mixed air volume.

Extends from Buildings.ThermalZones.Detailed.BaseClasses.PartialAirHeatMassBalance (Partial model for heat and mass balance of the air), Buildings.Fluid.Interfaces.LumpedVolumeDeclarations (Declarations for lumped volumes).

Parameters

TypeNameDefaultDescription
ParameterConstructiondatConExt[NConExt] Data for exterior construction
ParameterConstructionWithWindowdatConExtWin[NConExtWin] Data for exterior construction with window
ParameterConstructiondatConPar[NConPar] Data for partition construction
ParameterConstructiondatConBou[NConBou] Data for construction boundary
OpaqueSurfacesurBou[NSurBou] Record for data of surfaces whose heat conduction is modeled outside of this room
Brick120dummyCon Dummy construction to assign a parameter to the instance
SingleClear3dummyGlaSys Dummy construction to assign a parameter to the instance
replaceable package MediumPartialMediumMedium in the component
BooleanhaveShade Set to true if at least one window has an interior or exterior shade
VolumeV Volume [m3]
Exterior constructions
IntegernConExt Number of exterior constructions
IntegernConExtWin Number of window constructions
Partition constructions
IntegernConPar Number of partition constructions
Boundary constructions
IntegernConBou Number of constructions that have their outside surface exposed to the boundary of this room
IntegernSurBou Number of surface heat transfer models that connect to constructions that are modeled outside of this room
Nominal condition
MassFlowRatem_flow_nominal Nominal mass flow rate [kg/s]
Convective heat transfer
InteriorConvectionconMod Convective heat transfer model for opaque constructions
CoefficientOfHeatTransferhFixed Constant convection coefficient for opaque constructions [W/(m2.K)]
Ports
Booleanuse_C_flow Set to true to enable input connector for trace substance
Dynamics
Equations
DynamicsenergyDynamicsModelica.Fluid.Types.Dynamic...Type of energy balance: dynamic (3 initialization options) or steady state
DynamicsmassDynamicsenergyDynamicsType of mass balance: dynamic (3 initialization options) or steady state
RealmSenFac1Factor for scaling the sensible thermal mass of the volume
Initialization
AbsolutePressurep_startMedium.p_defaultStart value of pressure [Pa]
TemperatureT_startMedium.T_defaultStart value of temperature [K]
MassFractionX_start[Medium.nX]Medium.X_defaultStart value of mass fractions m_i/m [kg/kg]
ExtraPropertyC_start[Medium.nC]fill(0, Medium.nC)Start value of trace substances
ExtraPropertyC_nominal[Medium.nC]fill(1E-2, Medium.nC)Nominal value of trace substances. (Set to typical order of magnitude.)

Connectors

TypeNameDescription
input RealInputuSha[NConExtWin]Input connector, used to scale the surface area to take into account an operable shading device, 0: unshaded; 1: fully shaded
input RealInputQRadAbs_flow[NConExtWin]Total net radiation that is absorbed by the shade (positive if absorbed) [W]
input RealInputQCon_flowConvective sensible heat gains of the room
input RealInputQLat_flowLatent heat gains for the room
output RealOutputTSha[NConExtWin]Shade temperature [K]
VesselFluidPorts_bports[nPorts]Fluid inlets and outlets
HeatPort_aheaPorAirHeat port to air volume
HeatPort_aconExt[NConExt]Heat port that connects to room-side surface of exterior constructions
HeatPort_aconExtWin[NConExtWin]Heat port that connects to room-side surface of exterior constructions that contain a window
HeatPort_aglaUns[NConExtWin]Heat port that connects to room-side surface of unshaded glass
HeatPort_aglaSha[NConExtWin]Heat port that connects to room-side surface of shaded glass
HeatPort_aconExtWinFra[NConExtWin]Heat port that connects to room-side surface of window frame
HeatPort_aconPar_a[NConPar]Heat port that connects to room-side surface a of partition constructions
HeatPort_aconPar_b[NConPar]Heat port that connects to room-side surface b of partition constructions
HeatPort_aconBou[NConBou]Heat port that connects to room-side surface of constructions that expose their other surface to the outside
HeatPort_aconSurBou[NSurBou]Heat port to surfaces of models that compute the heat conduction outside of this room
input RealInputC_flow[Medium.nC]Trace substance mass flow rate added to the room air. Enable if use_C_flow = true

Modelica definition

model MixedAirHeatMassBalance "Heat and mass balance of the air, assuming completely mixed air" extends Buildings.ThermalZones.Detailed.BaseClasses.PartialAirHeatMassBalance; extends Buildings.Fluid.Interfaces.LumpedVolumeDeclarations; constant Boolean homotopyInitialization = true "= true, use homotopy method"; parameter Modelica.SIunits.MassFlowRate m_flow_nominal(min=0) "Nominal mass flow rate"; parameter Buildings.HeatTransfer.Types.InteriorConvection conMod "Convective heat transfer model for opaque constructions"; parameter Modelica.SIunits.CoefficientOfHeatTransfer hFixed "Constant convection coefficient for opaque constructions"; parameter Boolean use_C_flow "Set to true to enable input connector for trace substance"; Modelica.Blocks.Interfaces.RealInput C_flow[Medium.nC] if use_C_flow "Trace substance mass flow rate added to the room air. Enable if use_C_flow = true"; // Mixing volume Fluid.MixingVolumes.MixingVolumeMoistAir vol( redeclare package Medium = Medium, final energyDynamics=energyDynamics, final massDynamics=massDynamics, final V=V, final p_start=p_start, final T_start=T_start, final X_start=X_start, final C_start=C_start, final C_nominal=C_nominal, final mSenFac=mSenFac, final m_flow_nominal = m_flow_nominal, final prescribedHeatFlowRate = true, final nPorts=nPorts, m_flow_small=1E-4*abs(m_flow_nominal), allowFlowReversal=true, final use_C_flow=use_C_flow) "Room air volume"; // Convection models HeatTransfer.Convection.Interior convConExt[NConExt]( final A=AConExt, final til = datConExt.til, each conMod=conMod, each hFixed=hFixed, each final homotopyInitialization=homotopyInitialization) if haveConExt "Convective heat transfer"; HeatTransfer.Convection.Interior convConExtWin[NConExtWin]( final A=AConExtWinOpa, final til = datConExtWin.til, each conMod=conMod, each hFixed=hFixed, each final homotopyInitialization=homotopyInitialization) if haveConExtWin "Convective heat transfer"; HeatTransfer.Windows.InteriorHeatTransferConvective convConWin[NConExtWin]( final fFra=datConExtWin.fFra, final haveExteriorShade={datConExtWin[i].glaSys.haveExteriorShade for i in 1:NConExtWin}, final haveInteriorShade={datConExtWin[i].glaSys.haveInteriorShade for i in 1:NConExtWin}, final til=datConExtWin.til, each conMod=conMod, each hFixed=hFixed, final A=AConExtWinGla + AConExtWinFra) if haveConExtWin "Model for convective heat transfer at window"; HeatTransfer.Convection.Interior convConPar_a[nConPar]( final A=AConPar, final til=Modelica.Constants.pi .- datConPar.til, each conMod=conMod, each hFixed=hFixed, each final homotopyInitialization=homotopyInitialization) if haveConPar "Convective heat transfer"; HeatTransfer.Convection.Interior convConPar_b[nConPar]( final A=AConPar, final til = datConPar.til, each conMod=conMod, each hFixed=hFixed, each final homotopyInitialization=homotopyInitialization) if haveConPar "Convective heat transfer"; HeatTransfer.Convection.Interior convConBou[nConBou]( final A=AConBou, final til = datConBou.til, each conMod=conMod, each hFixed=hFixed, each final homotopyInitialization=homotopyInitialization) if haveConBou "Convective heat transfer"; HeatTransfer.Convection.Interior convSurBou[nSurBou]( final A=ASurBou, final til = surBou.til, each conMod=conMod, each hFixed=hFixed, each final homotopyInitialization=homotopyInitialization) if haveSurBou "Convective heat transfer"; // Latent and convective sensible heat gains protected constant Modelica.SIunits.SpecificEnergy h_fg= Buildings.Media.Air.enthalpyOfCondensingGas(273.15+37) "Latent heat of water vapor"; Modelica.Blocks.Math.Gain mWat_flow( final k(unit="kg/J")=1/h_fg, u(final unit="W"), y(final unit="kg/s")) "Water flow rate due to latent heat gain"; HeatTransfer.Sources.PrescribedHeatFlow conQCon_flow "Converter for convective heat flow rate"; HeatTransfer.Sources.PrescribedHeatFlow conQLat_flow "Converter for latent heat flow rate"; // Thermal collectors Modelica.Thermal.HeatTransfer.Components.ThermalCollector theConConExt(final m=nConExt) if haveConExt "Thermal collector to convert from vector to scalar connector"; Modelica.Thermal.HeatTransfer.Components.ThermalCollector theConConExtWin(final m=nConExtWin) if haveConExtWin "Thermal collector to convert from vector to scalar connector"; Modelica.Thermal.HeatTransfer.Components.ThermalCollector theConConWin(final m=nConExtWin) if haveConExtWin "Thermal collector to convert from vector to scalar connector"; Modelica.Thermal.HeatTransfer.Components.ThermalCollector theConConPar_a(final m=nConPar) if haveConPar "Thermal collector to convert from vector to scalar connector"; Modelica.Thermal.HeatTransfer.Components.ThermalCollector theConConPar_b(final m=nConPar) if haveConPar "Thermal collector to convert from vector to scalar connector"; Modelica.Thermal.HeatTransfer.Components.ThermalCollector theConConBou(final m=nConBou) if haveConBou "Thermal collector to convert from vector to scalar connector"; Modelica.Thermal.HeatTransfer.Components.ThermalCollector theConSurBou(final m=nSurBou) if haveSurBou "Thermal collector to convert from vector to scalar connector"; initial equation assert(homotopyInitialization, "In " + getInstanceName() + ": The constant homotopyInitialization has been modified from its default value. This constant will be removed in future releases.", level = AssertionLevel.warning); equation connect(convConPar_a.fluid,theConConPar_a.port_a); connect(convConPar_b.fluid,theConConPar_b.port_a); connect(convConBou.fluid,theConConBou.port_a); connect(convSurBou.fluid,theConSurBou.port_a); connect(theConConPar_a.port_b,vol.heatPort); connect(theConConPar_b.port_b,vol.heatPort); connect(theConConBou.port_b,vol.heatPort); connect(theConSurBou.port_b,vol.heatPort); connect(conExtWinFra,convConWin.frame); connect(convConExt.solid, conExt); connect(convConExt.fluid,theConConExt.port_a); connect(theConConExt.port_b,vol.heatPort); connect(theConConExtWin.port_b,vol.heatPort); connect(convConExtWin.fluid,theConConExtWin.port_a); connect(convConExtWin.solid, conExtWin); connect(theConConWin.port_b,vol.heatPort); connect(convConWin.air,theConConWin.port_a); connect(convConWin.glaSha, glaSha); connect(convConWin.glaUns, glaUns); connect(convConPar_a.solid, conPar_a); connect(convConPar_b.solid, conPar_b); connect(convConBou.solid, conBou); connect(convSurBou.solid, conSurBou); for i in 1:nPorts loop connect(vol.ports[i], ports[i]); end for; connect(heaPorAir, vol.heatPort); connect(uSha, convConWin.uSha); connect(convConWin.QRadAbs_flow, QRadAbs_flow); connect(convConWin.TSha, TSha); connect(conQCon_flow.port, vol.heatPort); connect(QCon_flow, conQCon_flow.Q_flow); connect(QLat_flow, mWat_flow.u); connect(mWat_flow.y, vol.mWat_flow); connect(conQLat_flow.Q_flow, QLat_flow); connect(conQLat_flow.port, vol.heatPort); connect(vol.C_flow, C_flow); end MixedAirHeatMassBalance;

Buildings.ThermalZones.Detailed.BaseClasses.PartialAirHeatMassBalance Buildings.ThermalZones.Detailed.BaseClasses.PartialAirHeatMassBalance

Partial model for heat and mass balance of the air

Buildings.ThermalZones.Detailed.BaseClasses.PartialAirHeatMassBalance

Information

This is a partial model that is used to implement the heat and mass balance of the air.

Extends from Buildings.ThermalZones.Detailed.BaseClasses.ConstructionRecords (Data records for construction data).

