Buildings.Electrical.Transmission.LowVoltageCables

Package of low voltage electricity cables used in distribution grid

Information

This package contains records of physical properties for low voltage commercial cables. New cables can be added by extending the base record Buildings.Electrical.Transmission.LowVoltageCables.Generic.

For low voltage cables, only the characteristic resistance and reactance are specified. See Buildings.Electrical.Transmission.Base.BaseCable for a comprehensive list of parameters that can be specified for a cable.

Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).

Package Content

Name Description
Buildings.Electrical.Transmission.LowVoltageCables.Cu10 Cu10 Cu cable 10 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.Cu100 Cu100 Cu cable 100 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.Cu20 Cu20 Cu cable 20 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.Cu25 Cu25 Cu cable 25 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.Cu35 Cu35 Cu cable 35 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.Cu50 Cu50 Cu cable 50 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.Cu95 Cu95 Cu cable 95 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.Generic Generic Data record for a generic low voltage cable
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl120 PvcAl120 Aluminum cable 120mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl120_ECM PvcAl120_ECM Aluminum cable 120mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl150 PvcAl150 Aluminum cable 150mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl16 PvcAl16 Aluminum cable 16 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl16_ECM PvcAl16_ECM Aluminum cable 16 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl25 PvcAl25 Aluminum cable 25 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl25_ECM PvcAl25_ECM Aluminum cable 25 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl35 PvcAl35 Aluminum cable 35 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl35_ECM PvcAl35_ECM Aluminum cable 35 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl50 PvcAl50 Aluminum cable 50 mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl70 PvcAl70 Aluminum cable 70mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl70_ECM PvcAl70_ECM Aluminum cable 70mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl75 PvcAl75 Aluminum cable 75mm^2
Buildings.Electrical.Transmission.LowVoltageCables.PvcAl95 PvcAl95 Aluminum cable 95mm^2

Buildings.Electrical.Transmission.LowVoltageCables.Cu10 Buildings.Electrical.Transmission.LowVoltageCables.Cu10

Cu cable 10 mm^2

Information

Copper cable with a cross-sectional area of 10mm^2. This type of cable has the following properties

RCha = 1.810-003 // Characteristic resistance [Ohm/m]
XCha = 0.076e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.CuMaterial of the cable
CurrentAmp65Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM234.5 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha1.81e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.076e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record Cu10 "Cu cable 10 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Cu, M = 234.5 + 273.15, Amp=65, RCha=1.81e-003, XCha=0.076e-003); end Cu10;

Buildings.Electrical.Transmission.LowVoltageCables.Cu100 Buildings.Electrical.Transmission.LowVoltageCables.Cu100

Cu cable 100 mm^2

Information

Copper cable with a cross-sectional area of 100mm^2. This type of cable has the following properties

RCha = 0.181e-003 // Characteristic resistance [Ohm/m]
XCha = 0.072e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.CuMaterial of the cable
CurrentAmp230Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM234.5 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.181e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.072e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record Cu100 "Cu cable 100 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Cu, M = 234.5 + 273.15, Amp = 230, RCha=0.181e-003, XCha=0.072e-003); end Cu100;

Buildings.Electrical.Transmission.LowVoltageCables.Cu20 Buildings.Electrical.Transmission.LowVoltageCables.Cu20

Cu cable 20 mm^2

Information

Copper cable with a cross-sectional area of 20mm^2. This type of cable has the following properties

RCha = 0.905e-003 // Characteristic resistance [Ohm/m]
XCha = 0.075e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.CuMaterial of the cable
CurrentAmp95Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM234.5 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.905e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.075e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record Cu20 "Cu cable 20 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Cu, M = 234.5 + 273.15, Amp=95, RCha=0.905e-003, XCha=0.075e-003); end Cu20;

Buildings.Electrical.Transmission.LowVoltageCables.Cu25 Buildings.Electrical.Transmission.LowVoltageCables.Cu25

