Buildings.Air.Systems.SingleZone.VAV.BaseClasses.Validation
Information
This package contains validations for the models that can be found in Buildings.Air.Systems.SingleZone.VAV.BaseClasses.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
Package Content
| Name | Description | 
|---|---|
|  ControllerChillerDXHeatingEconomizer | Validate the block ControllerChillerDXHeatingEconomizer | 
|  ControllerEconomizer | Validate the block ControllerEconomizer | 
|  ControllerHeatingFan | Validate the block ControllerHeatingFan | 
 Buildings.Air.Systems.SingleZone.VAV.BaseClasses.Validation.ControllerChillerDXHeatingEconomizer
Buildings.Air.Systems.SingleZone.VAV.BaseClasses.Validation.ControllerChillerDXHeatingEconomizer
Validate the block ControllerChillerDXHeatingEconomizer
 
Information
Validation test for the block Buildings.Air.Systems.SingleZone.VAV.BaseClasses.ControllerChillerDXHeatingEconomizer.
The inputs include:
- 
Mixed air temperature mixAirTem, varying from 12.5 °C to 27.5 °C
- 
Return air temperature retAirTem, varying from 11.0 °C to 31.0 °C
- 
Outdoor air temperature outAirTem, varying from 12.0 °C to 24.0 °C
- 
Zone air temperature heating setpoint TSetRooHea, varying from 15.0 °C to 18.0 °C according to occupancy.
- 
Zone air temperature cooling setpoint occSch, with occupied hours between 08:00 and 18:00.
- 
Occupancy schedule supAirTem, varying from 20 °C to 6 °C
- 
Supply air temperature supAirTem, varying from 20 °C to 6 °C
Extends from Modelica.Icons.Example (Icon for runnable examples).
Modelica definition
 Buildings.Air.Systems.SingleZone.VAV.BaseClasses.Validation.ControllerEconomizer
Buildings.Air.Systems.SingleZone.VAV.BaseClasses.Validation.ControllerEconomizer
Validate the block ControllerEconomizer
 
Information
Validation test for the block Buildings.Air.Systems.SingleZone.VAV.BaseClasses.ControllerEconomizer.
The inputs include:
- 
Mixed air temperature mixAirTem, varying from 12.5 °C to 27.5 °C
- 
Return air temperature retAirTem, varying from 17.0 °C to 25.0 °C
- 
Mixed air temperature setpoint mixAirTemSet, varying from 15.0 °C to 25.0 °C
- 
Outdoor air temperature outAirTem, varying from 12.0 °C to 24.0 °C
- 
Minimum outdoor air fraction minOutAirFra, varying from 0.05 to 0.35
- 
Cooling status signal cooSta, set to true.
Extends from Modelica.Icons.Example (Icon for runnable examples).
Modelica definition
 Buildings.Air.Systems.SingleZone.VAV.BaseClasses.Validation.ControllerHeatingFan
Buildings.Air.Systems.SingleZone.VAV.BaseClasses.Validation.ControllerHeatingFan
Validate the block ControllerHeatingFan
 
Information
Validation test for the block Buildings.Air.Systems.SingleZone.VAV.BaseClasses.ControllerHeatingFan.
The sine inputs include:- 
Zone heating setpoint zonHeaSet, varying from 19.0 °C to 21.0 °C
- 
Zone cooling setpoint zonCooSet, varying from 23.0 °C to 27.0 °C
- 
Zone temperature zonTem, varying from 17.0 °C to 25.0 °C
Extends from Modelica.Icons.Example (Icon for runnable examples).