Buildings.Controls.OBC.CDL.Continuous
Package with blocks for continuous variables
Information
Package with blocks for elementary mathematical functions for continuous variables.
Package Content
Name | Description |
---|---|
Abs | Output the absolute value of the input |
Add | Output the sum of the two inputs |
AddParameter | Output the sum of an input plus a parameter |
Atan | Output the arc tangent of the input |
Atan2 | Output atan(u1/u2) of the inputs u1 and u2 |
Average | Output the average of its two inputs |
ChangeSign | Change sign of the input |
Cos | Output the cosine of the input |
Derivative | Block that approximates the derivative of the input |
Division | Output first input divided by second input |
Exp | Output the exponential (base e) of the input |
Feedback | Output difference between commanded and feedback input |
Gain | Output the product of a gain value with the input signal |
Greater | Output y is true, if input u1 is greater than input u2 |
GreaterEqual | Output y is true, if input u1 is greater or equal than input u2 |
GreaterEqualThreshold | Output y is true, if input u is greater or equal than threshold |
GreaterThreshold | Output y is true, if input u is greater than threshold |
Hysteresis | Transform Real to Boolean signal with Hysteresis |
HysteresisWithHold | Hysteresis block that optionally allows to specify a hold time |
IntegratorWithReset | Output the integral of the input signal |
Less | Output y is true, if input u1 is less than input u2 |
LessEqual | Output y is true, if input u1 is less or equal than input u2 |
LessEqualThreshold | Output y is true, if input u is less or equal than threshold |
LessThreshold | Output y is true, if input u is less than threshold |
LimPID | P, PI, PD, and PID controller with limited output, anti-windup compensation and setpoint weighting |
Limiter | Limit the range of a signal |
Line | Output the value of the input x along a line specified by two points |
Log | Output the natural (base e) logarithm of the input (input > 0 required) |
Log10 | Output the base 10 logarithm of the input (input > 0 required) |
MatrixGain | Output the product of a gain matrix with the input signal vector |
MatrixMax | Output vector of row- or column-wise maximum of the input matrix |
MatrixMin | Output vector of row- or column-wise minimum values |
Max | Pass through the largest signal |
Min | Pass through the smallest signal |
Modulo | Output the remainder of first input divided by second input (~=0) |
MovingMean | Block to output moving average |
MultiMax | Output the maximum element of the input vector |
MultiMin | Output the minimum element of the input vector |
MultiSum | Sum of Reals, y = k[1]*u[1] + k[2]*u[2] + ... + k[n]*u[n] |
NumberOfRequests | Outputs the number of signals that are above/below a certain threshold |
Product | Output product of the two inputs |
Round | Round real number to given digits |
Sin | Output the sine of the input |
SlewRateLimiter | Limit the increase or decrease rate of input |
Sort | Sort elements of input vector in ascending or descending order |
Sqrt | Output the square root of the input (input >= 0 required) |
Tan | Output the tangent of the input |
Sources | Package with blocks that generate source signals |
Validation | Collection of models that validate the continuous blocks of the CDL |
Buildings.Controls.OBC.CDL.Continuous.Abs
Output the absolute value of the input
Information
Block that outputs y = abs(u)
,
where
u
is an input.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Add
Output the sum of the two inputs
Information
Block that outputs y
as the weighted sum of the
two input signals u1
and u2
,
y = k1*u1 + k2*u2;
where k1
and k2
are parameters.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | k1 | +1 | Gain for input u1 |
Real | k2 | +1 | Gain for input u2 |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of Real input signal 1 |
input RealInput | u2 | Connector of Real input signal 2 |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.AddParameter
Output the sum of an input plus a parameter
Information
Block that outputs y = k u + p
,
where k
and p
are
parameters and u
is an input.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | p | Value to be added | |
Real | k | Gain of input |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Atan
Output the arc tangent of the input
Information
Block that outputs y = atan(u)
,
where
u
is an input.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Atan2
Output atan(u1/u2) of the inputs u1 and u2
Information
Block that outputs the tangent-inverse y = atan2(u1, u2)
of the input u1
divided by the input u2
.
u1
and u2
shall not be zero at the same time instant.