Parameters

TypeNameDefaultDescription
ParameterConstructiondatConExt[NConExt] Data for exterior construction
ParameterConstructionWithWindowdatConExtWin[NConExtWin] Data for exterior construction with window
ParameterConstructiondatConPar[NConPar] Data for partition construction
ParameterConstructiondatConBou[NConBou] Data for construction boundary
OpaqueSurfacesurBou[NSurBou] Record for data of surfaces whose heat conduction is modeled outside of this room
Brick120dummyCon Dummy construction to assign a parameter to the instance
SingleClear3dummyGlaSys Dummy construction to assign a parameter to the instance
replaceable package MediumModelica.Media.Interfaces.Pa...Medium in the component
BooleanhaveShade Set to true if at least one window has an interior or exterior shade
VolumeV Volume [m3]
Exterior constructions
IntegernConExt Number of exterior constructions
IntegernConExtWin Number of window constructions
Partition constructions
IntegernConPar Number of partition constructions
Boundary constructions
IntegernConBou Number of constructions that have their outside surface exposed to the boundary of this room
IntegernSurBou Number of surface heat transfer models that connect to constructions that are modeled outside of this room

Connectors

TypeNameDescription
replaceable package MediumMedium in the component
input RealInputuSha[NConExtWin]Input connector, used to scale the surface area to take into account an operable shading device, 0: unshaded; 1: fully shaded
input RealInputQRadAbs_flow[NConExtWin]Total net radiation that is absorbed by the shade (positive if absorbed) [W]
input RealInputQCon_flowConvective sensible heat gains of the room
input RealInputQLat_flowLatent heat gains for the room
output RealOutputTSha[NConExtWin]Shade temperature [K]
VesselFluidPorts_bports[nPorts]Fluid inlets and outlets
HeatPort_aheaPorAirHeat port to air volume
HeatPort_aconExt[NConExt]Heat port that connects to room-side surface of exterior constructions
HeatPort_aconExtWin[NConExtWin]Heat port that connects to room-side surface of exterior constructions that contain a window
HeatPort_aglaUns[NConExtWin]Heat port that connects to room-side surface of unshaded glass
HeatPort_aglaSha[NConExtWin]Heat port that connects to room-side surface of shaded glass
HeatPort_aconExtWinFra[NConExtWin]Heat port that connects to room-side surface of window frame
HeatPort_aconPar_a[NConPar]Heat port that connects to room-side surface a of partition constructions
HeatPort_aconPar_b[NConPar]Heat port that connects to room-side surface b of partition constructions
HeatPort_aconBou[NConBou]Heat port that connects to room-side surface of constructions that expose their other surface to the outside
HeatPort_aconSurBou[NSurBou]Heat port to surfaces of models that compute the heat conduction outside of this room

Modelica definition

partial model PartialAirHeatMassBalance "Partial model for heat and mass balance of the air" extends Buildings.ThermalZones.Detailed.BaseClasses.ConstructionRecords; replaceable package Medium = Modelica.Media.Interfaces.PartialMedium "Medium in the component"; // Port definitions parameter Integer nPorts=0 "Number of ports"; parameter Boolean haveShade "Set to true if at least one window has an interior or exterior shade"; parameter Modelica.SIunits.Volume V "Volume"; // Input/output signals Modelica.Blocks.Interfaces.RealInput uSha[NConExtWin] if haveShade "Input connector, used to scale the surface area to take into account an operable shading device, 0: unshaded; 1: fully shaded"; Modelica.Blocks.Interfaces.RealInput QRadAbs_flow[NConExtWin]( each final unit="W") if haveShade "Total net radiation that is absorbed by the shade (positive if absorbed)"; Modelica.Blocks.Interfaces.RealInput QCon_flow "Convective sensible heat gains of the room"; Modelica.Blocks.Interfaces.RealInput QLat_flow "Latent heat gains for the room"; Modelica.Blocks.Interfaces.RealOutput TSha[NConExtWin]( each final unit="K", each final quantity="ThermodynamicTemperature") if haveShade "Shade temperature"; // Fluid port Modelica.Fluid.Vessels.BaseClasses.VesselFluidPorts_b ports[nPorts]( redeclare each final package Medium = Medium) "Fluid inlets and outlets"; // Heat ports Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a heaPorAir "Heat port to air volume"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conExt[NConExt] if haveConExt "Heat port that connects to room-side surface of exterior constructions"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conExtWin[NConExtWin] if haveConExtWin "Heat port that connects to room-side surface of exterior constructions that contain a window"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a glaUns[NConExtWin] if haveConExtWin "Heat port that connects to room-side surface of unshaded glass"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a glaSha[NConExtWin] if haveShade "Heat port that connects to room-side surface of shaded glass"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conExtWinFra[NConExtWin] if haveConExtWin "Heat port that connects to room-side surface of window frame"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conPar_a[NConPar] if haveConPar "Heat port that connects to room-side surface a of partition constructions"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conPar_b[NConPar] if haveConPar "Heat port that connects to room-side surface b of partition constructions"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conBou[NConBou] if haveConBou "Heat port that connects to room-side surface of constructions that expose their other surface to the outside"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conSurBou[NSurBou] if haveSurBou "Heat port to surfaces of models that compute the heat conduction outside of this room"; // Surface areas protected final parameter Modelica.SIunits.Area AConExt[NConExt] = datConExt.A "Areas of exterior constructions"; final parameter Modelica.SIunits.Area AConExtWinOpa[NConExtWin] = datConExtWin.AOpa "Opaque areas of exterior construction that have a window"; final parameter Modelica.SIunits.Area AConExtWinGla[NConExtWin] = (1 .- datConExtWin.fFra) .* datConExtWin.AWin "Glass areas of exterior construction that have a window"; final parameter Modelica.SIunits.Area AConExtWinFra[NConExtWin] = datConExtWin.fFra .* datConExtWin.AWin "Frame areas of exterior construction that have a window"; final parameter Modelica.SIunits.Area AConPar[NConPar] = datConPar.A "Areas of partition constructions"; final parameter Modelica.SIunits.Area AConBou[NConBou] = datConBou.A "Areas of constructions with exterior boundary conditions exposed to outside of room model"; final parameter Modelica.SIunits.Area ASurBou[NSurBou] = surBou.A "Area of surface models of constructions that are modeled outside of this room"; end PartialAirHeatMassBalance;

Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterface Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterface

Partial model that is used for infrared radiation balance

Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterface

Information

This partial model is used as a base class for models that need to exchange heat with room-facing surfaces. It defines parameters for the surface areas. The model is used as a base class to implement the convective model, and the various radiation models.

Extends from Buildings.ThermalZones.Detailed.BaseClasses.ConstructionRecords (Data records for construction data).

Parameters

TypeNameDefaultDescription
ParameterConstructiondatConExt[NConExt] Data for exterior construction
ParameterConstructionWithWindowdatConExtWin[NConExtWin] Data for exterior construction with window
ParameterConstructiondatConPar[NConPar] Data for partition construction
ParameterConstructiondatConBou[NConBou] Data for construction boundary
OpaqueSurfacesurBou[NSurBou] Record for data of surfaces whose heat conduction is modeled outside of this room
Brick120dummyCon Dummy construction to assign a parameter to the instance
SingleClear3dummyGlaSys Dummy construction to assign a parameter to the instance
Exterior constructions
IntegernConExt Number of exterior constructions
IntegernConExtWin Number of window constructions
Partition constructions
IntegernConPar Number of partition constructions
Boundary constructions
IntegernConBou Number of constructions that have their outside surface exposed to the boundary of this room
IntegernSurBou Number of surface heat transfer models that connect to constructions that are modeled outside of this room

Connectors

TypeNameDescription
HeatPort_aconExt[NConExt]Heat port that connects to room-side surface of exterior constructions
HeatPort_aconExtWin[NConExtWin]Heat port that connects to room-side surface of exterior constructions that contain a window
HeatPort_aconExtWinFra[NConExtWin]Heat port that connects to room-side surface of window frame
HeatPort_aconPar_a[NConPar]Heat port that connects to room-side surface a of partition constructions
HeatPort_aconPar_b[NConPar]Heat port that connects to room-side surface b of partition constructions
HeatPort_aconBou[NConBou]Heat port that connects to room-side surface of constructions that expose their other surface to the outside
HeatPort_aconSurBou[NSurBou]Heat port to surfaces of models that compute the heat conduction outside of this room

Modelica definition

partial model PartialSurfaceInterface "Partial model that is used for infrared radiation balance" extends Buildings.ThermalZones.Detailed.BaseClasses.ConstructionRecords; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conExt[NConExt] "Heat port that connects to room-side surface of exterior constructions"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conExtWin[NConExtWin] "Heat port that connects to room-side surface of exterior constructions that contain a window"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conExtWinFra[NConExtWin] "Heat port that connects to room-side surface of window frame"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conPar_a[NConPar] "Heat port that connects to room-side surface a of partition constructions"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conPar_b[NConPar] "Heat port that connects to room-side surface b of partition constructions"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conBou[NConBou] "Heat port that connects to room-side surface of constructions that expose their other surface to the outside"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a conSurBou[NSurBou] "Heat port to surfaces of models that compute the heat conduction outside of this room"; protected final parameter String instanceName = getInstanceName() "Name of the instance"; final parameter Modelica.SIunits.Area AConExt[NConExt] = datConExt.A "Areas of exterior constructions"; final parameter Modelica.SIunits.Area AConExtWinOpa[NConExtWin] = datConExtWin.AOpa "Opaque areas of exterior construction that have a window"; final parameter Modelica.SIunits.Area AConExtWinGla[NConExtWin] = (1 .- datConExtWin.fFra) .* datConExtWin.AWin "Glass areas of exterior construction that have a window"; final parameter Modelica.SIunits.Area AConExtWinFra[NConExtWin] = datConExtWin.fFra .* datConExtWin.AWin "Frame areas of exterior construction that have a window"; final parameter Modelica.SIunits.Area AConPar[NConPar] = datConPar.A "Areas of partition constructions"; final parameter Modelica.SIunits.Area AConBou[NConBou] = datConBou.A "Areas of constructions with exterior boundary conditions exposed to outside of room model"; final parameter Modelica.SIunits.Area ASurBou[NSurBou] = surBou.A "Area of surface models of constructions that are modeled outside of this room"; protected function checkSurfaceAreas input Integer n "Number of surfaces"; input Modelica.SIunits.Area A[:] "Surface areas"; input String name "Name of the surface data record, used in error message"; algorithm if n == 0 then assert(Modelica.Math.Vectors.norm(v=A, p=1) < 1E-10, "Error in declaration of room model: Construction record '" + name + "' has the following areas: " + Modelica.Math.Vectors.toString(A) + "However, the room model is declared as having zero surfaces. Check the parameters of the room model."); else for i in 1:n loop assert(A[i] > 0, "Error in declaration of room model: Construction record '" + name + "' has the following areas: " + Modelica.Math.Vectors.toString(A) + "However, the surface areas must be bigger than zero. Check the parameters of the room model."); end for; end if; end checkSurfaceAreas; initial algorithm checkSurfaceAreas(nConExt, datConExt.A, instanceName + ".datConExt"); checkSurfaceAreas(nConExtWin, datConExtWin.AWin, instanceName + ".datConExtWin"); checkSurfaceAreas(nConPar, datConPar.A, instanceName + ".datConPar"); checkSurfaceAreas(nConBou, datConBou.A, instanceName + ".datConBou"); checkSurfaceAreas(nSurBou, surBou.A, instanceName + ".surBou"); end PartialSurfaceInterface;

Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterfaceRadiative Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterfaceRadiative

Partial model that is used for infrared radiation balance

Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterfaceRadiative

Information

This partial model is used as a base class for models that need to exchange heat with room-facing surfaces by radiation. It declares parameters that are needed for the radiative balance.

Extends from Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterface (Partial model that is used for infrared radiation balance).

Parameters

TypeNameDefaultDescription
ParameterConstructiondatConExt[NConExt] Data for exterior construction
ParameterConstructionWithWindowdatConExtWin[NConExtWin] Data for exterior construction with window
ParameterConstructiondatConPar[NConPar] Data for partition construction
ParameterConstructiondatConBou[NConBou] Data for construction boundary
OpaqueSurfacesurBou[NSurBou] Record for data of surfaces whose heat conduction is modeled outside of this room
Brick120dummyCon Dummy construction to assign a parameter to the instance
SingleClear3dummyGlaSys Dummy construction to assign a parameter to the instance
Exterior constructions
IntegernConExt Number of exterior constructions
IntegernConExtWin Number of window constructions
Partition constructions
IntegernConPar Number of partition constructions
Boundary constructions
IntegernConBou Number of constructions that have their outside surface exposed to the boundary of this room
IntegernSurBou Number of surface heat transfer models that connect to constructions that are modeled outside of this room

Connectors

TypeNameDescription
HeatPort_aconExt[NConExt]Heat port that connects to room-side surface of exterior constructions
HeatPort_aconExtWin[NConExtWin]Heat port that connects to room-side surface of exterior constructions that contain a window
HeatPort_aconExtWinFra[NConExtWin]Heat port that connects to room-side surface of window frame
HeatPort_aconPar_a[NConPar]Heat port that connects to room-side surface a of partition constructions
HeatPort_aconPar_b[NConPar]Heat port that connects to room-side surface b of partition constructions
HeatPort_aconBou[NConBou]Heat port that connects to room-side surface of constructions that expose their other surface to the outside
HeatPort_aconSurBou[NSurBou]Heat port to surfaces of models that compute the heat conduction outside of this room

Modelica definition

partial model PartialSurfaceInterfaceRadiative "Partial model that is used for infrared radiation balance" extends Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterface; protected parameter Modelica.SIunits.Emissivity epsConExt[NConExt] = datConExt.layers.absIR_b "Absorptivity of exterior constructions"; parameter Modelica.SIunits.Emissivity epsConExtWinOpa[NConExtWin] = datConExtWin.layers.absIR_b "Absorptivity of opaque part of exterior constructions that contain a window"; parameter Modelica.SIunits.Emissivity epsConExtWinUns[NConExtWin]= {(datConExtWin[i].glaSys.glass[size(datConExtWin[i].glaSys.glass, 1)].absIR_b) for i in 1:NConExtWin} "Absorptivity of unshaded part of window constructions"; parameter Modelica.SIunits.Emissivity epsConExtWinSha[NConExtWin] = datConExtWin.glaSys.shade.absIR_a "Absorptivity of shaded part of window constructions"; parameter Modelica.SIunits.Emissivity epsConExtWinFra[NConExtWin] = datConExtWin.glaSys.absIRFra "Absorptivity of window frame"; parameter Modelica.SIunits.Emissivity epsConPar_a[NConPar] = datConPar.layers.absIR_a "Absorptivity of partition constructions surface a"; parameter Modelica.SIunits.Emissivity epsConPar_b[NConPar] = datConPar.layers.absIR_b "Absorptivity of partition constructions surface b"; parameter Modelica.SIunits.Emissivity epsConBou[NConBou] = datConBou.layers.absIR_b "Absorptivity of constructions with exterior boundary conditions exposed to outside of room model"; parameter Modelica.SIunits.Emissivity epsSurBou[NSurBou] = surBou.absIR "Absorptivity of surface models of constructions that are modeled outside of this room"; end PartialSurfaceInterfaceRadiative;

Buildings.ThermalZones.Detailed.BaseClasses.RadiationAdapter Buildings.ThermalZones.Detailed.BaseClasses.RadiationAdapter

Model to connect between signals and heat port for radiative gains of the room

Buildings.ThermalZones.Detailed.BaseClasses.RadiationAdapter

Information

This model can be used as a thermal adapter in situations where the temperature and the heat flow rate are computed in separate models. For example, this thermal adapter is used in the room model, which computes the distribution of radiative heat gains (such as due to a radiator) in Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationGainDistribution and computes the radiative temperature in Buildings.ThermalZones.Detailed.BaseClasses.RadiationTemperature. This adapter combines the heat flow rate and the temperatures that are computed in these separate models, and exposes these two quantities at its heat port.

