Buildings.Fluid.Actuators.BaseClasses.Examples
Collection of models that illustrate model use and test models
Information
This package contains examples for the use of models that can be found in Buildings.Fluid.Actuators.BaseClasses.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
Package Content
Name | Description |
---|---|
EqualPercentageDerivativeCheck |
Buildings.Fluid.Actuators.BaseClasses.Examples.EqualPercentageDerivativeCheck
Information
This example checks whether the function derivative is implemented correctly. If the derivative implementation is not correct, the model will stop with an assert statement.
Extends from Modelica.Icons.Example (Icon for runnable examples).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Real | R | 50 | Rangeability |
Real | delta | 0.01 | Value where transition occurs |
Real | l | 0.001 | Leakage |
Modelica definition
model EqualPercentageDerivativeCheck
extends Modelica.Icons.Example;
parameter Real R = 50 "Rangeability";
parameter Real delta = 0.01 "Value where transition occurs";
parameter Real l = 0.001 "Leakage";
Real x;
Real y;
initial equation
y=x;
equation
x=Buildings.Fluid.Actuators.BaseClasses.equalPercentage(time, R, l, delta);
der(y)=der(x);
assert(abs(x-y) < 1E-2, "Model has an error");