Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves
Package with sevral performance curves
Information
This package contains performance curves for the cooling capacity and the EIR of air-cooled DX cooling coils that are used in the examples.
For performance data of specific air-cooled DX cooling coils, see the packages Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.SingleSpeed and Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.DoubleSpeed.
The data are described in Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.Generic.DXCoil.
Package Content
Name | Description |
---|---|
Curve_I | Performance curve I |
Curve_II | Performance curve II |
Curve_III | Performance curve III |
Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves.Curve_I
Performance curve I
Information
This record declares performance curves for the cooling capacity and the EIR.
It has been obtained from the EnergyPlus 7.1 example file
AirflowNetwork_MultiZone_House.idf
.
Extends from Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Performance curves | |||
Real | capFunT[6] | {0.942587793,0.009543347,0.0... | Biquadratic coefficients for cooling capacity function of temperature |
Real | capFunFF[:] | {0.8,0.2,0,0} | Polynomial coefficients for cooling capacity function of flow fration |
Real | EIRFunT[6] | {0.342414409,0.034885008,-0.... | Biquadratic coefficients for EIR function of temperature |
Real | EIRFunFF[:] | {1.1552,-0.1808,0.0256,0} | Polynomial coefficients for EIR function of flow fration |
Minimum and maximum values | |||
Temperature | TConInMin | 291.15 | Minimum condenser inlet temperature for cooling capacity function [K] |
Temperature | TConInMax | 319.26111 | Maximum condenser inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMin | 285.92778 | Minimum evaporator inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMax | 297.03889 | Maximum evaporator inlet temperature for cooling capacity function [K] |
Real | ffMin | 0.6 | Minimum flow fraction for which performance data are valid |
Real | ffMax | 1.8 | Maximum flow fraction for which performance data are valid |
Modelica definition
Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves.Curve_II
Performance curve II
Information
This record declares performance curves for the cooling capacity and the EIR.
It has been obtained from the EnergyPlus 7.1 example file
DXCoilSystemAuto.idf
.
Extends from Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Performance curves | |||
Real | capFunT[6] | {0.766956,0.0107756,-0.00004... | Biquadratic coefficients for cooling capacity function of temperature |
Real | capFunFF[:] | {0.8,0.2,0,0} | Polynomial coefficients for cooling capacity function of flow fration |
Real | EIRFunT[6] | {0.297145,0.0430933,-0.00074... | Biquadratic coefficients for EIR function of temperature |
Real | EIRFunFF[:] | {1.1552,-0.1808,0.0256,0} | Polynomial coefficients for EIR function of flow fration |
Minimum and maximum values | |||
Temperature | TConInMin | 291.15 | Minimum condenser inlet temperature for cooling capacity function [K] |
Temperature | TConInMax | 319.26111 | Maximum condenser inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMin | 285.92778 | Minimum evaporator inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMax | 297.03889 | Maximum evaporator inlet temperature for cooling capacity function [K] |
Real | ffMin | 0.5 | Minimum flow fraction for which performance data are valid |
Real | ffMax | 1.5 | Maximum flow fraction for which performance data are valid |
Modelica definition
Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves.Curve_III
Performance curve III
Information
This record declares performance curves for the cooling capacity and the EIR.
It has been obtained from the EnergyPlus 7.1 example file
5ZoneAutoDXVAV.idf
.
Extends from Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Performance curves | |||
Real | capFunT[6] | {0.476428,0.0401147000,0.000... | Biquadratic coefficients for cooling capacity function of temperature |
Real | capFunFF[:] | {0.47278589,1.2433415,-1.038... | Polynomial coefficients for cooling capacity function of flow fration |
Real | EIRFunT[6] | {0.632475,-0.0121321000,0.00... | Biquadratic coefficients for EIR function of temperature |
Real | EIRFunFF[:] | {1.0079484,0.34544129,-0.692... | Polynomial coefficients for EIR function of flow fration |
Minimum and maximum values | |||
Temperature | TConInMin | 297.03889 | Minimum condenser inlet temperature for cooling capacity function [K] |
Temperature | TConInMax | 319.26111 | Maximum condenser inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMin | 285.92778 | Minimum evaporator inlet temperature for cooling capacity function [K] |
Temperature | TEvaInMax | 297.03889 | Maximum evaporator inlet temperature for cooling capacity function [K] |
Real | ffMin | 0.5 | Minimum flow fraction for which performance data are valid |
Real | ffMax | 1.5 | Maximum flow fraction for which performance data are valid |