Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.Examples.BaseClasses

This package contains base classes inherited by the examples

Information

This package contains base classes used by the examples that are part of the package Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.Examples.

Extends from Modelica.Icons.BasesPackage (Icon for packages containing base classes).

Package Content

Name Description
Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.Examples.BaseClasses.TransformerExample TransformerExample This example represents the basic test for a transformer model

Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.Examples.BaseClasses.TransformerExample Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.Examples.BaseClasses.TransformerExample

This example represents the basic test for a transformer model

Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.Examples.BaseClasses.TransformerExample

Information

This model is the base classes used by the examples that are part of the package Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.Examples.

The model has a voltage source, a transformer and a load. The transformer model is replaceable so that different types of transformers can easily be tested.

Extends from Modelica.Icons.Example (Icon for runnable examples).

Parameters

TypeNameDefaultDescription
VoltageV_primary12470RMS Voltage on the primary side of the transformer [V]
VoltageV_secondary4160RMS Voltage on the secondary side of the transformer [V]
PartialConvertertraredeclare Buildings.Electric...Transformer model
GeneralizedProbeprobe_2redeclare Sensors.BaseClasse...Probe that measures the voltage at the secondary side

Modelica definition

model TransformerExample "This example represents the basic test for a transformer model" extends Modelica.Icons.Example; parameter Modelica.SIunits.Voltage V_primary=12470 "RMS Voltage on the primary side of the transformer"; parameter Modelica.SIunits.Voltage V_secondary=4160 "RMS Voltage on the secondary side of the transformer"; Sources.FixedVoltage sou(f=60, V=V_primary) "Voltage source"; replaceable Buildings.Electrical.AC.ThreePhasesUnbalanced.Conversion.BaseClasses.PartialConverter tra "Transformer model"; Loads.Resistive load( loadConn=Buildings.Electrical.Types.LoadConnection.wye_to_wyeg, P_nominal=-1800e3, V_nominal=V_secondary, linearized=true) "Load model"; Sensors.ProbeWye probe_Y_1(perUnit=false, V_nominal=V_primary) "Probe that measures the voltage in Y configuration, primary side"; Sensors.ProbeDelta probe_D_1(perUnit=false, V_nominal=V_primary) "Probe that measures the voltage in D configuration, primary side"; replaceable Sensors.BaseClasses.GeneralizedProbe probe_2 constrainedby Sensors.BaseClasses.GeneralizedProbe(perUnit=false, V_nominal=V_secondary) "Probe that measures the voltage at the secondary side"; equation connect(sou.terminal, tra.terminal_n); connect(probe_Y_1.term, tra.terminal_n); connect(probe_D_1.term, tra.terminal_n); connect(tra.terminal_p, load.terminal); end TransformerExample;