Buildings.Fluid.HeatExchangers.DXCoils.AirCooled
Air-cooled DX package unit
Information
This package contains air-cooled DX coil models, including single-speed, multi-stage, and variable-speed DX coil models.Extends from Modelica.Icons.VariantsPackage (Icon for package containing variants).
Package Content
| Name | Description | 
|---|---|
|  MultiStage | Multi-stage DX cooling coil | 
|  SingleSpeed | Single speed DX cooling coil | 
|  VariableSpeed | Variable speed DX cooling coil | 
|  Data | Package with performance data for DX cooling coil | 
|  Examples | Package with example of DX cooling coil models | 
|  Validation | Collection of validation models | 
 Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.MultiStage
Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.MultiStage
Multi-stage DX cooling coil
 
Information
This model can be used to simulate an air-cooled DX cooling coil with multiple operating stages. Depending on the used performance curves, each stage could be a different compressor speed, or a different mode of operation, such as with or without hot gas reheat.
See Buildings.Fluid.HeatExchangers.DXCoils.UsersGuide for an explanation of the model.
Extends from Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.PartialDXCoil (Partial model for DX coil).
Parameters
| Type | Name | Default | Description | 
|---|---|---|---|
| replaceable package Medium | PartialCondensingGases | Medium in the component | |
| Boolean | use_mCon_flow | false | Set to true to enable connector for the condenser mass flow rate | 
| String | substanceName | "water" | Name of species substance | 
| Nominal condition | |||
| PressureDifference | dp_nominal | Pressure difference [Pa] | |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal | 
| Advanced | |||
| MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] | 
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at port is computed | 
| Flow resistance | |||
| Boolean | from_dp | false | = true, use m_flow = f(dp) else dp = f(m_flow) | 
| Boolean | linearizeFlowResistance | false | = true, use linear relation between m_flow and dp for any flow rate | 
| Real | deltaM | 0.1 | Fraction of nominal flow rate where flow transitions to laminar | 
| Dynamics | |||
| Nominal condition | |||
| Time | tau | 30 | Time constant at nominal flow (if energyDynamics <> SteadyState) [s] | 
| Equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state | 
| Dynamics | massDynamics | energyDynamics | Type of mass balance: dynamic (3 initialization options) or steady state | 
| Moisture balance | |||
| Boolean | computeReevaporation | true | Set to true to compute reevaporation of water that accumulated on coil | 
| Initialization | |||
| AbsolutePressure | p_start | Medium.p_default | Start value of pressure [Pa] | 
| Temperature | T_start | Medium.T_default | Start value of temperature [K] | 
| MassFraction | X_start[Medium.nX] | Medium.X_default | Start value of mass fractions m_i/m [kg/kg] | 
| ExtraProperty | C_start[Medium.nC] | fill(0, Medium.nC) | Start value of trace substances | 
Connectors
| Type | Name | Description | 
|---|---|---|
| FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) | 
| FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) | 
| input RealInput | TConIn | Outside air dry bulb temperature for an air cooled condenser or wetbulb temperature for an evaporative cooled condenser [K] | 
| input RealInput | mCon_flow | Water mass flow rate for condenser [kg/s] | 
| output RealOutput | P | Electrical power consumed by the unit [W] | 
| output RealOutput | QSen_flow | Sensible heat flow rate [W] | 
| output RealOutput | QLat_flow | Latent heat flow rate [W] | 
| input IntegerInput | stage | Stage of cooling coil (0: off, 1: first stage, 2: second stage...) | 
Modelica definition
 Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.SingleSpeed
Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.SingleSpeed
Single speed DX cooling coil
 
