Buildings.Fluid.HeatExchangers.CoolingTowers.Correlations
Package with correlations for cooling tower performance
Information
This package contains the performance curve for the Buildings.Fluid.HeatExchangers.CoolingTowers.YorkCalc cooling tower model.
Extends from Modelica.Icons.MaterialProperty (Icon for property classes).
Package Content
| Name | Description |
|---|---|
| Cooling tower performance correlation for YorkCalc model | |
| Coefficient data record for properties of York cooling tower model | |
| Collection of models that illustrate model use and test models | |
| Package with base classes for Buildings.Fluid.HeatExchangers.CoolingTowers.Correlations |
Buildings.Fluid.HeatExchangers.CoolingTowers.Correlations.yorkCalc
Cooling tower performance correlation for YorkCalc model
Information
Correlation for approach temperature for YorkCalc cooling tower model. See Buildings.Fluid.HeatExchangers.CoolingTowers.Correlations.Examples.YorkCalc for the graph.
Inputs
| Type | Name | Default | Description |
|---|---|---|---|
| Temperature | TWetBul | Air wet-bulb inlet temperature [K] | |
| MassFraction | FRWat | Ratio actual over design water mass flow ratio [1] | |
| MassFraction | FRAir | Ratio actual over design air mass flow ratio [1] | |
| Nominal condition | |||
| TemperatureDifference | TRan | Range temperature (water in - water out) [K] | |
Outputs
| Type | Name | Description |
|---|---|---|
| TemperatureDifference | TApp | Approach temperature [K] |
Modelica definition
Buildings.Fluid.HeatExchangers.CoolingTowers.Correlations.BoundsYorkCalc
Coefficient data record for properties of York cooling tower model
Information
This data record contains the bounds for the YorkCalc cooling tower correlations.
Extends from Buildings.Fluid.HeatExchangers.CoolingTowers.Correlations.BaseClasses.Bounds (Coefficient data record for properties of cooling tower model).
Parameters
| Type | Name | Default | Description |
|---|---|---|---|
| Custom Parameters | |||
| Temperature | TAirInWB_min | 273.15 - 34.4 | Minimum air inlet wet bulb temperature [K] |
| Temperature | TAirInWB_max | 273.15 + 26.7 | Maximum air inlet wet bulb temperature [K] |
| Temperature | TRan_min | 1.1 | Minimum range temperature [K] |
| Temperature | TRan_max | 22.2 | Minimum range temperature [K] |
| Temperature | TApp_min | 1.1 | Minimum approach temperature [K] |
| Temperature | TApp_max | 40 | Minimum approach temperature [K] |
| Real | FRWat_min | 0.75 | Minimum water flow ratio |
| Real | FRWat_max | 1.25 | Maximum water flow ratio |
| Real | liqGasRat_max | 8 | Maximum liquid to gas ratio |