Buildings.Fluid.MixingVolumes.BaseClasses
Package with base classes for Buildings.Fluid.MixingVolumes
Information
This package contains base classes that are used to construct the models in Buildings.Fluid.MixingVolumes.
Extends from Modelica.Icons.BasesPackage (Icon for packages containing base classes).
Package Content
Name | Description |
---|---|
MixingVolumeHeatMoisturePort | Mixing volume with heat and moisture port and initialize_p not set to final |
MixingVolumeHeatPort | Mixing volume with heat port and initialize_p not set to final |
PartialMixingVolume | Partial mixing volume with inlet and outlet ports (flow reversal is allowed) |
Validation | Collection of validation models |
Buildings.Fluid.MixingVolumes.BaseClasses.MixingVolumeHeatMoisturePort
Mixing volume with heat and moisture port and initialize_p not set to final
Information
Mixing volume with a heat port.
This model is identical to Buildings.Fluid.MixingVolumes.BaseClasses.PartialMixingVolume, except that it has a heat and a moisture port.
Note that this model is typically only used to implement new component models that
have staggered volumes.
In contrast to
Buildings.Fluid.MixingVolumes.MixingVolumeMoistAir, it does
not set initialize_p
to final
in order
for this model to be usable in staggered volumes which require one
pressure to be set to initialize_p = not Medium.singleState
and all others to false
.
Extends from Buildings.Fluid.MixingVolumes.BaseClasses.PartialMixingVolume (Partial mixing volume with inlet and outlet ports (flow reversal is allowed)).
Parameters
Type | Name | Default | Description |
---|---|---|---|
replaceable package Medium | PartialMedium | Medium in the component | |
Volume | V | Volume [m3] | |
Nominal condition | |||
MassFlowRate | m_flow_nominal | Nominal mass flow rate [kg/s] | |
Dynamics | |||
Equations | |||
Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
Dynamics | massDynamics | energyDynamics | Type of mass balance: dynamic (3 initialization options) or steady state |
Real | mSenFac | 1 | Factor for scaling the sensible thermal mass of the volume |
Initialization | |||
AbsolutePressure | p_start | Medium.p_default | Start value of pressure [Pa] |
Temperature | T_start | Medium.T_default | Start value of temperature [K] |
MassFraction | X_start[Medium.nX] | Medium.X_default | Start value of mass fractions m_i/m [kg/kg] |
ExtraProperty | C_start[Medium.nC] | fill(0, Medium.nC) | Start value of trace substances |
ExtraProperty | C_nominal[Medium.nC] | fill(1E-2, Medium.nC) | Nominal value of trace substances. (Set to typical order of magnitude.) |
Advanced | |||
Boolean | initialize_p | not Medium.singleState | = true to set up initial equations for pressure |
MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
Assumptions | |||
Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal. Used only if model has two ports. |
Connectors
Type | Name | Description |
---|---|---|
VesselFluidPorts_b | ports[nPorts] | Fluid inlets and outlets |
output RealOutput | U | Internal energy of the component [J] |
output RealOutput | m | Mass of the component [kg] |
output RealOutput | mXi[Medium.nXi] | Species mass of the component [kg] |
output RealOutput | mC[Medium.nC] | Trace substance mass of the component [kg] |
input RealInput | mWat_flow | Water flow rate added into the medium [kg/s] |
output RealOutput | X_w | Species composition of medium [kg/kg] |
HeatPort_a | heatPort | Heat port for heat exchange with the control volume |
Modelica definition
Buildings.Fluid.MixingVolumes.BaseClasses.MixingVolumeHeatPort
Mixing volume with heat port and initialize_p not set to final
Information
Mixing volume with a heat port.
This model is identical to Buildings.Fluid.MixingVolumes.BaseClasses.PartialMixingVolume, except that it has a heat port.
Note that this model is typically only used to implement new component models that
have staggered volumes.
