Buildings.Controls.SetPoints.Examples

Collection of models that illustrate model use and test models

Information

This package contains examples for the use of models that can be found in Buildings.Controls.SetPoints.

Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).

Package Content

Name Description
Buildings.Controls.SetPoints.Examples.OccupancySchedule OccupancySchedule Test model for occupancy schedule with look-ahead
Buildings.Controls.SetPoints.Examples.SupplyReturnTemperatureReset SupplyReturnTemperatureReset Test model for the heating curve
Buildings.Controls.SetPoints.Examples.Table Table Test model for table that determines set points

Buildings.Controls.SetPoints.Examples.OccupancySchedule Buildings.Controls.SetPoints.Examples.OccupancySchedule

Test model for occupancy schedule with look-ahead

Buildings.Controls.SetPoints.Examples.OccupancySchedule

Information

Example that demonstrates the use of the occupancy schedule. The figure below shows how the time until the next occupancy starts or ends is decreased. The red line hits zero when the schedule indicates an occupied time, and the blue line hits zero when the schedule indicates a non-occupied time.

Time until next occupancy.

Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model OccupancySchedule "Test model for occupancy schedule with look-ahead" extends Modelica.Icons.Example; Buildings.Controls.SetPoints.OccupancySchedule occSchDay "Day schedule"; Buildings.Controls.SetPoints.OccupancySchedule occSchWee(occupancy=3600*{7,19, 31,43,55,67,79,91,103,115,127,139}, period=7*24*3600) "Week schedule"; end OccupancySchedule;

Buildings.Controls.SetPoints.Examples.SupplyReturnTemperatureReset Buildings.Controls.SetPoints.Examples.SupplyReturnTemperatureReset

Test model for the heating curve

Buildings.Controls.SetPoints.Examples.SupplyReturnTemperatureReset

Information

Example that demonstrates the use of the hot water temperature reset for a heating system. The parameters of the block heaCur are for a heating system with 60°C supply water temperature and 40°C return water temperature at an outside temperature of -10°C and a room temperature of 20°C. The offset for the temperature reset is 8 Kelvin, i.e., above 12°C outside temperature, there is no heating load. The figure below shows the computed supply and return water temperatures.

Supply and return water temperatures.

Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model SupplyReturnTemperatureReset "Test model for the heating curve" extends Modelica.Icons.Example; Buildings.Controls.SetPoints.SupplyReturnTemperatureReset heaCur( m=1, TSup_nominal=333.15, TRet_nominal=313.15, TOut_nominal=263.15) "Temperature reset"; Modelica.Blocks.Sources.Ramp TOut( height=40, duration=1, offset=263.15) "Signal for outside air temperature"; Buildings.Controls.SetPoints.SupplyReturnTemperatureReset heaCur1( m=1, use_TRoo_in=true, TSup_nominal=333.15, TRet_nominal=313.15, TOut_nominal=263.15, dTOutHeaBal=15) "Temperature reset that uses room temperature as input"; Modelica.Blocks.Sources.Step TRoo( offset=273.15 + 20, startTime=0.5, height=-5) "Night set back from 20 to 15 deg C"; Modelica.Blocks.Sources.Constant TOut2(k=273.15 - 10) "Constant signal for outdoor air temperature"; equation connect(TOut.y, heaCur.TOut); connect(TOut2.y, heaCur1.TOut); connect(TRoo.y, heaCur1.TRoo_in); end SupplyReturnTemperatureReset;

Buildings.Controls.SetPoints.Examples.Table Buildings.Controls.SetPoints.Examples.Table

Test model for table that determines set points

Buildings.Controls.SetPoints.Examples.Table

Information

Example that demonstrates the use of the block Buildings.Controls.SetPoints.Table.

Extends from Modelica.Icons.Example (Icon for runnable examples).

Modelica definition

model Table "Test model for table that determines set points" extends Modelica.Icons.Example; Buildings.Controls.SetPoints.Table tabConExt(table=[20,0; 22,0.5; 25,0.5; 26,1]); Modelica.Blocks.Sources.Ramp TRoo( duration=1, offset=15, height=15); Buildings.Controls.SetPoints.Table tabLinExt(constantExtrapolation=false, table=[ 20,0; 22,0.5; 25,0.5; 26,1]); equation connect(TRoo.y, tabLinExt.u); connect(TRoo.y, tabConExt.u); end Table;