Extends from Buildings.BaseClasses.BaseIcon (Base icon).

Connectors

TypeNameDescription
HeatPort_aradPort for radiative heat gain and radiation temperature
input RealInputTRadRadiation temperature of room
output RealOutputQRad_flowRadiative heat gain

Modelica definition

model RadiationAdapter "Model to connect between signals and heat port for radiative gains of the room" extends Buildings.BaseClasses.BaseIcon; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a rad "Port for radiative heat gain and radiation temperature"; public Modelica.Blocks.Interfaces.RealInput TRad "Radiation temperature of room"; Modelica.Blocks.Interfaces.RealOutput QRad_flow "Radiative heat gain"; equation QRad_flow = rad.Q_flow; rad.T = TRad; end RadiationAdapter;

Buildings.ThermalZones.Detailed.BaseClasses.RadiationTemperature Buildings.ThermalZones.Detailed.BaseClasses.RadiationTemperature

Radiative temperature of the room

Buildings.ThermalZones.Detailed.BaseClasses.RadiationTemperature

Information

This model computes the radiative temperature in the room. For a room with windows but no shade, the radiative temperature is computed as

Trad = ∑i   (Ai   εi   Ti) ⁄ ∑i   (Ai   εi)

where Trad is the radiative temperature of the room, Ai are the surface areas of the room, εi are the infrared emissivities of the surfaces, and Ti are the surface temperatures.

If a the windows have a shade, then the equation is modified to take the actual shaded and non-shaded surface area into account. In this situation, the shaded part of a window has a infrared radiative power of

E = A   ( u   εs   Ts + (1-u)   εg τs   Tgs)

where A is the surface area of the glass, u is the control signal of the shade, εs is the infrared absorptivity of the shade, Ts is the temperature of the shade, εg is the infrared absorptivity of the glass, τs is the infrared transmittance of the shade, and Tgs is the glass temperature behind the shade.

For the unshaded part of the window, the radiative power is

E = A   (1-u)   εg   Tgn

where Tgn is the glass temperature of the non-shaded part of the window.

Extends from Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterfaceRadiative (Partial model that is used for infrared radiation balance).

Parameters

TypeNameDefaultDescription
ParameterConstructiondatConExt[NConExt] Data for exterior construction
ParameterConstructionWithWindowdatConExtWin[NConExtWin] Data for exterior construction with window
ParameterConstructiondatConPar[NConPar] Data for partition construction
ParameterConstructiondatConBou[NConBou] Data for construction boundary
OpaqueSurfacesurBou[NSurBou] Record for data of surfaces whose heat conduction is modeled outside of this room
Brick120dummyCon Dummy construction to assign a parameter to the instance
SingleClear3dummyGlaSys Dummy construction to assign a parameter to the instance
BooleanhaveShade Set to true if the windows have a shade
Exterior constructions
IntegernConExt Number of exterior constructions
IntegernConExtWin Number of window constructions
Partition constructions
IntegernConPar Number of partition constructions
Boundary constructions
IntegernConBou Number of constructions that have their outside surface exposed to the boundary of this room
IntegernSurBou Number of surface heat transfer models that connect to constructions that are modeled outside of this room

Connectors

TypeNameDescription
HeatPort_aconExt[NConExt]Heat port that connects to room-side surface of exterior constructions
HeatPort_aconExtWin[NConExtWin]Heat port that connects to room-side surface of exterior constructions that contain a window
HeatPort_aconExtWinFra[NConExtWin]Heat port that connects to room-side surface of window frame
HeatPort_aconPar_a[NConPar]Heat port that connects to room-side surface a of partition constructions
HeatPort_aconPar_b[NConPar]Heat port that connects to room-side surface b of partition constructions
HeatPort_aconBou[NConBou]Heat port that connects to room-side surface of constructions that expose their other surface to the outside
HeatPort_aconSurBou[NSurBou]Heat port to surfaces of models that compute the heat conduction outside of this room
HeatPort_aglaUns[NConExtWin]Heat port that connects to room-side surface of unshaded glass
HeatPort_aglaSha[NConExtWin]Heat port that connects to room-side surface of shaded glass
HeatPort_asha[NConExtWin]Heat port that connects to shade
input RealInputuSha[NConExtWin]Control signal for the shading device (removed if no shade is present)
output RealOutputTRadRadiative temperature [K]

Modelica definition

model RadiationTemperature "Radiative temperature of the room" extends Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterfaceRadiative; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a glaUns[NConExtWin] if haveConExtWin "Heat port that connects to room-side surface of unshaded glass"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a glaSha[NConExtWin] if haveShade "Heat port that connects to room-side surface of shaded glass"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a sha[NConExtWin] if haveShade "Heat port that connects to shade"; parameter Boolean haveShade "Set to true if the windows have a shade"; Modelica.Blocks.Interfaces.RealInput uSha[NConExtWin](each min=0, each max=1) if haveShade "Control signal for the shading device (removed if no shade is present)"; Modelica.Blocks.Interfaces.RealOutput TRad(min=0, unit="K", displayUnit="degC") "Radiative temperature"; protected final parameter Integer NOpa = NConExt+2*NConExtWin+2*NConPar+NConBou+NSurBou "Number of opaque surfaces, including the window frame"; final parameter Integer NWin = NConExtWin "Number of window surfaces"; final parameter Integer NTot = NOpa + NWin "Total number of surfaces"; final parameter Modelica.SIunits.Area AGla[NWin] = datConExtWin.AGla "Surface area of opaque surfaces"; final parameter Real epsGla[NWin](each min=0, each max=1)= {datConExtWin[i].glaSys.glass[size(datConExtWin[i].glaSys.glass, 1)].absIR_b for i in 1:NWin} "Absorptivity of glass"; final parameter Real epsSha[NWin](each min=0, each max=1)= {datConExtWin[i].glaSys.shade.absIR_a for i in 1:NWin} "Absorptivity of shade"; final parameter Real tauSha[NWin](each min=0, each max=1)= {(if datConExtWin[i].glaSys.haveInteriorShade then datConExtWin[i].glaSys.shade.tauIR_a else 1) for i in 1:NWin} "Transmissivity of shade"; final parameter Modelica.SIunits.Area epsAOpa[NOpa](each fixed=false) "Product of area times absorptivity of opaque surfaces"; final parameter Modelica.SIunits.Area epsAGla[NWin](each fixed=false) "Product of area times absorptivity of window surfaces"; final parameter Modelica.SIunits.Area epsASha[NWin](each fixed=false) "Product of area times absorptivity of window shade"; final parameter Modelica.SIunits.Area epsTauASha[NWin](each fixed=false) "Product of area times glass absorptivity times shade transmittance"; Modelica.SIunits.Temperature TOpa[NOpa](each start=293.15, each nominal=293.15) "Temperature of opaque surfaces"; Modelica.SIunits.Temperature TGlaUns[NWin](each start=293.15, each nominal=293.15) "Temperature of unshaded part of glass"; Modelica.SIunits.Temperature TGlaSha[NWin](each start=293.15, each nominal=293.15) "Temperature of shaded part of glass"; Modelica.SIunits.Temperature TSha[NWin](each start=293.15, each nominal=293.15) "Temperature of shade"; // Internal connectors, used because of the conditionally removed connectors Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a glaUns_internal[NConExtWin] "Heat port that connects to room-side surface of unshaded glass"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a glaSha_internal[NConExtWin] "Heat port that connects to room-side surface of shaded glass"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a sha_internal[NConExtWin] "Heat port that connects to shade"; Modelica.Blocks.Interfaces.RealInput uSha_internal[NConExtWin](each min=0, each max=1) "Control signal for the shading device"; initial equation // The next loops build the array epsAOpa that simplifies // the model equations. // The arrays stores the values of the constructios in the following order // [x[1:NConExt] x[1:NConPar] x[1: NConPar] x[1: NConBou] x[1: NSurBou] x[1: NConExtWin] x[1: NConExtWin]] // where x is epsOpa, AOpa or kOpa. // The last two entries are for the opaque wall that contains a window, and for the window frame. for i in 1:NConExt loop epsAOpa[i] = epsConExt[i] * AConExt[i]; end for; for i in 1:NConPar loop epsAOpa[i+NConExt] = epsConPar_a[i] * AConPar[i]; epsAOpa[i+NConExt+NConPar] = epsConPar_b[i] * AConPar[i]; end for; for i in 1:NConBou loop epsAOpa[i+NConExt+2*NConPar] = epsConBou[i] * AConBou[i]; end for; for i in 1:NSurBou loop epsAOpa[i+NConExt+2*NConPar+NConBou] = epsSurBou[i] * ASurBou[i]; end for; for i in 1:NConExtWin loop // Opaque part of construction that has a window embedded epsAOpa[i+NConExt+2*NConPar+NConBou+NSurBou] = epsConExtWinOpa[i] * AConExtWinOpa[i]; // Window frame epsAOpa[i+NConExt+2*NConPar+NConBou+NSurBou+NConExtWin] = epsConExtWinFra[i] * AConExtWinFra[i]; end for; // Window glass for i in 1:NConExtWin loop // Window glass epsAGla[i] = AGla[i] * epsGla[i]; // Window shade epsASha[i] = AGla[i] * epsSha[i]; // Emitted from glas and transmitted through window shade epsTauASha[i] = AGla[i] * epsGla[i] * tauSha[i]; end for; //////////////////////////////////////////////////////////////////// equation // Conditional connnector connect(glaUns, glaUns_internal); connect(glaSha, glaSha_internal); connect(sha, sha_internal); connect(uSha, uSha_internal); if not haveConExtWin then glaUns_internal.T = fill(293.15, NConExtWin); end if; if not haveShade then glaSha_internal.T = fill(293.15, NConExtWin); sha_internal.T = fill(293.15, NConExtWin); uSha_internal = fill(0, NConExtWin); end if; // Assign temperature of opaque surfaces for i in 1:NConExt loop TOpa[i] = conExt[i].T; end for; for i in 1:NConPar loop TOpa[i+NConExt] = conPar_a[i].T; TOpa[i+NConExt+NConPar] = conPar_b[i].T; end for; for i in 1:NConBou loop TOpa[i+NConExt+2*NConPar] = conBou[i].T; end for; for i in 1:NSurBou loop TOpa[i+NConExt+2*NConPar+NConBou] = conSurBou[i].T; end for; for i in 1:NConExtWin loop TOpa[i+NConExt+2*NConPar+NConBou+NSurBou] = conExtWin[i].T; TOpa[i+NConExt+2*NConPar+NConBou+NConExtWin+NSurBou] = conExtWinFra[i].T; end for; // Assign temperature of glass and shade for i in 1:NConExtWin loop TGlaUns[i] = glaUns_internal[i].T; TGlaSha[i] = glaSha_internal[i].T; TSha[i] = sha_internal[i].T; end for; // Compute radiative temperature if haveShade then TRad = (sum(epsAOpa[i] * TOpa[i] for i in 1:NOpa) + sum( ( uSha_internal[i] * (epsASha[i] * TSha[i] + epsTauASha[i] * TGlaSha[i]) + (1-uSha_internal[i]) * epsAGla[i] * TGlaUns[i]) for i in 1:NConExtWin)) / (sum(epsAOpa) + sum( ( uSha_internal[i] * (epsASha[i] + epsTauASha[i]) + (1-uSha_internal[i]) * epsAGla[i]) for i in 1:NConExtWin)); else TRad = (sum(epsAOpa[i] * TOpa[i] for i in 1:NOpa) + sum(epsAGla .* TGlaUns)) / (sum(epsAOpa) + sum(epsAGla)); end if; // Assign heat exchange to connectors if haveConExt then for i in 1:NConExt loop 0 = conExt[i].Q_flow; end for; else conExt[1].T = 293.15; end if; if haveConPar then for i in 1:NConPar loop 0 = conPar_a[i].Q_flow; 0 = conPar_b[i].Q_flow; end for; else conPar_a[1].T = 293.15; conPar_b[1].T = 293.15; end if; if haveConBou then for i in 1:NConBou loop 0 = conBou[i].Q_flow; end for; else conBou[1].T = 293.15; end if; if haveSurBou then for i in 1:NSurBou loop 0 = conSurBou[i].Q_flow; end for; else conSurBou[1].T = 293.15; end if; if haveConExtWin then for i in 1:NConExtWin loop 0 = conExtWin[i].Q_flow; 0 = conExtWinFra[i].Q_flow; end for; else conExtWin[1].T = 293.15; conExtWinFra[1].T = 293.15; end if; end RadiationTemperature;

Buildings.ThermalZones.Detailed.BaseClasses.RoomHeatMassBalance Buildings.ThermalZones.Detailed.BaseClasses.RoomHeatMassBalance

Base model for a room

Buildings.ThermalZones.Detailed.BaseClasses.RoomHeatMassBalance

Information

Partial model for a room heat and mass balance.

