Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data
Experimental data for verification of pipe models
Information
Subpackage that contains measurement data from various experiments at ULg and AIT. This data is used to validate BaseClasses.PipeCore.
References
van der Heijde, B., Fuchs, M., Ribas Tugores, C., Schweiger, G., Sartor, K., Basciotti, D., Müller, D., Nytsch-Geusen, C., Wetter, M. and Helsen, L. (2017). Dynamic equation-based thermo-hydraulic pipe model for district heating and cooling systems. Energy Conversion and Management, 151 (November), 158-169. https://doi.org/10.1016/j.enconman.2017.08.072
Package Content
Name | Description |
---|---|
TestData | Example to check pipe data records |
PipeDataAIT151218 | Experimental data from AIT monitoring data December 18, 2015 |
PipeDataULg150801 | Experimental data from ULg's pipe test bench from August 1 |
PipeDataULg151202 | Experimental data from ULg's pipe test bench from December 2, 2015 |
PipeDataULg151204_1 | Experimental data from ULg's pipe test bench from December 4, 2015 (1); increase followed by a decrease in temperature |
PipeDataULg151204_2 | Experimental data from ULg's pipe test bench from December 4, 2015 (2) |
PipeDataULg151204_4 | Experimental data from ULg's pipe test bench from December 4, 2015 (4); an increase followed by a decrease temperature |
PipeDataULg160104_2 | Experimental data from ULg's pipe test bench from 4 January 2016. Low mass flow |
PipeDataULg160118_1 | Experimental data from ULg's pipe test bench from January 18, 2016 |
BaseClasses | BaseClasses for data records |
Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.TestData
Example to check pipe data records
Information
Model used to visualize and check data of district heating networks
Extends from Modelica.Icons.Example (Icon for runnable examples).
Parameters
Type | Name | Default | Description |
---|---|---|---|
PipeDataAIT151218 | pipeDataToBeRead | redeclare PipeDataAIT151218 ... | Measurement dataset from AIT |
Modelica definition
Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.PipeDataAIT151218
Experimental data from AIT monitoring data December 18, 2015
Information
Overview
This record contains data of a real disitrict heating network for week-long period (23-29 Januar 2009) monitored by the Austrian Institut for Technology.
Pipes are layed underground
Data structure
Column 1: Time in s
Column 2: Temperature in point 1 in K
Column 3: Temperature in point 2 in K
Column 4: Temperature in point 3 in K
Column 5: Temperature in point 4 in K
Column 6: Mass flow rate in point 1 in kg/s
Column 7: Mass flow rate in point 2 in kg/s
Column 8: Mass flow rate in point 3 in kg/s
Column 9: Mass flow rate in point 4 in kg/s
Column 10: Outdoor temperature in K
Test procedure
Information at several points of the district heating network is recorded during a week.Test bench schematic
Notice that length are approximated
Pipe characteristics
- Inner diameter: 0.0825 m (DN080)
- Outer diameter: 0.0889 m (stell wall thickness 3.2 mm)
- Casing diameter: 0.18 m
- Insulation material: Polyurethane
- Heat conductivity of insulation material: 0.024 W/(m K) (average value at 50 °C)
- Length specific pipe's heat loss coefficient: 0.208 W/(m K)
- Wall roughness coefficient: 0.1 mm
Extends from BaseClasses.PipeDataBaseDefinition (BaseClass for experimental data from the pipe test bench).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Integer | nCol | 10 | Number of columns in the data file |
String | filNam | Modelica.Utilities.Files.loa... | Name of data file |
Modelica definition
Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.PipeDataULg150801
Experimental data from ULg's pipe test bench from August 1
Information
This data record contains the experimental data from the long test bench carried out at the University of Liège. See Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg for more information.
Extends from Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg (Base class for ULg experimental data).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Integer | nCol | 6 | Number of columns in the data file |
String | filNam | Modelica.Utilities.Files.loa... | Name of data file |
Temp_C | T_start_in | 16.6 | Initial temperature at inlet [degC] |
Temp_C | T_start_out | 16.8 | Initial temperature at outlet [degC] |
MassFlowRate | m_flowIni | 1.245 | Mass flow initialization [kg/s] |
Modelica definition
Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.PipeDataULg151202
Experimental data from ULg's pipe test bench from December 2, 2015
Information
This data record contains the experimental data from the long test bench carried out at the University of Liège. See Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg for more information.
