Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves

Package with sevral performance curves

Information

This package contains performance curves for the cooling capacity and the EIR of air-cooled DX cooling coils that are used in the examples.

For performance data of specific air-cooled DX cooling coils, see the packages Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.SingleSpeed and Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.DoubleSpeed.

The data are described in Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.Generic.DXCoil.

Package Content

Name Description
Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves.Curve_I Curve_I Performance curve I
Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves.Curve_II Curve_II Performance curve II
Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves.Curve_III Curve_III Performance curve III

Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves.Curve_I Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves.Curve_I

Performance curve I

Information

This record declares performance curves for the cooling capacity and the EIR. It has been obtained from the EnergyPlus 7.1 example file AirflowNetwork_MultiZone_House.idf.

Extends from Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).

Parameters

TypeNameDefaultDescription
Performance curves
RealcapFunT[6]{0.942587793,0.009543347,0.0...Biquadratic coefficients for cooling capacity function of temperature
RealcapFunFF[:]{0.8,0.2,0,0}Polynomial coefficients for cooling capacity function of flow fration
RealEIRFunT[6]{0.342414409,0.034885008,-0....Biquadratic coefficients for EIR function of temperature
RealEIRFunFF[:]{1.1552,-0.1808,0.0256,0}Polynomial coefficients for EIR function of flow fration
Minimum and maximum values
TemperatureTConInMin291.15Minimum condenser inlet temperature for cooling capacity function [K]
TemperatureTConInMax319.26111Maximum condenser inlet temperature for cooling capacity function [K]
TemperatureTEvaInMin285.92778Minimum evaporator inlet temperature for cooling capacity function [K]
TemperatureTEvaInMax297.03889Maximum evaporator inlet temperature for cooling capacity function [K]
RealffMin0.6Minimum flow fraction for which performance data are valid
RealffMax1.8Maximum flow fraction for which performance data are valid

Modelica definition

record Curve_I "Performance curve I" extends Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.Generic.BaseClasses.PerformanceCurve ( capFunT={0.942587793,0.009543347,0.000683770,-0.011042676,0.000005249, -0.000009720}, capFunFF={0.8,0.2,0,0}, EIRFunT={0.342414409,0.034885008,-0.000623700,0.004977216,0.000437951, -0.000728028}, EIRFunFF={1.1552,-0.1808,0.0256,0}, TConInMin=291.15, TConInMax=319.26111, TEvaInMin=285.92778, TEvaInMax=297.03889, ffMin=0.6, ffMax=1.8); end Curve_I;

Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves.Curve_II Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves.Curve_II

Performance curve II

Information

This record declares performance curves for the cooling capacity and the EIR. It has been obtained from the EnergyPlus 7.1 example file DXCoilSystemAuto.idf.

Extends from Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).

Parameters

TypeNameDefaultDescription
Performance curves
RealcapFunT[6]{0.766956,0.0107756,-0.00004...Biquadratic coefficients for cooling capacity function of temperature
RealcapFunFF[:]{0.8,0.2,0,0}Polynomial coefficients for cooling capacity function of flow fration
RealEIRFunT[6]{0.297145,0.0430933,-0.00074...Biquadratic coefficients for EIR function of temperature
RealEIRFunFF[:]{1.1552,-0.1808,0.0256,0}Polynomial coefficients for EIR function of flow fration
Minimum and maximum values
TemperatureTConInMin291.15Minimum condenser inlet temperature for cooling capacity function [K]
TemperatureTConInMax319.26111Maximum condenser inlet temperature for cooling capacity function [K]
TemperatureTEvaInMin285.92778Minimum evaporator inlet temperature for cooling capacity function [K]
TemperatureTEvaInMax297.03889Maximum evaporator inlet temperature for cooling capacity function [K]
RealffMin0.5Minimum flow fraction for which performance data are valid
RealffMax1.5Maximum flow fraction for which performance data are valid

Modelica definition

record Curve_II "Performance curve II" extends Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.Generic.BaseClasses.PerformanceCurve ( capFunT={0.766956,0.0107756,-0.0000414703,0.00134961,-0.000261144, 0.000457488}, capFunFF={0.8,0.2,0,0}, EIRFunT={0.297145,0.0430933,-0.000748766,0.00597727,0.000482112,-0.000956448}, EIRFunFF={1.1552,-0.1808,0.0256,0}, TConInMin=291.15, TConInMax=319.26111, TEvaInMin=285.92778, TEvaInMax=297.03889, ffMin=0.5, ffMax=1.5); end Curve_II;

Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves.Curve_III Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Examples.PerformanceCurves.Curve_III

Performance curve III

Information

This record declares performance curves for the cooling capacity and the EIR. It has been obtained from the EnergyPlus 7.1 example file 5ZoneAutoDXVAV.idf.

Extends from Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.Generic.BaseClasses.PerformanceCurve (Data record for a performance curve).

Parameters

TypeNameDefaultDescription
Performance curves
RealcapFunT[6]{0.476428,0.0401147000,0.000...Biquadratic coefficients for cooling capacity function of temperature
RealcapFunFF[:]{0.47278589,1.2433415,-1.038...Polynomial coefficients for cooling capacity function of flow fration
RealEIRFunT[6]{0.632475,-0.0121321000,0.00...Biquadratic coefficients for EIR function of temperature
RealEIRFunFF[:]{1.0079484,0.34544129,-0.692...Polynomial coefficients for EIR function of flow fration
Minimum and maximum values
TemperatureTConInMin297.03889Minimum condenser inlet temperature for cooling capacity function [K]
TemperatureTConInMax319.26111Maximum condenser inlet temperature for cooling capacity function [K]
TemperatureTEvaInMin285.92778Minimum evaporator inlet temperature for cooling capacity function [K]
TemperatureTEvaInMax297.03889Maximum evaporator inlet temperature for cooling capacity function [K]
RealffMin0.5Minimum flow fraction for which performance data are valid
RealffMax1.5Maximum flow fraction for which performance data are valid

Modelica definition

record Curve_III "Performance curve III" extends Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.Data.Generic.BaseClasses.PerformanceCurve ( capFunT={0.476428,0.0401147000,0.0002264110,-0.0008271360,-0.0000073224, -0.0004462780}, capFunFF={0.47278589,1.2433415,-1.0387055,0.32257813}, EIRFunT={0.632475,-0.0121321000,0.0005077730,0.0155377000,0.0002728400, -0.0006792010}, EIRFunFF={1.0079484,0.34544129,-0.6922891,0.33889943}, TConInMin=297.03889, TConInMax=319.26111, TEvaInMin=285.92778, TEvaInMax=297.03889, ffMin=0.5, ffMax=1.5); end Curve_III;