Atan2
uses the sign of u1
and u2
in order to construct the solution in the range
-π ≤ y ≤ π, whereas
Buildings.Controls.OBC.CDL.Continuous.Atan
gives a solution in the range
-π/2 ≤ y ≤ π/2.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of Real input signal 1 |
input RealInput | u2 | Connector of Real input signal 2 |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Average
Output the average of its two inputs
Information
Block that outputs y = avg(u1,u2)
,
where
u1
and u2
are inputs.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of Real input signal 1 |
input RealInput | u2 | Connector of Real input signal 2 |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.ChangeSign
Change sign of the input
Information
Block that outputs y = -u
,
where u
is an input.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Cos
Output the cosine of the input
Information
Block that outputs y = cos(u)
,
where
u
is an input.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Derivative
Block that approximates the derivative of the input
Information
This blocks defines the transfer function between the
input u
and the output y
(element-wise) as approximated derivative:
k * s y = ------------ * u T * s + 1
If k=0
, the block reduces to y=0
.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | k | 1 | Gains [1] |
Time | T | 0.01 | Time constant (T>0 required) [s] |
Initialization | |||
Init | initType | Buildings.Controls.OBC.CDL.T... | Type of initialization (1: no init, 2: initial state, 3: initial output) |
Real | x_start | 0 | Initial or guess value of state |
Real | y_start | 0 | Initial value of output (= state) |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Division
Output first input divided by second input
Information
Block that outputs y = u1 / u2
,
where
u1
and u2
are inputs.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of Real input signal 1 |
input RealInput | u2 | Connector of Real input signal 2 |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Exp
Output the exponential (base e) of the input
Information
Block that outputs y = exp(u)
,
where
u
is an input and exp()
is the
base-e exponential function.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Feedback
Output difference between commanded and feedback input
Information
Block that outputs y = u1 - u2
,
where
u1
and u2
are inputs.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of Real input signal 1 |
input RealInput | u2 | Connector of Real input signal 2 |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Gain
Output the product of a gain value with the input signal
Information
Block that outputs y = k * u
,
where
k
is a parameter and
u
is an input.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | k | Gain value multiplied with input signal |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Input signal connector |
output RealOutput | y | Output signal connector |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Greater
Output y is true, if input u1 is greater than input u2
Information
Block that outputs true
if the Real input u1
is greater than the Real input u2
.
Otherwise the output is false
.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of first Real input signal |
input RealInput | u2 | Connector of second Real input signal |
output BooleanOutput | y | Connector of Boolean output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.GreaterEqual
Output y is true, if input u1 is greater or equal than input u2
Information
Block that outputs true
if Real the input u1
is greater than or equal to the Real input u2
.
Otherwise the output is false
.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of first Real input signal |
input RealInput | u2 | Connector of second Real input signal |
output BooleanOutput | y | Connector of Boolean output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.GreaterEqualThreshold
Output y is true, if input u is greater or equal than threshold
Information
Block that outputs true
if the Real input is greater than or equal to
the parameter threshold
.
Otherwise the output is false
.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | threshold | 0 | Comparison with respect to threshold |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output BooleanOutput | y | Connector of Boolean output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.GreaterThreshold
Output y is true, if input u is greater than threshold
Information
Block that outputs true
if the Real input is greater than
the parameter threshold
.
Otherwise the output is false
.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | threshold | 0 | Comparison with respect to threshold |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output BooleanOutput | y | Connector of Boolean output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Hysteresis
Transform Real to Boolean signal with Hysteresis
Information
Block that transforms a Real
input signal into a Boolean
output signal:
- When the output was
false
and the input becomes greater than the parameteruHigh
, the output switches totrue
. - When the output was
true
and the input becomes less than the parameteruLow
, the output switches tofalse
.
The start value of the output is defined via parameter
pre_y_start
(= value of pre(y)
at initial time).
The default value of this parameter is false
.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | uLow | if y=true and u<uLow, switch to y=false | |
Real | uHigh | if y=false and u>uHigh, switch to y=true | |
Boolean | pre_y_start | false | Value of pre(y) at initial time |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Real input signal |
output BooleanOutput | y | Boolean output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.HysteresisWithHold
Hysteresis block that optionally allows to specify a hold time
Information
Model for a hysteresis block that optionally allows to specify a hold time. During the hold time, the output is not allowed to switch.
When the input u
becomes greater than uHigh
, the
output y
becomes true
and remains true
for at least trueHoldDuration
seconds, after which time it is allowed
to switch immediately.