In contrast to
Buildings.Fluid.MixingVolumes.MixingVolume, it does
not set initialize_p
to final
in order
for this model to be usable in staggered volumes which require one
pressure to be set to initialize_p = not Medium.singleState
and all others to false
.
Extends from Buildings.Fluid.MixingVolumes.BaseClasses.PartialMixingVolume (Partial mixing volume with inlet and outlet ports (flow reversal is allowed)).
Parameters
Type | Name | Default | Description |
---|---|---|---|
replaceable package Medium | PartialMedium | Medium in the component | |
Volume | V | Volume [m3] | |
Nominal condition | |||
MassFlowRate | m_flow_nominal | Nominal mass flow rate [kg/s] | |
Dynamics | |||
Equations | |||
Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
Dynamics | massDynamics | energyDynamics | Type of mass balance: dynamic (3 initialization options) or steady state |
Real | mSenFac | 1 | Factor for scaling the sensible thermal mass of the volume |
Initialization | |||
AbsolutePressure | p_start | Medium.p_default | Start value of pressure [Pa] |
Temperature | T_start | Medium.T_default | Start value of temperature [K] |
MassFraction | X_start[Medium.nX] | Medium.X_default | Start value of mass fractions m_i/m [kg/kg] |
ExtraProperty | C_start[Medium.nC] | fill(0, Medium.nC) | Start value of trace substances |
ExtraProperty | C_nominal[Medium.nC] | fill(1E-2, Medium.nC) | Nominal value of trace substances. (Set to typical order of magnitude.) |
Advanced | |||
Boolean | initialize_p | not Medium.singleState | = true to set up initial equations for pressure |
MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
Assumptions | |||
Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal. Used only if model has two ports. |
Connectors
Type | Name | Description |
---|---|---|
VesselFluidPorts_b | ports[nPorts] | Fluid inlets and outlets |
output RealOutput | U | Internal energy of the component [J] |
output RealOutput | m | Mass of the component [kg] |
output RealOutput | mXi[Medium.nXi] | Species mass of the component [kg] |
output RealOutput | mC[Medium.nC] | Trace substance mass of the component [kg] |
HeatPort_a | heatPort | Heat port for heat exchange with the control volume |
Modelica definition
Buildings.Fluid.MixingVolumes.BaseClasses.PartialMixingVolume
Partial mixing volume with inlet and outlet ports (flow reversal is allowed)
Information
This is a partial model of an instantaneously mixed volume. It is used as the base class for all fluid volumes of the package Buildings.Fluid.MixingVolumes.
Typical use and important parameters
Set the constant sensibleOnly=true
if the model that extends
or instantiates this model sets mWat_flow = 0
.
Set the constant simplify_mWat_flow = true
to simplify the equation
port_a.m_flow + port_b.m_flow = - mWat_flow;
to
port_a.m_flow + port_b.m_flow = 0;
This causes an error in the mass balance of about 0.5%, but generally leads to simpler equations because the pressure drop equations are then decoupled from the mass exchange in this component.
To increase the numerical robustness of the model, the constant
prescribedHeatFlowRate
can be set by the user.
This constant only has an effect if the model has exactly two fluid ports connected,
and if it is used as a steady-state model.
Use the following settings:
- Set
prescribedHeatFlowRate=true
if the only means of heat transfer at theheatPort
is a prescribed heat flow rate that is not a function of the temperature difference between the medium and an ambient temperature. Examples include an ideal electrical heater, a pump that rejects heat into the fluid stream, or a chiller that removes heat based on a performance curve. If theheatPort
is not connected, then setprescribedHeatFlowRate=true
as in this case,heatPort.Q_flow=0
. - Set
prescribedHeatFlowRate=false
if there is heat flow at theheatPort
computed as K * (T-heatPort.T), for some temperature T and some conductance K, which may itself be a function of temperature or mass flow rate.
If there is a combination of K * (T-heatPort.T) and a prescribed heat flow rate, for example a solar collector that dissipates heat to the ambient and receives heat from the solar radiation, then setprescribedHeatFlowRate=false
.