Cu cable 25 mm^2

Information

Copper cable with a cross-sectional area of 25mm^2. This type of cable has the following properties

RCha = 0.727e-003 // Characteristic resistance [Ohm/m]
XCha = 0.075e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.CuMaterial of the cable
CurrentAmp110Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM234.5 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.727e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.075e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record Cu25 "Cu cable 25 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Cu, M = 234.5 + 273.15, Amp=110, RCha=0.727e-003, XCha=0.075e-003); end Cu25;

Buildings.Electrical.Transmission.LowVoltageCables.Cu35 Buildings.Electrical.Transmission.LowVoltageCables.Cu35

Cu cable 35 mm^2

Information

Copper cable with a cross-sectional area of 35mm^2. This type of cable has the following properties

RCha = 0.517e-003 // Characteristic resistance [Ohm/m]
XCha = 0.074e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.CuMaterial of the cable
CurrentAmp130Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM234.5 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.517e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.074e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record Cu35 "Cu cable 35 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Cu, M = 234.5 + 273.15, Amp=130, RCha=0.517e-003, XCha=0.074e-003); end Cu35;

Buildings.Electrical.Transmission.LowVoltageCables.Cu50 Buildings.Electrical.Transmission.LowVoltageCables.Cu50

Cu cable 50 mm^2

Information

Copper cable with a cross-sectional area of 50mm^2. This type of cable has the following properties

RCha = 0.362e-003 // Characteristic resistance [Ohm/m]
XCha = 0.073e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.CuMaterial of the cable
CurrentAmp170Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM234.5 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.362e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.073e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record Cu50 "Cu cable 50 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Cu, M = 234.5 + 273.15, Amp=170, RCha=0.362e-003, XCha=0.073e-003); end Cu50;

Buildings.Electrical.Transmission.LowVoltageCables.Cu95 Buildings.Electrical.Transmission.LowVoltageCables.Cu95

Cu cable 95 mm^2

Information

Copper cable with a cross-sectional area of 95mm^2. This type of cable has the following properties

RCha = 0.191e-003 // Characteristic resistance [Ohm/m]
XCha = 0.072e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.CuMaterial of the cable
CurrentAmp220Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM234.5 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.191e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.072e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record Cu95 "Cu cable 95 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Cu, M = 234.5 + 273.15, Amp=220, RCha=0.191e-003, XCha=0.072e-003); end Cu95;

Buildings.Electrical.Transmission.LowVoltageCables.Generic Buildings.Electrical.Transmission.LowVoltageCables.Generic

Data record for a generic low voltage cable

Information

This is a base record for specifying physical properties for low voltage commercial cables. New cables can be added by extending the it.

For low voltage cables, only the characteristic resistance and reactance are specified.

Extends from Modelica.Icons.MaterialProperty (Icon for property classes), Buildings.Electrical.Transmission.BaseClasses.BaseCable (Record that contains the properties of a generic cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialBuildings.Electrical.Transmi...Material of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRChaRCha( ...Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXChaXCha( ...Characteristic reactance of the cable [Ohm/m]

Modelica definition

record Generic "Data record for a generic low voltage cable" extends Modelica.Icons.MaterialProperty; extends Buildings.Electrical.Transmission.BaseClasses.BaseCable; parameter Buildings.Electrical.Types.CharacteristicResistance RCha(start=0) "Characteristic resistance of the cable"; parameter Buildings.Electrical.Types.CharacteristicReactance XCha(start=0) "Characteristic reactance of the cable"; redeclare function extends lineResistance "Function that computes the resistance of a cable" input Buildings.Electrical.Transmission.LowVoltageCables.Generic cable "Record that contains cable properties"; algorithm R :=cable.RCha*l; end lineResistance; redeclare function extends lineInductance "Function that computes the resistance of a cable" input Buildings.Electrical.Transmission.LowVoltageCables.Generic cable "Record that contains cable properties"; algorithm L := l*(cable.XCha/omega); end lineInductance; redeclare function extends lineCapacitance "Function that computes the capacitance of a cable" input Buildings.Electrical.Transmission.LowVoltageCables.Generic cable "Record that contains cable properties"; algorithm C := 0.0; end lineCapacitance; end Generic;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl120 Buildings.Electrical.Transmission.LowVoltageCables.PvcAl120