This is the base class for Buildings.ThermalZones.Detailed.CFD and for Buildings.ThermalZones.Detailed.MixedAir

See Buildings.ThermalZones.Detailed.UsersGuide for detailed explanations.

Extends from Buildings.ThermalZones.Detailed.BaseClasses.ConstructionRecords (Data records for construction data).

Parameters

TypeNameDefaultDescription
ParameterConstructiondatConExt[NConExt] Data for exterior construction
ParameterConstructionWithWindowdatConExtWin[NConExtWin] Data for exterior construction with window
ParameterConstructiondatConPar[NConPar] Data for partition construction
ParameterConstructiondatConBou[NConBou] Data for construction boundary
OpaqueSurfacesurBou[NSurBou] Record for data of surfaces whose heat conduction is modeled outside of this room
Brick120dummyCon Dummy construction to assign a parameter to the instance
SingleClear3dummyGlaSys Dummy construction to assign a parameter to the instance
replaceable package MediumModelica.Media.Interfaces.Pa...Medium in the component
Anglelat Latitude [rad]
AreaAFlo Floor area [m2]
LengthhRoo Average room height [m]
BooleanlinearizeRadiationtrueSet to true to linearize emissive power
PartialAirHeatMassBalanceairredeclare BaseClasses.Partia...Convective heat and mass balance of air
Exterior constructions
IntegernConExt Number of exterior constructions
IntegernConExtWin Number of window constructions
Partition constructions
IntegernConPar Number of partition constructions
Boundary constructions
IntegernConBou Number of constructions that have their outside surface exposed to the boundary of this room
IntegernSurBou Number of surface heat transfer models that connect to constructions that are modeled outside of this room
Convective heat transfer
InteriorConvectionintConModBuildings.HeatTransfer.Types...Convective heat transfer model for room-facing surfaces of opaque constructions
CoefficientOfHeatTransferhIntFixed3.0Constant convection coefficient for room-facing surfaces of opaque constructions [W/(m2.K)]
ExteriorConvectionextConModBuildings.HeatTransfer.Types...Convective heat transfer model for exterior facing surfaces of opaque constructions
CoefficientOfHeatTransferhExtFixed10.0Constant convection coefficient for exterior facing surfaces of opaque constructions [W/(m2.K)]
Nominal condition
MassFlowRatem_flow_nominalV*1.2/3600Nominal mass flow rate [kg/s]
Dynamics
Glazing system
BooleansteadyStateWindowfalseSet to false to add thermal capacity at window, which generally leads to faster simulation
Experimental (may be changed in future releases)
BooleansampleModelfalseSet to true to time-sample the model, which can give shorter simulation time if there is already time sampling in the system model

Connectors

TypeNameDescription
replaceable package MediumMedium in the component
VesselFluidPorts_bports[nPorts]Fluid inlets and outlets
HeatPort_aheaPorAirHeat port to air volume
HeatPort_aheaPorRadHeat port for radiative heat gain and radiative temperature
input RealInputuWin[nConExtWin]Control signal for window state (used for electrochromic windows, removed otherwise) [1]
HeatPort_asurf_conBou[nConBou]Heat port at surface b of construction conBou
HeatPort_asurf_surBou[nSurBou]Heat port of surface that is connected to the room air
input RealInputqGai_flow[3]Radiant, convective and latent heat input into room (positive if heat gain) [W/m2]
BusweaBusWeather data

Modelica definition

partial model RoomHeatMassBalance "Base model for a room" extends Buildings.ThermalZones.Detailed.BaseClasses.ConstructionRecords; replaceable package Medium = Modelica.Media.Interfaces.PartialMedium "Medium in the component"; constant Boolean homotopyInitialization = true "= true, use homotopy method"; parameter Integer nPorts=0 "Number of ports"; Modelica.Fluid.Vessels.BaseClasses.VesselFluidPorts_b ports[nPorts]( redeclare each package Medium = Medium) "Fluid inlets and outlets"; parameter Modelica.SIunits.Angle lat "Latitude"; final parameter Modelica.SIunits.Volume V=AFlo*hRoo "Volume"; parameter Modelica.SIunits.Area AFlo "Floor area"; parameter Modelica.SIunits.Length hRoo "Average room height"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a heaPorAir "Heat port to air volume"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a heaPorRad "Heat port for radiative heat gain and radiative temperature"; //////////////////////////////////////////////////////////////////////// // Constructions Constructions.Construction conExt[NConExt]( final A=datConExt.A, final til=datConExt.til, final layers=datConExt.layers, final steadyStateInitial=datConExt.steadyStateInitial, final T_a_start=datConExt.T_a_start, final T_b_start=datConExt.T_b_start, final stateAtSurface_a = datConExt.stateAtSurface_a, final stateAtSurface_b = datConExt.stateAtSurface_b) if haveConExt "Heat conduction through exterior construction that have no window"; Constructions.ConstructionWithWindow conExtWin[NConExtWin]( final A=datConExtWin.A, final til=datConExtWin.til, final layers=datConExtWin.layers, final steadyStateInitial=datConExtWin.steadyStateInitial, final T_a_start=datConExtWin.T_a_start, final T_b_start=datConExtWin.T_b_start, final AWin=datConExtWin.AWin, final fFra=datConExtWin.fFra, final glaSys=datConExtWin.glaSys, each final homotopyInitialization=homotopyInitialization, each final linearizeRadiation=linearizeRadiation, each final steadyStateWindow=steadyStateWindow, final stateAtSurface_a = datConExtWin.stateAtSurface_a, final stateAtSurface_b = datConExtWin.stateAtSurface_b) if haveConExtWin "Heat conduction through exterior construction that have a window"; Constructions.Construction conPar[NConPar]( A=datConPar.A, til=datConPar.til, final layers=datConPar.layers, steadyStateInitial=datConPar.steadyStateInitial, T_a_start=datConPar.T_a_start, T_b_start=datConPar.T_b_start, final stateAtSurface_a = datConPar.stateAtSurface_a, final stateAtSurface_b = datConPar.stateAtSurface_b) if haveConPar "Heat conduction through partitions that have both sides inside the thermal zone"; Constructions.Construction conBou[NConBou]( A=datConBou.A, til=datConBou.til, final layers=datConBou.layers, steadyStateInitial=datConBou.steadyStateInitial, T_a_start=datConBou.T_a_start, T_b_start=datConBou.T_b_start, final stateAtSurface_a = datConBou.stateAtSurface_a, final stateAtSurface_b = datConBou.stateAtSurface_b) if haveConBou "Heat conduction through opaque constructions that have the boundary conditions of the other side exposed"; parameter Boolean linearizeRadiation=true "Set to true to linearize emissive power"; parameter Boolean steadyStateWindow = false "Set to false to add thermal capacity at window, which generally leads to faster simulation"; //////////////////////////////////////////////////////////////////////// // Convection parameter Buildings.HeatTransfer.Types.InteriorConvection intConMod=Buildings.HeatTransfer.Types.InteriorConvection.Temperature "Convective heat transfer model for room-facing surfaces of opaque constructions"; parameter Modelica.SIunits.CoefficientOfHeatTransfer hIntFixed=3.0 "Constant convection coefficient for room-facing surfaces of opaque constructions"; parameter Buildings.HeatTransfer.Types.ExteriorConvection extConMod=Buildings.HeatTransfer.Types.ExteriorConvection.TemperatureWind "Convective heat transfer model for exterior facing surfaces of opaque constructions"; parameter Modelica.SIunits.CoefficientOfHeatTransfer hExtFixed=10.0 "Constant convection coefficient for exterior facing surfaces of opaque constructions"; parameter Modelica.SIunits.MassFlowRate m_flow_nominal(min=0) = V*1.2/3600 "Nominal mass flow rate"; parameter Boolean sampleModel = false "Set to true to time-sample the model, which can give shorter simulation time if there is already time sampling in the system model"; //////////////////////////////////////////////////////////////////////// // Control signals Modelica.Blocks.Interfaces.RealInput uWin[nConExtWin]( each min=0, each max=1, each unit="1") if haveControllableWindow "Control signal for window state (used for electrochromic windows, removed otherwise)"; //////////////////////////////////////////////////////////////////////// // Models for boundary conditions Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a surf_conBou[nConBou] if haveConBou "Heat port at surface b of construction conBou"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a surf_surBou[nSurBou] if haveSurBou "Heat port of surface that is connected to the room air"; Modelica.Blocks.Interfaces.RealInput qGai_flow[3](each unit="W/m2") "Radiant, convective and latent heat input into room (positive if heat gain)"; // Reassign the tilt since a construction that is declared as a ceiling of the // room model has an exterior-facing surface that is a floor BaseClasses.ExteriorBoundaryConditions bouConExt( final nCon=nConExt, final lat=lat, linearizeRadiation=linearizeRadiation, final conMod=extConMod, final conPar=datConExt, final hFixed=hExtFixed) if haveConExt "Exterior boundary conditions for constructions without a window"; // Reassign the tilt since a construction that is declared as a ceiling of the // room model has an exterior-facing surface that is a floor BaseClasses.ExteriorBoundaryConditionsWithWindow bouConExtWin( final nCon=nConExtWin, final lat=lat, final conPar=datConExtWin, linearizeRadiation=linearizeRadiation, final conMod=extConMod, final hFixed=hExtFixed) if haveConExtWin "Exterior boundary conditions for constructions with a window"; HeatTransfer.Windows.BaseClasses.WindowRadiation conExtWinRad[NConExtWin]( final AWin=(1 .- datConExtWin.fFra) .* datConExtWin.AWin, final N={size(datConExtWin[i].glaSys.glass, 1) for i in 1:NConExtWin}, final tauGlaSol=datConExtWin.glaSys.glass.tauSol, final rhoGlaSol_a=datConExtWin.glaSys.glass.rhoSol_a, final rhoGlaSol_b=datConExtWin.glaSys.glass.rhoSol_b, final xGla=datConExtWin.glaSys.glass.x, final tauShaSol_a=datConExtWin.glaSys.shade.tauSol_a, final tauShaSol_b=datConExtWin.glaSys.shade.tauSol_b, final rhoShaSol_a=datConExtWin.glaSys.shade.rhoSol_a, final rhoShaSol_b=datConExtWin.glaSys.shade.rhoSol_b, final haveExteriorShade=datConExtWin.glaSys.haveExteriorShade, final haveInteriorShade=datConExtWin.glaSys.haveInteriorShade) if haveConExtWin "Model for solar radiation through shades and window"; BoundaryConditions.WeatherData.Bus weaBus "Weather data"; replaceable BaseClasses.PartialAirHeatMassBalance air constrainedby BaseClasses.PartialAirHeatMassBalance( redeclare final package Medium = Medium, nPorts=nPorts, final nConExt=nConExt, final nConExtWin=nConExtWin, final nConPar=nConPar, final nConBou=nConBou, final nSurBou=nSurBou, final datConExt=datConExt, final datConExtWin=datConExtWin, final datConPar=datConPar, final datConBou=datConBou, final surBou=surBou, final haveShade=haveShade, final V=V) "Convective heat and mass balance of air"; Buildings.ThermalZones.Detailed.BaseClasses.SolarRadiationExchange solRadExc( final nConExt=nConExt, final nConExtWin=nConExtWin, final nConPar=nConPar, final nConBou=nConBou, final nSurBou=nSurBou, final datConExt = datConExt, final datConExtWin = datConExtWin, final datConPar = datConPar, final datConBou = datConBou, final surBou = surBou, final isFloorConExt=isFloorConExt, final isFloorConExtWin=isFloorConExtWin, final isFloorConPar_a=isFloorConPar_a, final isFloorConPar_b=isFloorConPar_b, final isFloorConBou=isFloorConBou, final isFloorSurBou=isFloorSurBou, final tauGla={datConExtWin[i].glaSys.glass[size(datConExtWin[i].glaSys.glass, 1)].tauSol[1] for i in 1:NConExtWin}) if haveConExtWin "Solar radiative heat exchange"; Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationGainDistribution irRadGai( final nConExt=nConExt, final nConExtWin=nConExtWin, final nConPar=nConPar, final nConBou=nConBou, final nSurBou=nSurBou, final datConExt = datConExt, final datConExtWin = datConExtWin, final datConPar = datConPar, final datConBou = datConBou, final surBou = surBou, final haveShade=haveShade) "Distribution for infrared radiative heat gains (e.g., due to equipment and people)"; Buildings.ThermalZones.Detailed.BaseClasses.InfraredRadiationExchange irRadExc( final nConExt=nConExt, final nConExtWin=nConExtWin, final nConPar=nConPar, final nConBou=nConBou, final nSurBou=nSurBou, final datConExt = datConExt, final datConExtWin = datConExtWin, final datConPar = datConPar, final datConBou = datConBou, final surBou = surBou, final linearizeRadiation = linearizeRadiation, final homotopyInitialization = homotopyInitialization, final sampleModel = sampleModel) "Infrared radiative heat exchange"; Buildings.ThermalZones.Detailed.BaseClasses.RadiationTemperature radTem( final nConExt=nConExt, final nConExtWin=nConExtWin, final nConPar=nConPar, final nConBou=nConBou, final nSurBou=nSurBou, final datConExt=datConExt, final datConExtWin=datConExtWin, final datConPar=datConPar, final datConBou=datConBou, final surBou=surBou, final haveShade=haveShade) "Radiative temperature of the room"; HeatTransfer.Windows.BaseClasses.ShadeRadiation shaRad[NConExtWin]( final A=(1 .- datConExtWin.fFra) .* datConExtWin.AWin, final thisSideHasShade=haveInteriorShade, final absIR_air=datConExtWin.glaSys.shade.absIR_a, final absIR_glass={(datConExtWin[i].glaSys.glass[size(datConExtWin[i].glaSys.glass, 1)].absIR_b) for i in 1:NConExtWin}, final tauIR_air=tauIRSha_air, final tauIR_glass=tauIRSha_glass, each final linearize = linearizeRadiation, each final homotopyInitialization=homotopyInitialization) if haveShade "Radiation model for room-side window shade"; protected final parameter Modelica.SIunits.TransmissionCoefficient tauIRSha_air[NConExtWin]= datConExtWin.glaSys.shade.tauIR_a "Infrared transmissivity of shade for radiation coming from the exterior or the room"; final parameter Modelica.SIunits.TransmissionCoefficient tauIRSha_glass[NConExtWin]= datConExtWin.glaSys.shade.tauIR_b "Infrared transmissivity of shade for radiation coming from the glass"; // If at least one glass layer in the room has mutiple states, then // set haveControllableWindow=true. In this case, the input connector for // the control signal will be enabled. Otherwise, it is removed. final parameter Boolean haveControllableWindow= Modelica.Math.BooleanVectors.anyTrue( {datConExtWin[i].glaSys.haveControllableWindow for i in 1:NConExtWin}) "Flag, true if the windows allow multiple states, such as for electrochromic windows"; final parameter Boolean haveExteriorShade[NConExtWin]= {datConExtWin[i].glaSys.haveExteriorShade for i in 1:NConExtWin} "Set to true if window has exterior shade (at surface a)"; final parameter Boolean haveInteriorShade[NConExtWin]= {datConExtWin[i].glaSys.haveInteriorShade for i in 1:NConExtWin} "Set to true if window has interior shade (at surface b)"; final parameter Boolean haveShade= Modelica.Math.BooleanVectors.anyTrue(haveExteriorShade[:]) or Modelica.Math.BooleanVectors.anyTrue(haveInteriorShade[:]) "Set to true if the windows have a shade"; final parameter Boolean isFloorConExt[NConExt]= datConExt.isFloor "Flag to indicate if floor for exterior constructions"; final parameter Boolean isFloorConExtWin[NConExtWin]= datConExtWin.isFloor "Flag to indicate if floor for constructions"; final parameter Boolean isFloorConPar_a[NConPar]= datConPar.isFloor "Flag to indicate if floor for constructions"; final parameter Boolean isFloorConPar_b[NConPar]= datConPar.isCeiling "Flag to indicate if floor for constructions"; final parameter Boolean isFloorConBou[NConBou]= datConBou.isFloor "Flag to indicate if floor for constructions with exterior boundary conditions exposed to outside of room model"; parameter Boolean isFloorSurBou[NSurBou]= surBou.isFloor "Flag to indicate if floor for constructions that are modeled outside of this room"; HeatTransfer.Windows.BaseClasses.ShadingSignal shaSig[NConExtWin]( each final haveShade=haveShade) if haveConExtWin "Shading signal"; Buildings.ThermalZones.Detailed.BaseClasses.HeatGain heaGai(final AFlo=AFlo) "Model to convert internal heat gains"; Buildings.ThermalZones.Detailed.BaseClasses.RadiationAdapter radiationAdapter; Modelica.Blocks.Math.Add add; Modelica.Blocks.Math.Add sumJToWin[NConExtWin]( each final k1=1, each final k2=1) if haveConExtWin "Sum of radiosity flows from room surfaces toward the window"; HeatTransfer.Radiosity.RadiositySplitter radShaOut[NConExtWin] if haveConExtWin "Splitter for radiosity that strikes shading device or unshaded part of window"; Modelica.Blocks.Math.Sum sumJFroWin[NConExtWin](each nin=if haveShade then 2 else 1) if haveConExtWin "Sum of radiosity fom window to room surfaces"; Modelica.Thermal.HeatTransfer.Sources.PrescribedTemperature TSha[NConExtWin] if haveShade "Temperature of shading device"; initial equation assert(homotopyInitialization, "In " + getInstanceName() + ": The constant homotopyInitialization has been modified from its default value. This constant will be removed in future releases.", level = AssertionLevel.warning); equation connect(conBou.opa_a, surf_conBou); connect(bouConExtWin.opa_a, conExtWin.opa_a); connect(conExtWin.JInUns_a, bouConExtWin.JOutUns); connect(bouConExtWin.JInUns, conExtWin.JOutUns_a); connect(conExtWin.glaUns_a, bouConExtWin.glaUns); connect(bouConExtWin.glaSha, conExtWin.glaSha_a); connect(conExtWin.JInSha_a, bouConExtWin.JOutSha); connect(bouConExtWin.JInSha, conExtWin.JOutSha_a); connect(conExtWin.fra_a, bouConExtWin.fra); connect(conExt.opa_a, bouConExt.opa_a); connect(weaBus, bouConExtWin.weaBus); connect(weaBus, bouConExt.weaBus); connect(bouConExtWin.QAbsSolSha_flow, conExtWinRad.QAbsExtSha_flow); connect(bouConExtWin.inc, conExtWinRad.incAng); connect(bouConExtWin.HDir, conExtWinRad.HDir); connect(bouConExtWin.HDif, conExtWinRad.HDif); connect(conExtWin.QAbsSha_flow, conExtWinRad.QAbsGlaSha_flow); connect(conExtWinRad.QAbsGlaUns_flow, conExtWin.QAbsUns_flow); // Connect statements from the model BaseClasses.MixedAir connect(conExt.opa_b, irRadExc.conExt); connect(conExtWin.fra_b, irRadExc.conExtWinFra); connect(conPar.opa_a, irRadExc.conPar_a); connect(conPar.opa_b, irRadExc.conPar_b); connect(conBou.opa_b, irRadExc.conBou); connect(surf_surBou, irRadExc.conSurBou); connect(irRadGai.conExt, conExt.opa_b); connect(irRadGai.conExtWinFra, conExtWin.fra_b); connect(irRadGai.conPar_a, conPar.opa_a); connect(irRadGai.conPar_b, conPar.opa_b); connect(irRadGai.conBou, conBou.opa_b); connect(irRadGai.conSurBou, surf_surBou); connect(conExtWin.opa_b, irRadExc.conExtWin); connect(conExtWin.opa_b, irRadGai.conExtWin); connect(conExt.opa_b, solRadExc.conExt); connect(conExtWin.fra_b, solRadExc.conExtWinFra); connect(conPar.opa_a, solRadExc.conPar_a); connect(conPar.opa_b, solRadExc.conPar_b); connect(conBou.opa_b, solRadExc.conBou); connect(surf_surBou, solRadExc.conSurBou); connect(conExtWin.opa_b, solRadExc.conExtWin); connect(solRadExc.JInDifConExtWin, conExtWinRad.QTraDif_flow); connect(solRadExc.HOutConExtWin,conExtWinRad.HRoo); connect(conExt.opa_b, radTem.conExt); connect(conExtWin.opa_b, radTem.conExtWin); connect(conExtWin.fra_b, radTem.conExtWinFra); connect(conPar.opa_a, radTem.conPar_a); connect(conPar.opa_b, radTem.conPar_b); connect(conBou.opa_b, radTem.conBou); connect(surf_surBou, radTem.conSurBou); connect(radTem.glaUns, conExtWin.glaUns_b); connect(radTem.glaSha, conExtWin.glaSha_b); connect(radTem.TRad, radiationAdapter.TRad); connect(radiationAdapter.rad, heaPorRad); connect(radiationAdapter.QRad_flow, add.u1); connect(add.y, irRadGai.Q_flow); connect(irRadExc.JOutConExtWin, sumJToWin.u1); connect(irRadGai.JOutConExtWin, sumJToWin.u2); connect(shaSig.y, radShaOut.u); connect(shaSig.y, shaRad.u); connect(sumJToWin.y, radShaOut.JIn); connect(radShaOut.JOut_1, shaRad.JIn_air); connect(radShaOut.JOut_2, conExtWin.JInUns_b); connect(shaRad.JOut_glass, conExtWin.JInSha_b); connect(conExtWin.JOutSha_b, shaRad.JIn_glass); connect(irRadExc.JInConExtWin, sumJFroWin.y); connect(shaRad.QSolAbs_flow, conExtWinRad.QAbsIntSha_flow); connect(sumJFroWin.u[1], conExtWin.JOutUns_b); connect(sumJFroWin.u[2], shaRad.JOut_air); connect(radTem.sha, TSha.port); for i in 1:nPorts loop connect(ports[i],air. ports[i]); end for; connect(air.conExt, conExt.opa_b); connect(air.conExtWin, conExtWin.opa_b); connect(air.glaUns, conExtWin.glaUns_b); connect(air.glaSha, conExtWin.glaSha_b); connect(air.conExtWinFra, conExtWin.fra_b); connect(air.conPar_a, conPar.opa_a); connect(air.conPar_b, conPar.opa_b); connect(air.conBou, conBou.opa_b); connect(air.conSurBou, surf_surBou); connect(shaRad.QRadAbs_flow,air. QRadAbs_flow); connect(air.TSha, shaRad.TSha); connect(air.heaPorAir, heaPorAir); connect(air.TSha, TSha.T); connect(uWin, conExtWinRad.uSta); connect(qGai_flow,heaGai. qGai_flow); connect(air.QCon_flow,heaGai. QCon_flow); connect(air.QLat_flow,heaGai. QLat_flow); connect(heaGai.QRad_flow, add.u2); connect(conExtWinRad.QTraDir_flow, solRadExc.JInDirConExtWin); end RoomHeatMassBalance;