When the input u
becomes less than uLow
, the output
y
becomes false
and remains false
for
at least falseHoldDuration
seconds, after which time it is allowed
to switch immediately.
This model for example could be used to disable an economizer, and not re-enable it for 10 minutes, and vice versa. Using hysteresis can avoid the distraction from the input noise.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | uLow | if y=true and u<uLow, switch to y=false | |
Real | uHigh | if y=false and u>uHigh, switch to y=true | |
Time | trueHoldDuration | true hold duration [s] | |
Time | falseHoldDuration | trueHoldDuration | false hold duration [s] |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Real input signal |
output BooleanOutput | y | Boolean output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.IntegratorWithReset
Output the integral of the input signal
Information
This model is similar to
Modelica.Blocks.Continuous.Integrator
except that it optionally allows to reset the output y
of the integrator.
The output of the integrator can be reset as follows:
-
If
reset = Types.Reset.Disabled
, which is the default, then the integrator is never reset. -
If
reset = Types.Reset.Parameter
, then a boolean input signaltrigger
is enabled. Whenever the value of this input changes fromfalse
totrue
, the integrator is reset by settingy
to the value of the parametery_reset
. -
If
reset = Types.Reset.Input
, then a boolean input signaltrigger
is enabled. Whenever the value of this input changes fromfalse
totrue
, the integrator is reset by settingy
to the value of the input signaly_reset_in
.
Implementation
To adjust the icon layer, the code of Modelica.Blocks.Continuous.Integrator has been copied into this model rather than extended.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | k | 1 | Integrator gain [1] |
Reset | reset | Buildings.Controls.OBC.CDL.T... | Type of integrator reset |
Initialization | |||
Init | initType | Buildings.Controls.OBC.CDL.T... | Type of initialization (1: no init, 2: initial state, 3: initial output) |
Real | y_start | 0 | Initial or guess value of output (= state) |
Integrator reset | |||
Real | y_reset | 0 | Value to which integrator is reset, used if reset = Types.Reset.Parameter |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
input RealInput | y_reset_in | Input signal for state to which integrator is reset, enabled if reset = Types.Reset.Input |
input BooleanInput | trigger | Resets the integrator output when trigger becomes true |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Less
Output y is true, if input u1 is less than input u2
Information
Block that outputs true
if the Real input u1
is less than the Real input u2
.
Otherwise the output is false
.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of first Real input signal |
input RealInput | u2 | Connector of second Real input signal |
output BooleanOutput | y | Connector of Boolean output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.LessEqual
Output y is true, if input u1 is less or equal than input u2
Information
Block that outputs true
if the Real input u1
is less than or equal to the Real input u2
.
Otherwise the output is false
.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of first Real input signal |
input RealInput | u2 | Connector of second Real input signal |
output BooleanOutput | y | Connector of Boolean output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.LessEqualThreshold
Output y is true, if input u is less or equal than threshold
Information
Block that outputs true
if the Real input is less than or equal to
the parameter threshold
.
Otherwise the output is false
.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | threshold | 0 | Comparison with respect to threshold |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output BooleanOutput | y | Connector of Boolean output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.LessThreshold
Output y is true, if input u is less than threshold
Information
Block that outputs true
if the Real input is less than
the parameter threshold
.
Otherwise the output is false
.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | threshold | 0 | Comparison with respect to threshold |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output BooleanOutput | y | Connector of Boolean output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.LimPID
P, PI, PD, and PID controller with limited output, anti-windup compensation and setpoint weighting
Information
PID controller in the standard form
y = k ( e(t) + 1 ⁄ Ti ∫ e(s) ds + Td de(t)⁄dt ),
where y is the control signal, e(t) = us - um is the control error, with us being the set point and um being the measured quantity, k is the gain, Ti is the time constant of the integral term and Td is the time constant of the derivative term.
Note that the units of k are the inverse of the units of the control error, while the units of Ti and Td are seconds.
For detailed treatment of integrator anti-windup, set-point weights and output limitation, see Modelica.Blocks.Continuous.LimPID. The model is similar to Modelica.Blocks.Continuous.LimPID, except for the following changes:
-
It can be configured to have a reverse action.
If the parameter
reverseAction=false
(the default), thenu_m < u_s
increases the controller output, otherwise the controller output is decreased. Thus,- for a heating coil with a two-way valve, set
reverseAction = false
, - for a cooling coils with a two-way valve, set
reverseAction = true
.