Aluminum cable 120mm^2

Information

Aluminium cable with a cross-sectional area of 120mm^2. This type of cable has the following properties

RCha = 0.269e-003 // Characteristic resistance [Ohm/m]
XCha = 0.071e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.269e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.071e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl120 "Aluminum cable 120mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=0.269e-003, XCha=0.071e-003); end PvcAl120;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl120_ECM Buildings.Electrical.Transmission.LowVoltageCables.PvcAl120_ECM

Aluminum cable 120mm^2

Information

Aluminium cable with a cross-sectional area of 120mm^2, ECM type. This type of cable has the following properties

RCha = 0.278e-003 // Characteristic resistance [Ohm/m]
XCha = 0.071e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.278e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.071e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl120_ECM "Aluminum cable 120mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=0.278e-003, XCha=0.071e-003); end PvcAl120_ECM;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl150 Buildings.Electrical.Transmission.LowVoltageCables.PvcAl150

Aluminum cable 150mm^2

Information

Aluminium cable with a cross-sectional area of 150mm^2. This type of cable has the following properties

RCha = 0.206e-003 // Characteristic resistance [Ohm/m]
XCha = 0.070e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.206e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.070e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl150 "Aluminum cable 150mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=0.206e-003, XCha=0.070e-003); end PvcAl150;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl16 Buildings.Electrical.Transmission.LowVoltageCables.PvcAl16

Aluminum cable 16 mm^2

Information

Aluminium cable with a cross-sectional area of 16mm^2, ECM type. This type of cable has the following properties

RCha = 2.105e-003 // Characteristic resistance [Ohm/m]
XCha = 0.076e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha2.105e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.076e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl16 "Aluminum cable 16 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=2.105e-003, XCha=0.076e-003); end PvcAl16;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl16_ECM Buildings.Electrical.Transmission.LowVoltageCables.PvcAl16_ECM

Aluminum cable 16 mm^2

Information

Aluminium cable with a cross-sectional area of 16mm^2, ECM type. This type of cable has the following properties

RCha = 2.105e-003 // Characteristic resistance [Ohm/m]
XCha = 0.076e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha2.105e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.076e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl16_ECM "Aluminum cable 16 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=2.105e-003, XCha=0.076e-003); end PvcAl16_ECM;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl25 Buildings.Electrical.Transmission.LowVoltageCables.PvcAl25

Aluminum cable 25 mm^2

Information

Aluminium cable with a cross-sectional area of 25mm^2, ECM type. This type of cable has the following properties

RCha = 1.292e-003 // Characteristic resistance [Ohm/m]
XCha = 0.075e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha1.292e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.075e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl25 "Aluminum cable 25 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=1.292e-003, XCha=0.075e-003); end PvcAl25;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl25_ECM Buildings.Electrical.Transmission.LowVoltageCables.PvcAl25_ECM

Aluminum cable 25 mm^2

Information

Aluminium cable with a cross-sectional area of 25mm^2, ECM type. This type of cable has the following properties

RCha = 1.320e-003 // Characteristic resistance [Ohm/m]
XCha = 0.075e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha1.32e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.075e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl25_ECM "Aluminum cable 25 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=1.32e-003, XCha=0.075e-003); end PvcAl25_ECM;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl35 Buildings.Electrical.Transmission.LowVoltageCables.PvcAl35

Aluminum cable 35 mm^2

Information

Aluminium cable with a cross-sectional area of 35mm^2, ECM type. This type of cable has the following properties

RCha = 0.923e-003 // Characteristic resistance [Ohm/m]
XCha = 0.074e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.923e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.074e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl35 "Aluminum cable 35 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=0.923e-003, XCha=0.074e-003); end PvcAl35;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl35_ECM Buildings.Electrical.Transmission.LowVoltageCables.PvcAl35_ECM

