Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.Examples.BaseClasses
This package contains base classes inherited by the examples
Information
This package contains base classes used by the examples that are part of the package Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.Examples.
Extends from Modelica.Icons.BasesPackage (Icon for packages containing base classes).
Package Content
| Name | Description | 
|---|---|
| This example represents the basic test for a transformer model | 
Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.Examples.BaseClasses.TransformerExample
This example represents the basic test for a transformer model
Information
This model is the base classes used by the examples that are part of the package Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.Examples.
The model has a voltage source, a transformer and a load. The transformer model is replaceable so that different types of transformers can easily be tested.
Extends from Modelica.Icons.Example (Icon for runnable examples).
Parameters
| Type | Name | Default | Description | 
|---|---|---|---|
| Voltage | V_primary | 12470 | RMS Voltage on the primary side of the transformer [V] | 
| Voltage | V_secondary | 4160 | RMS Voltage on the secondary side of the transformer [V] | 
| PartialConverter | tra | redeclare Buildings.Electric... | Transformer model | 
| GeneralizedProbe | probe_2 | redeclare Sensors.BaseClasse... | Probe that measures the voltage at the secondary side | 
Modelica definition
model TransformerExample
  "This example represents the basic test for a transformer model"
  extends Modelica.Icons.Example;
  parameter Modelica.SIunits.Voltage V_primary = 12470
    "RMS Voltage on the primary side of the transformer";
  parameter Modelica.SIunits.Voltage V_secondary = 4160
    "RMS Voltage on the secondary side of the transformer";
  Sources.FixedVoltage sou(
    f=60,
    V=V_primary) "Voltage source";
  replaceable Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.BaseClasses.PartialConverter
    tra "Transformer model";
  Loads.Resistive load(
    loadConn=Buildings.Electrical.Types.LoadConnection.wye_to_wyeg,
    P_nominal=-1800e3,
    V_nominal=V_secondary,
    linearized=true)       "Load model";
  Sensors.ProbeWye probe_Y_1(perUnit=false, V_nominal = V_primary)
    "Probe that measures the voltage in Y configuration, primary side";
  Sensors.ProbeDelta probe_D_1(perUnit=false, V_nominal = V_primary)
    "Probe that measures the voltage in D configuration, primary side";
  replaceable Sensors.BaseClasses.GeneralizedProbe probe_2 constrainedby Sensors.BaseClasses.GeneralizedProbe
    (                                    perUnit=false,
    V_nominal=V_secondary)
    "Probe that measures the voltage at the secondary side";
equation 
  connect(sou.terminal, tra.terminal_n);
  connect(probe_Y_1.term, tra.terminal_n);
  connect(probe_D_1.term, tra.terminal_n);
  connect(tra.terminal_p, load.terminal);