Buildings.ThermalZones.Detailed.BaseClasses.SkyRadiationExchange Buildings.ThermalZones.Detailed.BaseClasses.SkyRadiationExchange

Radiative heat exchange with the sky and the ambient

Buildings.ThermalZones.Detailed.BaseClasses.SkyRadiationExchange

Information

This model computes the infrared radiative heat flow between exterior building surfaces and the ambient. The ambient consists of the sky black-body radiation and the outdoor temperature (which is used as an approximation to the surface temperature of the ground and neighboring buildings).

Extends from Buildings.BaseClasses.BaseIcon (Base icon).

Parameters

TypeNameDefaultDescription
Integern Number of constructions
AreaA[n] Area of exterior constructions [m2]
RealvieFacSky[n] View factor to sky (=1 for roofs)
EmissivityabsIR[n] Infrared absorptivity of building surface [1]

Connectors

TypeNameDescription
HeatPort_aport[n]Heat port
input RealInputTOutOutside air temperature [K]
input RealInputTBlaSkyBlack body sky temperature [K]

Modelica definition

model SkyRadiationExchange "Radiative heat exchange with the sky and the ambient" extends Buildings.BaseClasses.BaseIcon; parameter Integer n(min=1) "Number of constructions"; parameter Modelica.SIunits.Area A[n] "Area of exterior constructions"; parameter Real vieFacSky[n]( each min=0, each max=1) "View factor to sky (=1 for roofs)"; parameter Modelica.SIunits.Emissivity absIR[n] "Infrared absorptivity of building surface"; Modelica.Thermal.HeatTransfer.Interfaces.HeatPort_a port[n] "Heat port"; Modelica.Blocks.Interfaces.RealInput TOut(final quantity="ThermodynamicTemperature", final unit = "K", min=0) "Outside air temperature"; Modelica.Blocks.Interfaces.RealInput TBlaSky( final quantity="ThermodynamicTemperature", final unit="K", min=0) "Black body sky temperature"; protected parameter Real k[n]( each unit="W/K4") = {4*A[i]*Modelica.Constants.sigma*absIR[i] for i in 1:n} "Constant for radiative heat exchange"; Modelica.SIunits.Temperature TEnv[n] "Environment temperature"; Real TBlaSky4(unit="K4") "Auxiliary variable for radiative heat exchange"; Real TOut4(unit="K4") "Auxiliary variable for radiative heat exchange"; Modelica.SIunits.CoefficientOfHeatTransfer h[n] "Radiative heat transfer coefficient"; equation TBlaSky4 = TBlaSky^4; TOut4 = TOut^4; for i in 1:n loop TEnv[i] = (vieFacSky[i] * TBlaSky4 + (1-vieFacSky[i]) * TOut4)^(0.25); // h[i] uses TEnv[i] instead of (port[i].T+TEnv[i])/2 to avoid // a nonlinear equation system h[i] = k[i] * TEnv[i]^3; port[i].Q_flow = h[i] * (port[i].T-TEnv[i]); end for; end SkyRadiationExchange;

Buildings.ThermalZones.Detailed.BaseClasses.SolarRadiationExchange Buildings.ThermalZones.Detailed.BaseClasses.SolarRadiationExchange

Solar radiation heat exchange between the room facing surfaces

Buildings.ThermalZones.Detailed.BaseClasses.SolarRadiationExchange

Information

This model computes the distribution of the solar radiation gain to the room surfaces. Let Nw denote the number of windows, Nf the number of floor elements and Nn the number of non-floor elements such as ceiling, wall and window elements. Input to the model are the diffuse and direct solar radiosities Jidif, i ∈ {1, … , Nw} and Jidir, i ∈ {1, … , Nw} that were transmitted through the window. The total incoming solar radiation is therefore for the diffuse irradiation

Hdif = ∑i=1Nw Jdifi

and for the direct irradiation

Hdir = ∑i=1Nw Jdiri.