- for a heating coil with a two-way valve, set
-
It can be configured to enable an input port that allows resetting the controller output. The controller output can be reset as follows:
-
If
reset = CDL.Types.Reset.Disabled
, which is the default, then the controller output is never reset. -
If
reset = CDL.Types.Reset.Parameter
, then a boolean input signaltrigger
is enabled. Whenever the value of this input changes fromfalse
totrue
, the controller output is reset by settingy
to the value of the parametery_reset
. -
If
reset = CDL.Types.Reset.Input
, then a boolean input signaltrigger
is enabled. Whenever the value of this input changes fromfalse
totrue
, the controller output is reset by settingy
to the value of the input signaly_reset_in
.
Note that this controller implements an integrator anti-windup. Therefore, for most applications, keeping the default setting of
reset = CDL.Types.Reset.Disabled
is sufficient. Examples where it may be beneficial to reset the controller output are situations where the equipment control input should continuously increase as the equipment is switched on, such as as a light dimmer that may slowly increase the luminance, or a variable speed drive of a motor that should continuously increase the speed. -
If
-
The parameter
limitsAtInit
has been removed. - Some parameters assignments in the instances have been made final.
For recommendations regarding tuning of closed loop control, see Modelica.Blocks.Continuous.LimPID or the control literature.
Parameters
Type | Name | Default | Description |
---|---|---|---|
SimpleController | controllerType | Buildings.Controls.OBC.CDL.T... | Type of controller |
Real | k | 1 | Gain of controller [1] |
Time | Ti | 0.5 | Time constant of integrator block [s] |
Time | Td | 0.1 | Time constant of derivative block [s] |
Real | yMax | Upper limit of output | |
Real | yMin | -yMax | Lower limit of output |
Real | wp | 1 | Set-point weight for Proportional block (0..1) |
Real | wd | 0 | Set-point weight for Derivative block (0..1) |
Real | Ni | 0.9 | Ni*Ti is time constant of anti-windup compensation |
Real | Nd | 10 | The higher Nd, the more ideal the derivative block |
Boolean | reverseAction | false | Set to true for throttling the water flow rate through a cooling coil controller |
Initialization | |||
Init | initType | Buildings.Controls.OBC.CDL.T... | Type of initialization |
Real | xi_start | 0 | Initial or guess value value for integrator output (= integrator state) |
Real | xd_start | 0 | Initial or guess value for state of derivative block |
Real | y_start | 0 | Initial value of output |
Integrator reset | |||
Reset | reset | Buildings.Controls.OBC.CDL.T... | Type of controller output reset |
Real | y_reset | xi_start | Value to which the controller output is reset if the boolean trigger has a rising edge, used if reset == CDL.Types.Reset.Parameter |
Advanced | |||
Boolean | strict | true | = true, if strict limits with noEvent(..) |
Connectors
Type | Name | Description |
---|---|---|
input BooleanInput | trigger | Resets the controller output when trigger becomes true |
input RealInput | y_reset_in | Input signal for state to which integrator is reset, enabled if reset = CDL.Types.Reset.Input |
input RealInput | u_s | Connector of setpoint input signal |
input RealInput | u_m | Connector of measurement input signal |
output RealOutput | y | Connector of actuator output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Limiter
Limit the range of a signal
Information
Block that outputs y = min(uMax, max(uMin, u))
,
where
u
is an input
and
uMax
and uMin
are parameters.
If uMax < uMin
, an error occurs and no output is produced.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | uMax | Upper limit of input signal | |
Real | uMin | Lower limit of input signal |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Line
Output the value of the input x along a line specified by two points
Information
Block that outputs y = a + b u
,
where
u
is an input
and the coefficients a
and b
are determined so that the line intercepts the two input points
specified by the two points x1
and f1
,
and x2
and f2
.
The parameters limitBelow
and limitAbove
determine whether x1
and x2
are also used
to limit the input u
.
If the limits are used, then this block requires x1 < x2
.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Boolean | limitBelow | true | If true, limit input u to be no smaller than x1 |
Boolean | limitAbove | true | If true, limit input u to be no larger than x2 |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | x1 | Support point x1, with x1 < x2 |
input RealInput | f1 | Support point f(x1) |
input RealInput | x2 | Support point x2, with x2 > x1 |
input RealInput | f2 | Support point f(x2) |
input RealInput | u | Independent variable |
output RealOutput | y | f(x) along the line specified by (x1, f1) and (x2, f2) |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Log
Output the natural (base e) logarithm of the input (input > 0 required)
Information
Block that outputs y = log(u)
,
where
u
is an input and log()
is the
natural logarithm (base-e) function.