Aluminum cable 35 mm^2

Information

Aluminium cable with a cross-sectional area of 35mm^2, ECM type. This type of cable has the following properties

RCha = 0.956e-003 // Characteristic resistance [Ohm/m]
XCha = 0.074e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.956e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.074e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl35_ECM "Aluminum cable 35 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=0.956e-003, XCha=0.074e-003); end PvcAl35_ECM;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl50 Buildings.Electrical.Transmission.LowVoltageCables.PvcAl50

Aluminum cable 50 mm^2

Information

Aluminium cable with a cross-sectional area of 50mm^2. This type of cable has the following properties

RCha = 0.641e-003 // Characteristic resistance [Ohm/m]
XCha = 0.073e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.641e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.073e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl50 "Aluminum cable 50 mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=0.641e-003, XCha=0.073e-003); end PvcAl50;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl70 Buildings.Electrical.Transmission.LowVoltageCables.PvcAl70

Aluminum cable 70mm^2

Information

Aluminium cable with a cross-sectional area of 70mm^2. This type of cable has the following properties

RCha = 0.5071e-003 // Characteristic resistance [Ohm/m]
XCha = 0.072e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.5071e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.072e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl70 "Aluminum cable 70mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=0.5071e-003, XCha=0.072e-003); end PvcAl70;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl70_ECM Buildings.Electrical.Transmission.LowVoltageCables.PvcAl70_ECM

Aluminum cable 70mm^2

Information

Aluminium cable with a cross-sectional area of 70mm^2, ECM type. This type of cable has the following properties

RCha = 0.488e-003 // Characteristic resistance [Ohm/m]
XCha = 0.072e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.488e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.072e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl70_ECM "Aluminum cable 70mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=0.488e-003, XCha=0.072e-003); end PvcAl70_ECM;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl75 Buildings.Electrical.Transmission.LowVoltageCables.PvcAl75

Aluminum cable 75mm^2

Information

Aluminium cable with a cross-sectional area of 75mm^2. This type of cable has the following properties

RCha = 0.431e-003 // Characteristic resistance [Ohm/m]
XCha = 0.072e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.431e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.072e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl75 "Aluminum cable 75mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=0.431e-003, XCha=0.072e-003); end PvcAl75;

Buildings.Electrical.Transmission.LowVoltageCables.PvcAl95 Buildings.Electrical.Transmission.LowVoltageCables.PvcAl95

Aluminum cable 95mm^2

Information

Aluminium cable with a cross-sectional area of 95mm^2. This type of cable has the following properties

RCha = 0.320e-003 // Characteristic resistance [Ohm/m]
XCha = 0.072e-003 // Characteristic reactance [Ohm/m]

Extends from Buildings.Electrical.Transmission.LowVoltageCables.Generic (Data record for a generic low voltage cable).

Parameters

TypeNameDefaultDescription
MaterialmaterialTypes.Material.AlMaterial of the cable
CurrentAmp0.0Ampacitance of the cable [A]
TemperatureT_ref298.15Reference cable temperature [K]
TemperatureM228.1 + 273.15Temperature constant of the material [K]
replaceable function lineResistancelineResistanceFunction that computes the resistance of a cable
replaceable function lineInductancelineInductanceFunction that computes the inductance of a cable
replaceable function lineCapacitancelineCapacitanceFunction that computes the capacitance of a cable
CharacteristicResistanceRCha0.320e-003Characteristic resistance of the cable [Ohm/m]
CharacteristicReactanceXCha0.072e-003Characteristic reactance of the cable [Ohm/m]

Modelica definition

record PvcAl95 "Aluminum cable 95mm^2" extends Buildings.Electrical.Transmission.LowVoltageCables.Generic( material=Types.Material.Al, M = 228.1 + 273.15, RCha=0.320e-003, XCha=0.072e-003); end PvcAl95;