Extends from Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg (Base class for ULg experimental data).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Integer | nCol | 6 | Number of columns in the data file |
String | filNam | Modelica.Utilities.Files.loa... | Name of data file |
Temp_C | T_start_in | 18.8 | Initial temperature at inlet [degC] |
Temp_C | T_start_out | 18.2 | Initial temperature at outlet [degC] |
MassFlowRate | m_flowIni | 0.589 | Mass flow initialization [kg/s] |
Modelica definition
Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.PipeDataULg151204_1
Experimental data from ULg's pipe test bench from December 4, 2015 (1); increase followed by a decrease in temperature
Information
This data record contains the experimental data from the long test bench carried out at the University of Liège. See Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg for more information.
Extends from Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg (Base class for ULg experimental data).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Integer | nCol | 6 | Number of columns in the data file |
String | filNam | Modelica.Utilities.Files.loa... | Name of data file |
Temp_C | T_start_in | 14.0 | Initial temperature at inlet [degC] |
Temp_C | T_start_out | 14.0 | Initial temperature at outlet [degC] |
MassFlowRate | m_flowIni | 1.618 | Mass flow initialization [kg/s] |
Modelica definition
Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.PipeDataULg151204_2
Experimental data from ULg's pipe test bench from December 4, 2015 (2)
Information
This data record contains the experimental data from the long test bench carried out at the University of Liège. See Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg for more information.
Extends from Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg (Base class for ULg experimental data).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Integer | nCol | 6 | Number of columns in the data file |
String | filNam | Modelica.Utilities.Files.loa... | Name of data file |
Temp_C | T_start_in | 14.7 | Initial temperature at inlet [degC] |
Temp_C | T_start_out | 14.3 | Initial temperature at outlet [degC] |
MassFlowRate | m_flowIni | 1.251 | Mass flow initialization [kg/s] |
Modelica definition
Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.PipeDataULg151204_4
Experimental data from ULg's pipe test bench from December 4, 2015 (4); an increase followed by a decrease temperature
Information
This data record contains the experimental data from the long test bench carried out at the University of Liège. See Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg for more information.
Extends from Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg (Base class for ULg experimental data).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Integer | nCol | 6 | Number of columns in the data file |
String | filNam | Modelica.Utilities.Files.loa... | Name of data file |
Temp_C | T_start_in | 31.2 | Initial temperature at inlet [degC] |
Temp_C | T_start_out | 27.7 | Initial temperature at outlet [degC] |
MassFlowRate | m_flowIni | 1.257 | Mass flow initialization [kg/s] |
Modelica definition
Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.PipeDataULg160104_2
Experimental data from ULg's pipe test bench from 4 January 2016. Low mass flow
Information
This data record contains the experimental data from the long test bench carried out at the University of Liège. See Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg for more information.
Extends from Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg (Base class for ULg experimental data).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Integer | nCol | 6 | Number of columns in the data file |
String | filNam | Modelica.Utilities.Files.loa... | Name of data file |
Temp_C | T_start_in | 17.9 | Initial temperature at inlet [degC] |
Temp_C | T_start_out | 15.0 | Initial temperature at outlet [degC] |
MassFlowRate | m_flowIni | 0.2494 | Mass flow initialization [kg/s] |
Modelica definition
Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.PipeDataULg160118_1
Experimental data from ULg's pipe test bench from January 18, 2016
Information
This data record contains the experimental data from the long test bench carried out at the University of Liège. See Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg for more information.
Extends from Buildings.Fluid.FixedResistances.Validation.PlugFlowPipes.Data.BaseClasses.PipeDataULg (Base class for ULg experimental data).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Integer | nCol | 6 | Number of columns in the data file |
String | filNam | Modelica.Utilities.Files.loa... | Name of data file |
Temp_C | T_start_in | 17.9 | Initial temperature at inlet [degC] |
Temp_C | T_start_out | 18.2 | Initial temperature at outlet [degC] |
MassFlowRate | m_flowIni | 2.269 | Mass flow initialization [kg/s] |