An error occurs if the input u
is
zero or negative.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Log10
Output the base 10 logarithm of the input (input > 0 required)
Information
Block that outputs y = log10(u)
,
where
u
is an input and log10()
is the
logarithm (base-10) function.
An error occurs if the input u
is
zero or negative.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.MatrixGain
Output the product of a gain matrix with the input signal vector
Information
This blocks computes output vector y as the product of the gain matrix K with the input signal vector u as y = K u. For example,
parameter Real K[:,:] = [0.12 2; 3 1.5];
results in
| y[1] | | 0.12 2.00 | | u[1] | | | = | | * | | | y[2] | | 3.00 1.50 | | u[2] |
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | K[:, :] | [1, 0; 0, 1] | Gain matrix which is multiplied with the input |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u[nin] | Connector of Real input signals |
output RealOutput | y[nout] | Connector of Real output signals |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.MatrixMax
Output vector of row- or column-wise maximum of the input matrix
Information
If rowMax = true
, this block outputs the row-wise maximum
of the input matrix u
,
otherwise it outputs the column-wise maximum of the input matrix u
.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Boolean | rowMax | true | If true, outputs row-wise maximum, otherwise column-wise |
Integer | nRow | nRow( ... | Number of rows in input matrix |
Integer | nCol | nCol( ... | Number of columns in input matrix |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u[nRow, nCol] | Connector of Real input signals |
output RealOutput | y[if rowMax then size(u, 1) else size(u, 2)] | Connector of Real output signals |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.MatrixMin
Output vector of row- or column-wise minimum values
Information
If rowMin = true
, this block outputs the row-wise minimum
of the input matrix u
,
otherwise it outputs the column-wise minimum of the input matrix u
.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Boolean | rowMin | true | If true, outputs row-wise minimum, otherwise column-wise |
Integer | nRow | nRow( ... | Number of rows in input matrix |
Integer | nCol | nCol( ... | Number of columns in input matrix |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u[nRow, nCol] | Connector of Real input signals |
output RealOutput | y[if rowMin then size(u, 1) else size(u, 2)] | Connector of Real output signals |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Max
Pass through the largest signal
Information
Block that outputs y = max(u1, u2)
,
where
u1
and u2
are inputs.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of Real input signal 1 |
input RealInput | u2 | Connector of Real input signal 2 |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Min
Pass through the smallest signal
Information
Block that outputs y = min(u1, u2)
,
where
u1
and u2
are inputs.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of Real input signal 1 |
input RealInput | u2 | Connector of Real input signal 2 |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Modulo
Output the remainder of first input divided by second input (~=0)
Information
Block that outputs y = mod(u1/u2)
,
where
u1
and u2
are inputs.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of Real input signal 1 |
input RealInput | u2 | Connector of Real input signal 2 |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.MovingMean
Block to output moving average
Information
This block outputs the mean value of its input signal as
1 t y = - ∫ u(s) ds δ t-δ
where δ is a parameter that determines the time window over which the input is averaged. For t < δ seconds, it outputs
1 t y = -------- ∫ u(s) ds t-t0+10-10 t0
where t0 is the initial time.
This block can for example be used to output the moving average of a noisy measurement signal.
See Buildings.Controls.OBC.CDL.Continuous.Validation.MovingMean and Buildings.Controls.OBC.CDL.Continuous.Validation.MovingMean_nonZeroStart for example.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Time | delta | delta( ... | Time horizon over which the input is averaged [s] |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.MultiMax
Output the maximum element of the input vector
Information
Outputs the maximum element of the input vector.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u[nin] | Connector of Real input signals |
output RealOutput | y | Connector of Real output signals |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.MultiMin
Output the minimum element of the input vector
Information
Outputs the minimum element of the input vector.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u[nin] | Connector of Real input signals |
output RealOutput | y | Connector of Real output signals |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.MultiSum
Sum of Reals, y = k[1]*u[1] + k[2]*u[2] + ... + k[n]*u[n]
Information
Block that outputs
y = ∑i=1n ki ui,
where k is a parameter with n elements and u is an input of the same length. The dimension of u can be enlarged by drawing an additional connection line. The connection is automatically connected to this new free index.