It is assumed that the diffuse irradiation is distributed to all surfaces proportionally to the product of surface emissivity plus transmissivity (which generally is zero except for windows) times the area. For the direct irradiation, it is assumed that it first hits the floor where some of it is absorbed, and some of it is diffusely reflected to all other surfaces. Only the first reflection is taken into account and the location of the floor patch relative to the window is neglected.

Hence, the diffuse radiation that is absorbed by each area is

Qidif = Hdif   (εii)   Ai ⁄ ∑j=1N   Aj,

where the sum is over all areas. Hence, this calculation treats the wall that contains the window identical as any other construction, which is a simplification.

Similarly, the direct radiation that is absorbed by each floor patch i ∈ {1, …, Nf}, and may be partially transmitted in the unusual case that the floor contains a window, is

Qidir = Hdir   (εii)   Ai ⁄ ∑j=1Nf   Aj.

The sum of the direct radiation that is reflected by the floor is therefore

Jf = Hdir   ∑i=1Nf (1-εii)   Ai ⁄ ∑j=1Nf   Aj.

This reflected radiosity is then distributed to all non-floor areas i ∈ {1, …, Nn} using

Qidir = Jf   Ai   (εii) ⁄ ∑k=1Nn Ak   (εkk)

The heat flow rate that is absorbed by each surface is

Qi = Qidif + Qidir.

For opaque surfaces, the heat flow rate Qi is set to be equal to the heat flow rate at the heat port. For the glass of the windows, the heat flow rate Qi is set to the radiosity Jouti that will strike the glass or the window shade as diffuse solar radiation.

Main assumptions

The main assumptions or simplifications are that the shaded and unshaded part of the window have the same solar absorbtance. Furthermore, if the room has electrochromic windows, the optical properties are taken from the state 1, which generally is the uncontrolled state. The error should be small as in the controlled state, there is little solar radiation entering the room, and with this simplification, the main error is that the radiation that is reflected in the room and hits the window is larger than it otherwise would be. This simplification allows lumping the solar distribution into a parameter.

The model also assumes that all radiation first hits the floor from which it is diffusely distributed to the other surfaces.

Extends from Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterfaceRadiative (Partial model that is used for infrared radiation balance).

Parameters

TypeNameDefaultDescription
ParameterConstructiondatConExt[NConExt] Data for exterior construction
ParameterConstructionWithWindowdatConExtWin[NConExtWin] Data for exterior construction with window
ParameterConstructiondatConPar[NConPar] Data for partition construction
ParameterConstructiondatConBou[NConBou] Data for construction boundary
OpaqueSurfacesurBou[NSurBou] Record for data of surfaces whose heat conduction is modeled outside of this room
Brick120dummyCon Dummy construction to assign a parameter to the instance
SingleClear3dummyGlaSys Dummy construction to assign a parameter to the instance
BooleanisFloorConExt[NConExt] Flag to indicate if floor for exterior constructions
BooleanisFloorConExtWin[NConExtWin] Flag to indicate if floor for constructions
BooleanisFloorConPar_a[NConPar] Flag to indicate if floor for constructions
BooleanisFloorConPar_b[NConPar] Flag to indicate if floor for constructions
BooleanisFloorConBou[NConBou] Flag to indicate if floor for constructions with exterior boundary conditions exposed to outside of room model
BooleanisFloorSurBou[NSurBou] Flag to indicate if floor for constructions that are modeled outside of this room
EmissivitytauGla[NConExtWin] Transmissivity of window [1]
Exterior constructions
IntegernConExt Number of exterior constructions
IntegernConExtWin Number of window constructions
Partition constructions
IntegernConPar Number of partition constructions
Boundary constructions
IntegernConBou Number of constructions that have their outside surface exposed to the boundary of this room
IntegernSurBou Number of surface heat transfer models that connect to constructions that are modeled outside of this room

Connectors

TypeNameDescription
HeatPort_aconExt[NConExt]Heat port that connects to room-side surface of exterior constructions
HeatPort_aconExtWin[NConExtWin]Heat port that connects to room-side surface of exterior constructions that contain a window
HeatPort_aconExtWinFra[NConExtWin]Heat port that connects to room-side surface of window frame
HeatPort_aconPar_a[NConPar]Heat port that connects to room-side surface a of partition constructions
HeatPort_aconPar_b[NConPar]Heat port that connects to room-side surface b of partition constructions
HeatPort_aconBou[NConBou]Heat port that connects to room-side surface of constructions that expose their other surface to the outside
HeatPort_aconSurBou[NSurBou]Heat port to surfaces of models that compute the heat conduction outside of this room
input RealInputJInDifConExtWin[NConExtWin]Diffuse solar radiation transmitted by window per unit area [W]
input RealInputJInDirConExtWin[NConExtWin]Direct solar radiation transmitted by window per unit area [W]
output RealOutputHOutConExtWin[NConExtWin]Outgoing solar radiation that strikes window per unit area [W/m2]

Modelica definition

model SolarRadiationExchange "Solar radiation heat exchange between the room facing surfaces" extends Buildings.ThermalZones.Detailed.BaseClasses.PartialSurfaceInterfaceRadiative ( final epsConExt = datConExt.layers.absSol_b, final epsConExtWinOpa = datConExtWin.layers.absSol_b, final epsConExtWinUns={(1-datConExtWin[i].glaSys.glass[size(datConExtWin[i].glaSys.glass, 1)].tauSol[1] -datConExtWin[i].glaSys.glass[size(datConExtWin[i].glaSys.glass, 1)].rhoSol_b[1]) for i in 1:NConExtWin}, final epsConExtWinSha = {(1-datConExtWin[i].glaSys.glass[size(datConExtWin[i].glaSys.glass, 1)].tauSol[1] -datConExtWin[i].glaSys.glass[size(datConExtWin[i].glaSys.glass, 1)].rhoSol_b[1]) for i in 1:NConExtWin}, final epsConExtWinFra = datConExtWin.glaSys.absSolFra, final epsConPar_a = datConPar.layers.absSol_a, final epsConPar_b = datConPar.layers.absSol_b, final epsConBou = datConBou.layers.absSol_b, final epsSurBou = surBou.absSol); // In the above declaration, we simplified the assignment of epsConExtWinSha. // An exact formulation would need to take into account the transmission and reflection // of the shade for the solar radiation that strikes the window from the room-side. // The simplification leads to too low a value of epsConExtWinSha. Since epsConExtWinSha // is used as a weight for how much solar radiation hits the window from the room-side, // underestimating epsConExtWinSha does not seem to cause concerns. The reason is that // the model assumes diffuse reflection, whereas in reality, reflection of the solar // radiation at the floor is likely specular, and therefore less radiation would hit // the window from the room-side. parameter Boolean isFloorConExt[NConExt] "Flag to indicate if floor for exterior constructions"; parameter Boolean isFloorConExtWin[NConExtWin] "Flag to indicate if floor for constructions"; parameter Boolean isFloorConPar_a[NConPar] "Flag to indicate if floor for constructions"; parameter Boolean isFloorConPar_b[NConPar] "Flag to indicate if floor for constructions"; parameter Boolean isFloorConBou[NConBou] "Flag to indicate if floor for constructions with exterior boundary conditions exposed to outside of room model"; parameter Boolean isFloorSurBou[NSurBou] "Flag to indicate if floor for constructions that are modeled outside of this room"; parameter Modelica.SIunits.Emissivity tauGla[NConExtWin] "Transmissivity of window"; Modelica.Blocks.Interfaces.RealInput JInDifConExtWin[NConExtWin](each unit="W") "Diffuse solar radiation transmitted by window per unit area"; Modelica.Blocks.Interfaces.RealInput JInDirConExtWin[NConExtWin](each unit="W") "Direct solar radiation transmitted by window per unit area"; Modelica.Blocks.Interfaces.RealOutput HOutConExtWin[NConExtWin](each unit="W/m2") "Outgoing solar radiation that strikes window per unit area"; Modelica.SIunits.HeatFlowRate JOutConExtWin[NConExtWin] "Outgoing solar radiation that strikes the window"; protected final parameter Real kDir1(unit="1", fixed=false) "Intermediate variable for gain for direct solar radiation distribution"; final parameter Real kDir2(fixed=false) "Intermediate variable for gain for solar radiation distribution"; Modelica.SIunits.HeatFlowRate Q_flow[NTot] "Total solar radiation that is absorbed by the surfaces (or transmitted back through the glass)"; final parameter Integer NOpa = NConExt+2*NConExtWin+2*NConPar+NConBou+NSurBou "Number of opaque surfaces, including the window frame"; final parameter Integer NWin = NConExtWin "Number of window surfaces"; final parameter Integer NTot = NOpa + NWin "Total number of surfaces"; final parameter Boolean isFlo[NTot](each fixed=false) "Flag, true if a surface is a floor"; final parameter Real eps[NTot](each min=0, each max=1, each fixed=false) "Solar absorptivity"; final parameter Real tau[NTot](each min=0, each max=1, each fixed=false) "Solar transmissivity"; final parameter Modelica.SIunits.Area AFlo(fixed=false) "Total floor area"; final parameter Modelica.SIunits.Area A[NTot](each fixed=false) "Surface areas"; final parameter Real kDif[NTot]( each unit="1", each fixed=false) "Gain for diffuse solar radiation distribution"; final parameter Real kDir[NTot]( each unit="1", each fixed=false) "Gain for direct solar radiation distribution"; final parameter Real epsTauA[NTot]( each unit="m2", each fixed=false) "Product (eps[i]+tau[i])*A[i] for all surfaces"; final parameter Real sumEpsTauA(unit="m2", fixed=false) "Sum(epsTauA)"; initial equation // The next loops builds arrays that simplify // the model equations. // These arrays store the values of the constructios in the following order // [x[1:NConExt] x[1:NConPar] x[1: NConPar] x[1: NConBou] x[1: NSurBou] x[1: NConExtWin] x[1: NConExtWin]] // where x is epsOpa, AOpa or kOpa. // The last two entries are for the opaque wall that contains a window, and for the window frame. for i in 1:NConExt loop eps[i] = epsConExt[i]; A[i] = AConExt[i]; isFlo[i] = isFloorConExt[i]; end for; for i in 1:NConPar loop eps[i+NConExt] = epsConPar_a[i]; A[i+NConExt] = AConPar[i]; isFlo[i+NConExt] = isFloorConPar_a[i]; eps[i+NConExt+NConPar] = epsConPar_b[i]; A[i+NConExt+NConPar] = AConPar[i]; isFlo[i+NConExt+NConPar] = isFloorConPar_b[i]; end for; for i in 1:NConBou loop eps[i+NConExt+2*NConPar] = epsConBou[i]; A[i+NConExt+2*NConPar] = AConBou[i]; isFlo[i+NConExt+2*NConPar] = isFloorConBou[i]; end for; for i in 1:NSurBou loop eps[i+NConExt+2*NConPar+NConBou] = epsSurBou[i]; A[i+NConExt+2*NConPar+NConBou] = ASurBou[i]; isFlo[i+NConExt+2*NConPar+NConBou] = isFloorSurBou[i]; end for; for i in 1:NConExtWin loop // Opaque part of construction that has a window embedded eps[i+NConExt+2*NConPar+NConBou+NSurBou] = epsConExtWinOpa[i]; A[i+NConExt+2*NConPar+NConBou+NSurBou] = AConExtWinOpa[i]; isFlo[i+NConExt+2*NConPar+NConBou+NSurBou] = isFloorConExtWin[i]; // Window frame eps[i+NConExt+2*NConPar+NConBou+NSurBou+NConExtWin] = epsConExtWinFra[i]; A[i+NConExt+2*NConPar+NConBou+NSurBou+NConExtWin] = AConExtWinFra[i]; isFlo[i+NConExt+2*NConPar+NConBou+NSurBou+NConExtWin] = isFloorConExtWin[i]; end for; // Window glass for i in 1:NConExtWin loop // We simplify and assume that the shaded and unshaded part of the window // have the same solar absorbtance. // A further simplification is that the window is assumed to have the // optical properties of state 1, which for electrochromic windows is // the uncontrolled state. The error should be small as in the controlled state, // there is little solar radiation entering the room, and with this simplification, // the main error is that the radiation that is reflected in the room and hits the // window is larger than it otherwise would be. // This simplification allows lumping the solar distribution into // a parameter. eps[i+NConExt+2*NConPar+NConBou+NSurBou+2*NConExtWin] = epsConExtWinUns[i]; isFlo[i+NConExt+2*NConPar+NConBou+NSurBou+2*NConExtWin] = isFloorConExtWin[i]; A[i+NConExt+2*NConPar+NConBou+NSurBou+2*NConExtWin] = AConExtWinGla[i]; end for; // Vector with all surface areas. // The next loops build the array A that simplifies // the model equations. // These array stores the values of the constructios in the following order // [AOpa[1:NConExt] AOpa[1:NConPar] AOpa[1: NConPar] AOpa[1: NConBou] AOpa[1: NSurBou] // AOpa[1: NConExtWin] AOpa[1: NConExtWin] AGla[1: NConExtWin]] // since NWin=NConExtWin. // Solar transmissivity for i in 1:NOpa loop tau[i] = 0; end for; for i in 1:NWin loop tau[NOpa+i] = tauGla[i]; end for; // Sum of surface areas and products of emmissivity, transmissivity and area AFlo = sum( (if isFlo[i] then A[i] else 0) for i in 1:NTot); epsTauA = (eps .+ tau).*A; sumEpsTauA = sum(epsTauA[i] for i in 1:NTot); // Coefficients for distribution of diffuse solar irradiation inside the room. for i in 1:NTot loop kDif[i] = (eps[i] + tau[i])*A[i]/sumEpsTauA; end for; // Coefficients for distribution of direct solar radiation inside the room. // Coefficient that is used for non-floor areas. // The expression max(1E-20, AFlo) is used to prevent a division by zero in case AFlo=0. // The situation for AFlo=0 is caught by the assert statement. kDir1 = sum((if isFlo[i] then (A[i]*(1 - eps[i] - tau[i])) else 0) for i in 1: NTot)/max(1E-20, AFlo); kDir2 = sum((if isFlo[i] then 0 else epsTauA[i]) for i in 1:NTot); if (kDir2 > 1E-10) then for i in 1:NTot loop if isFlo[i] then kDir[i] = epsTauA[i]/AFlo; else kDir[i] =kDir1/kDir2*epsTauA[i]; end if; end for; else // This branch only happens if k2=0, i.e., there is no surface other than floors for i in 1:NTot loop if isFlo[i] then kDir[i] = A[i]/AFlo; else kDir[i] = 0; end if; end for; end if; // Test whether there is a floor inside this room assert( AFlo > 1E-10, "Error in parameters of the room model: The geometry is incorrect:\n" + " The room model must have a construction that is a floor,\n" + " and this construction must not have a window.\n" + " The parameters for the room model are such that there is no such construction.\n" + " Revise the model parameters."); // Test whether the distribution factors add up to one assert(abs(1 - sum(kDif)) < 1E-5, "Program error: Sum of diffuse solar distribution factors in room is not equal to one. kDif=" + String(sum(kDif))); assert(abs(1 - sum(kDir)) < 1E-5, "Program error: Sum of direct solar distribution factors in room is not equal to one. kDir=" + String(sum(kDir))); //////////////////////////////////////////////////////////////////// equation // Radiation that is absorbed by the surfaces Q_flow =-kDif .* sum(JInDifConExtWin) - kDir .* sum(JInDirConExtWin); // Assign heat exchange to connectors if haveConExt then for i in 1:NConExt loop Q_flow[i] = conExt[i].Q_flow; end for; else conExt[1].T = 293.15; end if; if haveConPar then for i in 1:NConPar loop Q_flow[i+NConExt] = conPar_a[i].Q_flow; Q_flow[i+NConExt+NConPar] = conPar_b[i].Q_flow; end for; else conPar_a[1].T = 293.15; conPar_b[1].T = 293.15; end if; if haveConBou then for i in 1:NConBou loop Q_flow[i+NConExt+2*NConPar] = conBou[i].Q_flow; end for; else conBou[1].T = 293.15; end if; if haveSurBou then for i in 1:NSurBou loop Q_flow[i+NConExt+2*NConPar+NConBou] = conSurBou[i].Q_flow; end for; else conSurBou[1].T = 293.15; end if; if haveConExtWin then for i in 1:NConExtWin loop Q_flow[i+NConExt+2*NConPar+NConBou+NSurBou] = conExtWin[i].Q_flow; Q_flow[i+NConExt+2*NConPar+NConBou+NSurBou+NConExtWin] = conExtWinFra[i].Q_flow; end for; else conExtWin[1].T = 293.15; conExtWinFra[1].T = 293.15; end if; // Windows for j in 1:NWin loop Q_flow[j+NOpa] = JOutConExtWin[j]; HOutConExtWin[j] = if (AConExtWinGla[j] > 1E-10) then JOutConExtWin[j] / AConExtWinGla[j] else 0; end for; end SolarRadiationExchange;