Information
This model can be used to simulate an air-cooled DX cooling coil with single speed compressor.
See Buildings.Fluid.HeatExchangers.DXCoils.UsersGuide for an explanation of the model.
Extends from Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.PartialDXCoil (Partial model for DX coil).
Parameters
| Type | Name | Default | Description | 
|---|---|---|---|
| replaceable package Medium | PartialCondensingGases | Medium in the component | |
| Boolean | use_mCon_flow | false | Set to true to enable connector for the condenser mass flow rate | 
| String | substanceName | "water" | Name of species substance | 
| Nominal condition | |||
| PressureDifference | dp_nominal | Pressure difference [Pa] | |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal | 
| Advanced | |||
| MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] | 
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at port is computed | 
| Flow resistance | |||
| Boolean | from_dp | false | = true, use m_flow = f(dp) else dp = f(m_flow) | 
| Boolean | linearizeFlowResistance | false | = true, use linear relation between m_flow and dp for any flow rate | 
| Real | deltaM | 0.1 | Fraction of nominal flow rate where flow transitions to laminar | 
| Dynamics | |||
| Nominal condition | |||
| Time | tau | 30 | Time constant at nominal flow (if energyDynamics <> SteadyState) [s] | 
| Equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state | 
| Dynamics | massDynamics | energyDynamics | Type of mass balance: dynamic (3 initialization options) or steady state | 
| Moisture balance | |||
| Boolean | computeReevaporation | true | Set to true to compute reevaporation of water that accumulated on coil | 
| Initialization | |||
| AbsolutePressure | p_start | Medium.p_default | Start value of pressure [Pa] | 
| Temperature | T_start | Medium.T_default | Start value of temperature [K] | 
| MassFraction | X_start[Medium.nX] | Medium.X_default | Start value of mass fractions m_i/m [kg/kg] | 
| ExtraProperty | C_start[Medium.nC] | fill(0, Medium.nC) | Start value of trace substances | 
Connectors
| Type | Name | Description | 
|---|---|---|
| FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) | 
| FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) | 
| input RealInput | TConIn | Outside air dry bulb temperature for an air cooled condenser or wetbulb temperature for an evaporative cooled condenser [K] | 
| input RealInput | mCon_flow | Water mass flow rate for condenser [kg/s] | 
| output RealOutput | P | Electrical power consumed by the unit [W] | 
| output RealOutput | QSen_flow | Sensible heat flow rate [W] | 
| output RealOutput | QLat_flow | Latent heat flow rate [W] | 
| input BooleanInput | on | Set to true to enable compressor, or false to disable compressor | 
Modelica definition
 Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.VariableSpeed
Buildings.Fluid.HeatExchangers.DXCoils.AirCooled.VariableSpeed
Variable speed DX cooling coil
 
Information
This model can be used to simulate an air-cooled DX cooling coil with continuously variable speed compressors. The control input is the speed ratio. The coil will switch off if the speed ratio is below a minimum value.
See Buildings.Fluid.HeatExchangers.DXCoils.UsersGuide for an explanation of the model.
Extends from Buildings.Fluid.HeatExchangers.DXCoils.BaseClasses.PartialDXCoil (Partial model for DX coil).
Parameters
| Type | Name | Default | Description | 
|---|---|---|---|
| replaceable package Medium | PartialCondensingGases | Medium in the component | |
| Boolean | use_mCon_flow | false | Set to true to enable connector for the condenser mass flow rate | 
| String | substanceName | "water" | Name of species substance | 
| Real | minSpeRat | Minimum speed ratio | |
| Real | speRatDeaBan | 0.05 | Deadband for minimum speed ratio | 
| Nominal condition | |||
| PressureDifference | dp_nominal | Pressure difference [Pa] | |
| Assumptions | |||
| Boolean | allowFlowReversal | true | = false to simplify equations, assuming, but not enforcing, no flow reversal | 
| Advanced | |||
| MassFlowRate | m_flow_small | 1E-4*abs(m_flow_nominal) | Small mass flow rate for regularization of zero flow [kg/s] | 
| Diagnostics | |||
| Boolean | show_T | false | = true, if actual temperature at port is computed | 
| Flow resistance | |||
| Boolean | from_dp | false | = true, use m_flow = f(dp) else dp = f(m_flow) | 
| Boolean | linearizeFlowResistance | false | = true, use linear relation between m_flow and dp for any flow rate | 
| Real | deltaM | 0.1 | Fraction of nominal flow rate where flow transitions to laminar | 
| Dynamics | |||
| Nominal condition | |||
| Time | tau | 30 | Time constant at nominal flow (if energyDynamics <> SteadyState) [s] | 
| Equations | |||
| Dynamics | energyDynamics | Modelica.Fluid.Types.Dynamic... | Type of energy balance: dynamic (3 initialization options) or steady state | 
| Dynamics | massDynamics | energyDynamics | Type of mass balance: dynamic (3 initialization options) or steady state | 
| Moisture balance | |||
| Boolean | computeReevaporation | true | Set to true to compute reevaporation of water that accumulated on coil | 
| Initialization | |||
| AbsolutePressure | p_start | Medium.p_default | Start value of pressure [Pa] | 
| Temperature | T_start | Medium.T_default | Start value of temperature [K] | 
| MassFraction | X_start[Medium.nX] | Medium.X_default | Start value of mass fractions m_i/m [kg/kg] | 
| ExtraProperty | C_start[Medium.nC] | fill(0, Medium.nC) | Start value of trace substances | 
Connectors
| Type | Name | Description | 
|---|---|---|
| FluidPort_a | port_a | Fluid connector a (positive design flow direction is from port_a to port_b) | 
| FluidPort_b | port_b | Fluid connector b (positive design flow direction is from port_a to port_b) | 
| input RealInput | TConIn | Outside air dry bulb temperature for an air cooled condenser or wetbulb temperature for an evaporative cooled condenser [K] | 
| input RealInput | mCon_flow | Water mass flow rate for condenser [kg/s] | 
| output RealOutput | P | Electrical power consumed by the unit [W] | 
| output RealOutput | QSen_flow | Sensible heat flow rate [W] | 
| output RealOutput | QLat_flow | Latent heat flow rate [W] | 
| input RealInput | speRat | Speed ratio | 