If no connection to the input connector u is present, the output is y=0.
See Buildings.Controls.OBC.CDL.Continuous.Validation.MultiSum for an example.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | k[nin] | fill(1, nin) | Input gains |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u[nin] | Connector of Real input signals |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.NumberOfRequests
Outputs the number of signals that are above/below a certain threshold
Information
Block that outputs the number of inputs that exceed a threshold.
The parameter kind
is used to determine the kind of the
inequality. The table below shows the allowed settings.
Value of parameter kind |
Output signal incremented by 1 for each i ∈ {1, ..., nin} if |
---|---|
0 | u[i] > threShold |
1 | u[i] ≥ threShold |
2 | u[i] ≤ threShold |
3 | u[i] < threShold |
This model may be used to check how many rooms exceed a temperature threshold.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Integer | nin | Number of inputs | |
Real | threShold | 0 | Threshold |
Integer | kind | Set to 0 for u>threShold, to 1 for >=, to 2 for <= or to 3 for < |
Connectors
Type | Name | Description |
---|---|---|
output IntegerOutput | y | Number of input signals that violate the threshold |
input RealInput | u[nin] | Input signals |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Product
Output product of the two inputs
Information
Block that outputs y = u1 * u2
,
where
u1
and u2
are inputs.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u1 | Connector of Real input signal 1 |
input RealInput | u2 | Connector of Real input signal 2 |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Round
Round real number to given digits
Information
Block that outputs the input after rounding it to n
digits.
For example,
-
set
n = 0
to round to the nearest integer, -
set
n = 1
to round to the next decimal point, and -
set
n = -1
to round to the next multiple of ten.
Hence, the block outputs
y = floor(u*(10^n) + 0.5)/(10^n) for u > 0, y = ceil(u*(10^n) - 0.5)/(10^n) for u < 0.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Integer | n | Number of digits being round to |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Sin
Output the sine of the input
Information
Block that outputs y = sin(u)
,
where
u
is an input.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.SlewRateLimiter
Limit the increase or decrease rate of input
Information
The block limits the rate of change of the input by a ramp.
This block computes a threshold for the rate of change between
input u
and output y
as
thr = (u-y)/Td
, where Td > 0
is parameter.
The output y
is computed as follows:
If thr < fallingSlewRate
, then dy/dt = fallingSlewRate
,
if thr > raisingSlewRate
, then dy/dt = raisingSlewRate
,
otherwise, dy/dt = thr
.
Implementation
For the block to work with arbitrary inputs and in order to produce a differential output,
the input is numerically differentiated with derivative time constant Td
.
Smaller time constant Td
means nearer ideal derivative.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | raisingSlewRate | raisingSlewRate( min = Con... | Speed with which to increase the output [1/s] |
Real | fallingSlewRate | -raisingSlewRate | Speed with which to decrease the output [1/s] |
Time | Td | raisingSlewRate*10 | Derivative time constant [s] |
Boolean | enable | true | Set to false to disable rate limiter |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Sort
Sort elements of input vector in ascending or descending order
Information
Block that sorts the elements of the input signal u.
If the parameter ascending = true
, then the output signal satisfies
yi <= yi+1 for all i ∈ {1, ..., n-1}.
Otherwise, it satisfies
yi >= yi+1 for all i ∈ {1, ..., n-1}.
This block may for example be used in a variable air volume flow controller to access the position of the dampers that are most open.
Parameters
Type | Name | Default | Description |
---|---|---|---|
Boolean | ascending | true | = true if ascending order, otherwise descending order |
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u[nin] | Connector of Real input signals |
output RealOutput | y[nin] | Connector of Real output signals |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Sqrt
Output the square root of the input (input >= 0 required)
Information
Block that outputs square root of the input y = sqrt(u)
,
where u
is an input. All elements of the input vector shall be non-negative.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |
Modelica definition
Buildings.Controls.OBC.CDL.Continuous.Tan
Output the tangent of the input
Information
Block that outputs y = tan(u)
,
where
u
is an input.
Connectors
Type | Name | Description |
---|---|---|
input RealInput | u | Connector of Real input signal |
output RealOutput | y | Connector of Real output signal |