Buildings.ThermalZones.Detailed.BaseClasses.cfdExchangeData Buildings.ThermalZones.Detailed.BaseClasses.cfdExchangeData

Exchange data between CFD and Modelica

Information

This function calls a C function to conduct the data exchange between Modelica and CFD program during the coupled simulation.

Extends from Modelica.Icons.Function (Icon for functions).

Inputs

TypeNameDefaultDescription
Integerflag Communication flag to CFD
Timet Current Modelica simulation time to CFD [s]
Timedt Requested synchronization time step size [s]
Realu[nU] Input to CFD
IntegernU Number of inputs to CFD
IntegernY Number of outputs from CFD

Outputs

TypeNameDescription
TimemodTimReaCurrent model time from CFD [s]
Realy[nY]Output computed by CFD
IntegerretValReturn value for CFD simulation status

Modelica definition

function cfdExchangeData "Exchange data between CFD and Modelica" extends Modelica.Icons.Function; input Integer flag "Communication flag to CFD"; input Modelica.SIunits.Time t "Current Modelica simulation time to CFD"; input Modelica.SIunits.Time dt(min=100*Modelica.Constants.eps) "Requested synchronization time step size"; input Real[nU] u "Input to CFD"; input Integer nU "Number of inputs to CFD"; input Integer nY "Number of outputs from CFD"; output Modelica.SIunits.Time modTimRea "Current model time from CFD"; output Real[nY] y "Output computed by CFD"; output Integer retVal "Return value for CFD simulation status"; external"C" retVal = cfdExchangeData( t, dt, u, nU, nY, modTimRea, y); end cfdExchangeData;

Buildings.ThermalZones.Detailed.BaseClasses.cfdStartCosimulation Buildings.ThermalZones.Detailed.BaseClasses.cfdStartCosimulation

Start the coupled simulation with CFD

Information

This function calls a C function to start the coupled simulation with CFD.

Extends from Modelica.Icons.Function (Icon for functions).

Inputs

TypeNameDefaultDescription
StringcfdFilNam CFD input file name
Stringname[nSur] Surface names
AreaA[nSur] Surface areas [m2]
Angletil[nSur] Surface tilt [rad]
CFDBoundaryConditionsbouCon[nSur] Type of boundary condition
IntegernPorts Number of fluid ports for the HVAC inlet and outlets
StringportName[nPorts] Names of fluid ports as declared in the CFD input file
BooleanhaveSensor Flag, true if the model has at least one sensor
StringsensorName[nSen] Names of sensors as declared in the CFD input file
BooleanhaveShade Flag, true if the windows have a shade
IntegernSur Number of surfaces
IntegernSen Number of sensors that are connected to CFD output
IntegernConExtWin number of exterior construction with window
IntegernXi Number of independent species
IntegernC Number of trace substances
Densityrho_start Density at initial state [kg/m3]

Outputs

TypeNameDescription
IntegerretValReturn value of the function (0 indicates CFD successfully started.)

Modelica definition

function cfdStartCosimulation "Start the coupled simulation with CFD" extends Modelica.Icons.Function; input String cfdFilNam "CFD input file name"; input String[nSur] name "Surface names"; input Modelica.SIunits.Area[nSur] A "Surface areas"; input Modelica.SIunits.Angle[nSur] til "Surface tilt"; input Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions[nSur] bouCon "Type of boundary condition"; input Integer nPorts(min=0) "Number of fluid ports for the HVAC inlet and outlets"; input String portName[nPorts] "Names of fluid ports as declared in the CFD input file"; input Boolean haveSensor "Flag, true if the model has at least one sensor"; input String sensorName[nSen] "Names of sensors as declared in the CFD input file"; input Boolean haveShade "Flag, true if the windows have a shade"; input Integer nSur "Number of surfaces"; input Integer nSen(min=0) "Number of sensors that are connected to CFD output"; input Integer nConExtWin(min=0) "number of exterior construction with window"; input Integer nXi(min=0) "Number of independent species"; input Integer nC(min=0) "Number of trace substances"; input Modelica.SIunits.Density rho_start "Density at initial state"; output Integer retVal "Return value of the function (0 indicates CFD successfully started.)"; external"C" retVal = cfdStartCosimulation( cfdFilNam, name, A, til, bouCon, nPorts, portName, haveSensor, sensorName, haveShade, nSur, nSen, nConExtWin, nXi, nC, rho_start); end cfdStartCosimulation;

Buildings.ThermalZones.Detailed.BaseClasses.to_W Buildings.ThermalZones.Detailed.BaseClasses.to_W

Add unit [W] to data

Buildings.ThermalZones.Detailed.BaseClasses.to_W

Information

This component adds the unit [W] into the data.

Extends from Modelica.Blocks.Icons.Block (Basic graphical layout of input/output block).

Connectors

TypeNameDescription
input RealInputu 
output RealOutputyPower [W]

Modelica definition

block to_W "Add unit [W] to data" extends Modelica.Blocks.Icons.Block; Modelica.Blocks.Interfaces.RealInput u; Modelica.Blocks.Interfaces.RealOutput y(final quantity="Power", final unit= "W") "Power"; equation y = u; end to_W;

Buildings.ThermalZones.Detailed.BaseClasses.CFDSurfaceIdentifier Buildings.ThermalZones.Detailed.BaseClasses.CFDSurfaceIdentifier

Data record to identify surfaces in the CFD code

Information

This record is a data structure that is used to assemble information that is used in the CFD to identify surface data that are exchanged with Modelica.

Extends from Modelica.Icons.Record (Icon for records).

Modelica definition

record CFDSurfaceIdentifier "Data record to identify surfaces in the CFD code" extends Modelica.Icons.Record; String name "Name of the surface"; Modelica.SIunits.Area A "Area of the surface"; Modelica.SIunits.Angle til "Tilt of the surface"; Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions bouCon "Boundary condition used in the CFD simulation"; end CFDSurfaceIdentifier;

Buildings.ThermalZones.Detailed.BaseClasses.ConstructionNumbers Buildings.ThermalZones.Detailed.BaseClasses.ConstructionNumbers

Data records for construction data

Information

Record that defines the number of constructions that are used in the room model.

This record also declares parameters that contain the number of constructions, such as the number of exterior constructions nConExt. This parameter may take on the value 0. If this parameter were to be used to declare the size of vectors of component models, then there may be vectors with zero components. This can cause problems in Dymola 7.4. Therefore, a parameter is declared in the form

  NConExt = max(1, nConExt)

This parameter is the used by models that extend this model to set the size of the vector of component models.

There are also parameters that can be used to conditionally remove components, such as haveConExt, which is set to

  haveConExt = nConExt > 0;

Extends from Modelica.Icons.Record (Icon for records).

Parameters

TypeNameDefaultDescription
Exterior constructions
IntegernConExt Number of exterior constructions
IntegernConExtWin Number of window constructions
Partition constructions
IntegernConPar Number of partition constructions
Boundary constructions
IntegernConBou Number of constructions that have their outside surface exposed to the boundary of this room
IntegernSurBou Number of surface heat transfer models that connect to constructions that are modeled outside of this room

Modelica definition

record ConstructionNumbers "Data records for construction data" extends Modelica.Icons.Record; //////////////////////////////////////////////////////////////////////// // Number of constructions and surface areas parameter Integer nConExt(min=0) "Number of exterior constructions"; parameter Integer nConExtWin(min=0) "Number of window constructions"; parameter Integer nConPar(min=0) "Number of partition constructions"; parameter Integer nConBou(min=0) "Number of constructions that have their outside surface exposed to the boundary of this room"; parameter Integer nSurBou(min=0) "Number of surface heat transfer models that connect to constructions that are modeled outside of this room"; // Dimensions of components and connectors final parameter Integer NConExt(min=1) = max(1, nConExt) "Number of elements for exterior constructions"; final parameter Integer NConExtWin(min=1)=max(1, nConExtWin) "Number of elements for exterior constructions with windows"; final parameter Integer NConPar(min=1)=max(1, nConPar) "Number of elements for partition constructions"; final parameter Integer NConBou(min=1)=max(1, nConBou) "Number of elements for constructions that have their outside surface exposed to the boundary of this room"; final parameter Integer NSurBou(min=1)=max(1, nSurBou) "Number of elements for surface heat transfer models that connect to constructions that are modeled outside of this room"; // Flags to conditionally remove components final parameter Boolean haveConExt = nConExt > 0 "Flag to conditionally remove components"; final parameter Boolean haveConExtWin = nConExtWin > 0 "Flag to conditionally remove components"; final parameter Boolean haveConPar = nConPar > 0 "Flag to conditionally remove components"; final parameter Boolean haveConBou = nConBou > 0 "Flag to conditionally remove components"; final parameter Boolean haveSurBou = nSurBou > 0 "Flag to conditionally remove components"; end ConstructionNumbers;

Buildings.ThermalZones.Detailed.BaseClasses.ConstructionRecords Buildings.ThermalZones.Detailed.BaseClasses.ConstructionRecords

Data records for construction data

Buildings.ThermalZones.Detailed.BaseClasses.ConstructionRecords

Information

Record that defines the number of constructions that are used in the room model.

Extends from Buildings.ThermalZones.Detailed.BaseClasses.ConstructionNumbers (Data records for construction data).

