Buildings.Fluid.SolarCollectors.Controls.BaseClasses
Package of BaseClass models used to create the models in the Controls package
Information
This package contains base classes that are used in the Buildings.Fluid.SolarCollectors.Controls package.
Extends from Modelica.Icons.Package (Icon for standard packages).
Package Content
Name | Description |
---|---|
GCritCalc | Model calculating the critical insolation level |
Examples | Package containing examples demonstrating the use of Controls.BaseClasses models |
Buildings.Fluid.SolarCollectors.Controls.BaseClasses.GCritCalc
Model calculating the critical insolation level
Information
This component calculates the solar radiation necessary for the fluid in the collector to gain heat. It is used in the model Buildings.Fluid.SolarCollectors.Controls.SolarPumpController.
The critical solar radiation level is calculated using Equation 6.8.2 in Duffie and Beckman (2006). It is
GTC=FRUL (TIn-TEnv) /(FR(τα))
where GTC is the critical solar radiation, FRUL is the heat loss coefficient, TIn is the inlet temperature, TEnv is the ambient temperature, and FR(τα) is the maximum efficiency.
References
J.A. Duffie and W.A. Beckman 2006, Solar Engineering of Thermal Processes (3rd
Edition), John Wiley & Sons, Inc.
Extends from Modelica.Blocks.Icons.Block (Basic graphical layout of input/output block).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | slope | slope( ... | Slope from ratings data [W/(m2.K)] |
Real | y_intercept | y_intercept from ratings data |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | TIn | Temperature of water entering the collector [K] |
output RealOutput | G_TC | Critical radiation level [W/m2] |
input RealInput | TEnv | Ambient temperature at the collector [K] |