Set the parameter use_C_flow = true
to enable an input connector
for the trace substance flow rate.
Implementation
If the model is (i) operated in steady-state,
(ii) has two fluid ports connected, and
(iii) prescribedHeatFlowRate=true
or allowFlowReversal=false
,
then the model uses
Buildings.Fluid.Interfaces.StaticTwoPortConservationEquation
in order to use
the same energy and mass balance implementation as is used as in
steady-state component models.
In this situation, the functions inStream
are used for the two
flow directions rather than the function
actualStream
, which is less efficient.
However, the use of inStream
has the disadvantage
that hOut
has to be computed, in
Buildings.Fluid.Interfaces.StaticTwoPortConservationEquation,
using
if allowFlowReversal then hOut = Buildings.Utilities.Math.Functions.regStep(y1=port_b.h_outflow, y2=port_a.h_outflow, x=port_a.m_flow, x_small=m_flow_small/1E3); else hOut = port_b.h_outflow; end if;
Hence, for allowFlowReversal=true
, if hOut
were to be used to compute the temperature that
drives heat transfer such as by conduction,
then the heat transfer would depend on upstream and the downstream
temperatures for small mass flow rates.
This can give wrong results. Consider for example a mass flow rate that is positive
but very close to zero. Suppose the upstream temperature is 20°C,
the downstream temperature is 10°C, and the heat port is
connected through a heat conductor to a boundary condition of 20°C.
Then, hOut = (port_b.h_outflow + port_a.h_outflow)/2
and hence
the temperature heatPort.T
is 15°C. Therefore, heat is added to the component.
As the mass flow rate is by assumption very small, the fluid that leaves the component
will have a very high temperature, violating the 2nd law.
To avoid this situation, if
prescribedHeatFlowRate=false
, then the model
Buildings.Fluid.Interfaces.ConservationEquation
is used instead of
Buildings.Fluid.Interfaces.StaticTwoPortConservationEquation.
For simple models that uses this model, see Buildings.Fluid.MixingVolumes.
Extends from Buildings.Fluid.Interfaces.LumpedVolumeDeclarations (Declarations for lumped volumes).
Parameters
Type | Name | Default | Description |
---|---|---|---|
replaceable package Medium | PartialMedium | Medium in the component | |
Volume | V | Volume [m3] | |
Nominal condition | |||
MassFlowRate | m_flow_nominal | Nominal mass flow rate [kg/s] | |
Dynamics | |||
Equations | |||
Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state |
Dynamics | massDynamics | energyDynamics | Type of mass balance: dynamic (3 initialization options) or steady state |
Real | mSenFac | 1 | Factor for scaling the sensible thermal mass of the volume |
Initialization | |||
AbsolutePressure | p_start | Medium.p_default | Start value of pressure [Pa] |
Temperature | T_start | Medium.T_default | Start value of temperature [K] |
MassFraction | X_start[Medium.nX] | Medium.X_default | Start value of mass fractions m_i/m [kg/kg] |
ExtraProperty | C_start[Medium.nC] | fill(0, Medium.nC) | Start value of trace substances |
ExtraProperty | C_nominal[Medium.nC] | fill(1E-2, Medium.nC) | Nominal value of trace substances. (Set to typical order of magnitude.) |
Advanced | |||
Boolean | initialize_p | not Medium.singleState | = true to set up initial equations for pressure |
MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] |
Assumptions | |||
Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal. Used only if model has two ports. |
Connectors
Type | Name | Description |
---|---|---|
VesselFluidPorts_b | ports[nPorts] | Fluid inlets and outlets |
output RealOutput | U | Internal energy of the component [J] |
output RealOutput | m | Mass of the component [kg] |
output RealOutput | mXi[Medium.nXi] | Species mass of the component [kg] |
output RealOutput | mC[Medium.nC] | Trace substance mass of the component [kg] |