Buildings.Fluid.HeatExchangers.ActiveBeams.Data

Package with performance data

Information

Package with performance data for active beams.

Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).

Package Content

Name Description
Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Trox Trox Performance data for Trox
Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Generic Generic Generic data record for active beam
Buildings.Fluid.HeatExchangers.ActiveBeams.Data.BaseClasses BaseClasses Base classes for performance data

Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Generic Buildings.Fluid.HeatExchangers.ActiveBeams.Data.Generic

Generic data record for active beam

Information

Performance data for a generic active beam.

Extends from Modelica.Icons.Record (Icon for records).

Parameters

TypeNameDefaultDescription
AirFlowprimaryAirprimaryAir( r_V={0,0.2,1},...Performance data for primary air
WaterFlowwaterwater( r_V={0,0.5,1}, ...Performance data for water
TemperatureDifferencedTdT( r_dT={0,0.5,1}, f=...Performance data for normalized temperature difference room minus water inlet
Nominal condition
MassFlowRatemAir_flow_nominal Nominal air mass flow rate per beam [kg/s]
MassFlowRatemWat_flow_nominal Nominal water mass flow rate per beam [kg/s]
PressureDifferencedpWat_nominaldpWat_nominal( ...Water-side nominal pressure drop per beam [Pa]
PressureDifferencedpAir_nominaldpAir_nominal( ...Air-side nominal pressure drop [Pa]
TemperatureDifferencedT_nominal Nominal temperature difference water inlet minus room air [K]
HeatFlowRateQ_flow_nominal Nominal capacity per beam [W]

Modelica definition

record Generic "Generic data record for active beam" extends Modelica.Icons.Record; parameter BaseClasses.AirFlow primaryAir( r_V={0,0.2,1}, f={0,0.5,1}) "Performance data for primary air"; parameter Buildings.Fluid.HeatExchangers.ActiveBeams.Data.BaseClasses.WaterFlow water( r_V={0,0.5,1}, f={0,0.7,1}) "Performance data for water"; parameter BaseClasses.TemperatureDifference dT( r_dT={0,0.5,1}, f={0,0.5,1}) "Performance data for normalized temperature difference room minus water inlet"; parameter Modelica.SIunits.MassFlowRate mAir_flow_nominal "Nominal air mass flow rate per beam"; parameter Modelica.SIunits.MassFlowRate mWat_flow_nominal "Nominal water mass flow rate per beam"; parameter Modelica.SIunits.PressureDifference dpWat_nominal(displayUnit="Pa") "Water-side nominal pressure drop per beam"; parameter Modelica.SIunits.PressureDifference dpAir_nominal(displayUnit="Pa") "Air-side nominal pressure drop"; parameter Modelica.SIunits.TemperatureDifference dT_nominal "Nominal temperature difference water inlet minus room air"; parameter Modelica.SIunits.HeatFlowRate Q_flow_nominal "Nominal capacity per beam"; end Generic;