Parameters

TypeNameDefaultDescription
ParameterConstructiondatConExt[NConExt]datConExt(each A=0, each lay...Data for exterior construction
ParameterConstructionWithWindowdatConExtWin[NConExtWin]datConExtWin(each A=0, each ...Data for exterior construction with window
ParameterConstructiondatConPar[NConPar]datConPar(each A=0, each lay...Data for partition construction
ParameterConstructiondatConBou[NConBou]datConBou(each A=0, each lay...Data for construction boundary
OpaqueSurfacesurBou[NSurBou]surBou(each A=0, each til=0)Record for data of surfaces whose heat conduction is modeled outside of this room
Brick120dummyCon Dummy construction to assign a parameter to the instance
SingleClear3dummyGlaSys Dummy construction to assign a parameter to the instance
Exterior constructions
IntegernConExt Number of exterior constructions
IntegernConExtWin Number of window constructions
Partition constructions
IntegernConPar Number of partition constructions
Boundary constructions
IntegernConBou Number of constructions that have their outside surface exposed to the boundary of this room
IntegernSurBou Number of surface heat transfer models that connect to constructions that are modeled outside of this room

Modelica definition

record ConstructionRecords "Data records for construction data" extends Buildings.ThermalZones.Detailed.BaseClasses.ConstructionNumbers; parameter ParameterConstruction datConExt[NConExt]( each A=0, each layers = dummyCon, each til=0, each azi=0) "Data for exterior construction"; parameter Buildings.ThermalZones.Detailed.BaseClasses.ParameterConstructionWithWindow datConExtWin[NConExtWin]( each A=0, each layers = dummyCon, each til=0, each azi=0, each hWin=0, each wWin=0, each glaSys=dummyGlaSys) "Data for exterior construction with window"; parameter Buildings.ThermalZones.Detailed.BaseClasses.ParameterConstruction datConPar[NConPar]( each A=0, each layers = dummyCon, each til=0, each azi=0) "Data for partition construction"; parameter Buildings.ThermalZones.Detailed.BaseClasses.ParameterConstruction datConBou[NConBou]( each A=0, each layers = dummyCon, each til=0, each azi=0) "Data for construction boundary"; parameter Buildings.ThermalZones.Detailed.BaseClasses.OpaqueSurface surBou[NSurBou]( each A=0, each til=0) "Record for data of surfaces whose heat conduction is modeled outside of this room"; // Dummy constructions to assign values to parameters. // The actual assignments will be overwritten by models that extend this model. // Note that parameters in records cannot be protected. However, we set the // annotation HideResult=true to avoid that they show up in the output file. parameter HeatTransfer.Data.OpaqueConstructions.Brick120 dummyCon "Dummy construction to assign a parameter to the instance"; parameter Buildings.HeatTransfer.Data.GlazingSystems.SingleClear3 dummyGlaSys "Dummy construction to assign a parameter to the instance"; end ConstructionRecords;

Buildings.ThermalZones.Detailed.BaseClasses.OpaqueSurface Buildings.ThermalZones.Detailed.BaseClasses.OpaqueSurface

Record for exterior constructions that have no window

Information

This data record is used to set the parameters of opaque surfaces.

The surface tilt is defined in Buildings.Types.Tilt

Extends from Buildings.HeatTransfer.Data.OpaqueSurfaces.Generic (Thermal properties of opaque surfaces).

Parameters

TypeNameDefaultDescription
AreaA Area [m2]
Angletil Surface tilt (0: ceiling, pi/2: wall, pi: floor [rad]
EmissivityabsIR0.84Infrared absorptivity [1]
EmissivityabsSol0.84Solar absorptivity [1]
Stringname""Surface name. Optional for MixedAir, required for CFD.
Boundary condition
CFDBoundaryConditionsboundaryConditionBuildings.ThermalZones.Detai...Boundary condition used in the CFD simulation

Modelica definition

record OpaqueSurface "Record for exterior constructions that have no window" extends Buildings.HeatTransfer.Data.OpaqueSurfaces.Generic; parameter String name = "" "Surface name. Optional for MixedAir, required for CFD."; parameter Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions boundaryCondition= Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions.Temperature "Boundary condition used in the CFD simulation"; end OpaqueSurface;

Buildings.ThermalZones.Detailed.BaseClasses.Overhang Buildings.ThermalZones.Detailed.BaseClasses.Overhang

Record for window overhang

Information

This record declares parameters for window overhangs.

See Buildings.HeatTransfer.Windows.Overhang for an explanation of the parameters, and for the assumptions and limitations of the overhang model.

Extends from Modelica.Icons.Record (Icon for records).

Parameters

TypeNameDefaultDescription
Overhang
LengthwL Overhang width left to the window, measured from the window corner [m]
LengthwR Overhang width right to the window, measured from the window corner [m]
Lengthdep Overhang depth (measured perpendicular to the wall plane) [m]
Lengthgap Distance between window upper edge and overhang lower edge [m]

Modelica definition

record Overhang "Record for window overhang" extends Modelica.Icons.Record; parameter Modelica.SIunits.Length wL(min=0) "Overhang width left to the window, measured from the window corner"; parameter Modelica.SIunits.Length wR(min=0) "Overhang width right to the window, measured from the window corner"; parameter Modelica.SIunits.Length dep(min=0) "Overhang depth (measured perpendicular to the wall plane)"; parameter Modelica.SIunits.Length gap(min=0) "Distance between window upper edge and overhang lower edge"; final parameter Boolean haveOverhang= dep > Modelica.Constants.eps "Flag, true if the window has an overhang"; end Overhang;

Buildings.ThermalZones.Detailed.BaseClasses.ParameterConstruction Buildings.ThermalZones.Detailed.BaseClasses.ParameterConstruction

Record for exterior constructions that have no window

Information

This data record is used to set the parameters of constructions that do not have a window.

The surface azimuth is defined in Buildings.Types.Azimuth and the surface tilt is defined in Buildings.Types.Tilt

Extends from Buildings.ThermalZones.Detailed.BaseClasses.PartialParameterConstruction (Partial record for constructions).

Parameters

TypeNameDefaultDescription
Stringname""Surface name. Optional for MixedAir, required for FFD.
Angletil Surface tilt [rad]
Angleazi Surface azimuth [rad]
AreaA Heat transfer area [m2]
Opaque construction
Genericlayers Material properties of opaque construction
Initialization
BooleansteadyStateInitialfalse=true initializes dT(0)/dt=0, false initializes T(0) at fixed temperature using T_a_start and T_b_start
TemperatureT_a_start293.15Initial temperature at port_a, used if steadyStateInitial = false [K]
TemperatureT_b_start293.15Initial temperature at port_b, used if steadyStateInitial = false [K]
Boundary condition
CFDBoundaryConditionsboundaryConditionBuildings.ThermalZones.Detai...Boundary condition used in the CFD simulation
Dynamics
BooleanstateAtSurface_atrue=true, a state will be at the surface a
BooleanstateAtSurface_btrue=true, a state will be at the surface b

Modelica definition

record ParameterConstruction "Record for exterior constructions that have no window" extends Buildings.ThermalZones.Detailed.BaseClasses.PartialParameterConstruction; parameter Modelica.SIunits.Area A "Heat transfer area"; end ParameterConstruction;

Buildings.ThermalZones.Detailed.BaseClasses.ParameterConstructionWithWindow Buildings.ThermalZones.Detailed.BaseClasses.ParameterConstructionWithWindow

Record for exterior constructions that have a window

Buildings.ThermalZones.Detailed.BaseClasses.ParameterConstructionWithWindow

Information

This data record is used to set the parameters of constructions that do have a window.

The surface azimuth is defined in Buildings.Types.Azimuth and the surface tilt is defined in Buildings.Types.Tilt

Extends from Buildings.ThermalZones.Detailed.BaseClasses.PartialParameterConstruction (Partial record for constructions).

Parameters

TypeNameDefaultDescription
Stringname""Surface name. Optional for MixedAir, required for FFD.
Angletil Surface tilt [rad]
Angleazi Surface azimuth [rad]
AreaA Heat transfer area of opaque construction and window combined [m2]
Opaque construction
Genericlayers Material properties of opaque construction
Initialization
BooleansteadyStateInitialfalse=true initializes dT(0)/dt=0, false initializes T(0) at fixed temperature using T_a_start and T_b_start
TemperatureT_a_start293.15Initial temperature at port_a, used if steadyStateInitial = false [K]
TemperatureT_b_start293.15Initial temperature at port_b, used if steadyStateInitial = false [K]
Boundary condition
CFDBoundaryConditionsboundaryConditionBuildings.ThermalZones.Detai...Boundary condition used in the CFD simulation
Glazing system
LengthhWin Window height [m]
LengthwWin Window width [m]
RealfFra0.1Fraction of window frame divided by total window area
Overhangoveove(wR=0, wL=0, dep=0, gap=0)Geometry of overhang
SideFinssidFinsidFin(h=0, dep=0, gap=0)Geometry of side fins
GenericglaSys Material properties of glazing system
Dynamics
BooleanstateAtSurface_atrue=true, a state will be at the surface a
BooleanstateAtSurface_btrue=true, a state will be at the surface b

Modelica definition

record ParameterConstructionWithWindow "Record for exterior constructions that have a window" extends Buildings.ThermalZones.Detailed.BaseClasses.PartialParameterConstruction; parameter Modelica.SIunits.Area A "Heat transfer area of opaque construction and window combined"; parameter Modelica.SIunits.Length hWin "Window height"; parameter Modelica.SIunits.Length wWin "Window width"; final parameter Modelica.SIunits.Area AWin=hWin*wWin "Heat transfer area of window"; final parameter Modelica.SIunits.Area AOpa = A-AWin "Heat transfer area of opaque construction"; parameter Real fFra( final min=0, final max=1) = 0.1 "Fraction of window frame divided by total window area"; parameter Buildings.ThermalZones.Detailed.BaseClasses.Overhang ove( wR=0, wL=0, dep=0, gap=0) "Geometry of overhang"; parameter Buildings.ThermalZones.Detailed.BaseClasses.SideFins sidFin(h=0, dep=0, gap=0) "Geometry of side fins"; final parameter Modelica.SIunits.Area AFra = fFra*AWin "Frame area"; final parameter Modelica.SIunits.Area AGla=AWin - AFra "Glass area"; parameter HeatTransfer.Data.GlazingSystems.Generic glaSys "Material properties of glazing system"; final parameter Boolean haveOverhangOrSideFins = (ove.dep > 1E-8) or (sidFin.dep > 1E-8) "Flag, true if the construction has either an overhang or side fins"; end ParameterConstructionWithWindow;

Buildings.ThermalZones.Detailed.BaseClasses.PartialParameterConstruction Buildings.ThermalZones.Detailed.BaseClasses.PartialParameterConstruction

Partial record for constructions

Information

This data record is used to set the parameters of constructions that do not have a window.

The surface azimuth is defined in Buildings.Types.Azimuth and the surface tilt is defined in Buildings.Types.Tilt

Extends from Modelica.Icons.Record (Icon for records).

Parameters

TypeNameDefaultDescription
Stringname""Surface name. Optional for MixedAir, required for FFD.
Angletil Surface tilt [rad]
Angleazi Surface azimuth [rad]
Opaque construction
Genericlayers Material properties of opaque construction
Initialization
BooleansteadyStateInitialfalse=true initializes dT(0)/dt=0, false initializes T(0) at fixed temperature using T_a_start and T_b_start
TemperatureT_a_start293.15Initial temperature at port_a, used if steadyStateInitial = false [K]
TemperatureT_b_start293.15Initial temperature at port_b, used if steadyStateInitial = false [K]
Boundary condition
CFDBoundaryConditionsboundaryConditionBuildings.ThermalZones.Detai...Boundary condition used in the CFD simulation
Dynamics
BooleanstateAtSurface_atrue=true, a state will be at the surface a
BooleanstateAtSurface_btrue=true, a state will be at the surface b

Modelica definition

record PartialParameterConstruction "Partial record for constructions" extends Modelica.Icons.Record; parameter String name = "" "Surface name. Optional for MixedAir, required for FFD."; parameter Buildings.HeatTransfer.Data.OpaqueConstructions.Generic layers "Material properties of opaque construction"; parameter Modelica.SIunits.Angle til "Surface tilt"; parameter Modelica.SIunits.Angle azi "Surface azimuth"; final parameter Boolean isFloor=til > 2.74889125 and til < 3.53428875 "Flag, true if construction is a floor"; final parameter Boolean isCeiling=til > -0.392699 and til < 0.392699 "Flag, true if construction is a floor"; // final parameter Integer nLay(min=1, fixed=true) = size(layers.material, 1) // "Number of layers"; // final parameter Integer nSta[:](each min=1)={layers.material[i].nSta for i in 1:size(layers.material, 1)} // "Number of states" annotation(Evaluate=true); parameter Boolean steadyStateInitial=false "=true initializes dT(0)/dt=0, false initializes T(0) at fixed temperature using T_a_start and T_b_start"; parameter Modelica.SIunits.Temperature T_a_start=293.15 "Initial temperature at port_a, used if steadyStateInitial = false"; parameter Modelica.SIunits.Temperature T_b_start=293.15 "Initial temperature at port_b, used if steadyStateInitial = false"; parameter Boolean stateAtSurface_a=true "=true, a state will be at the surface a"; parameter Boolean stateAtSurface_b=true "=true, a state will be at the surface b"; parameter Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions boundaryCondition= Buildings.ThermalZones.Detailed.Types.CFDBoundaryConditions.Temperature "Boundary condition used in the CFD simulation"; end PartialParameterConstruction;

Buildings.ThermalZones.Detailed.BaseClasses.SideFins Buildings.ThermalZones.Detailed.BaseClasses.SideFins

Record for window side fins

Information

This record declares parameters for window side fins.

See Buildings.HeatTransfer.Windows.SideFins for an explanation of the parameters, and for the assumptions and limitations of the model for side fins.

Extends from Modelica.Icons.Record (Icon for records).

Parameters

TypeNameDefaultDescription
Side fin
Lengthh Height of side fin that extends above window, measured from top of window [m]
Lengthdep Side fin depth (measured perpendicular to the wall plane) [m]
Lengthgap Distance between side fin and window edge [m]

Modelica definition

record SideFins "Record for window side fins" extends Modelica.Icons.Record; parameter Modelica.SIunits.Length h(min=0) "Height of side fin that extends above window, measured from top of window"; parameter Modelica.SIunits.Length dep(min=0) "Side fin depth (measured perpendicular to the wall plane)"; parameter Modelica.SIunits.Length gap(min=0) "Distance between side fin and window edge"; final parameter Boolean haveSideFins= dep > Modelica.Constants.eps "Flag, true if the window has side fins"; end SideFins;