Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating
Records for scroll water to water heat pumps in heating mode
Information
Package with data for heating performance of water to water heat pump models Buildings.Fluid.HeatPumps.ScrollWaterToWater with scroll compressor.
Extends from Modelica.Icons.MaterialPropertiesPackage (Icon for package containing property classes).
Package Content
Name | Description |
---|---|
Carrier_50PSW122_38kW_4_29COP_R410A | Calibrated parameters for Carrier 50PSW122 |
Carrier_50PSW180_52kW_4_50COP_R410A | Calibrated parameters for Carrier 50PSW180 |
Carrier_50PSW210_70kW_4_40COP_R410A | Calibrated parameters for Carrier 50PSW210 |
Carrier_50PSW240_93kW_4_40COP_R410A | Calibrated parameters for Carrier 50PSW240 |
Carrier_50PSW360_105kW_4_50COP_R410A | Calibrated parameters for Carrier 50PSW360 |
Carrier_50PSW420_140kW_4_40COP_R410A | Calibrated parameters for Carrier 50PSW420 |
ClimateMaster_TMW036_12kW_4_90COP_R410A | Calibrated parameters for ClimateMaster TMW036 |
ClimateMaster_TMW060_21kW_4_60COP_R410A | Calibrated parameters for ClimateMaster TMW060 |
ClimateMaster_TMW120_42kW_4_50COP_R410A | Calibrated parameters for ClimateMaster TMW120 |
ClimateMaster_TMW170_48kW_4_30COP_R410A | Calibrated parameters for ClimateMaster TMW170 |
ClimateMaster_TMW340_98kW_4_40COP_R410A | Calibrated parameters for ClimateMaster TMW340 |
Daikin_WRA036_13kW_4_50COP_R410A | Calibrated parameters for Daikin WRA036 |
Daikin_WRA048_16kW_4_60COP_R410A | Calibrated parameters for Daikin WRA048 |
Daikin_WRA060_19kW_4_50COP_R410A | Calibrated parameters for Daikin WRA060 |
Daikin_WRA072_24kW_4_30COP_R410A | Calibrated parameters for Daikin WRA072 |
Daikin_WRA120_37kW_4_40COP_R410A | Calibrated parameters for Daikin WRA120 |
Daikin_WRA150_49kW_4_70COP_R410A | Calibrated parameters for Daikin WRA150 |
Daikin_WRA180_63kW_4_50COP_R410A | Calibrated parameters for Daikin WRA180 |
Daikin_WRA240_79kW_4_40COP_R410A | Calibrated parameters for Daikin WRA240 |
Daikin_WRA300_93kW_4_60COP_R410A | Calibrated parameters for Daikin WRA300 |
Daikin_WRA360_116kW_4_60COP_R410A | Calibrated parameters for Daikin WRA360 |
Daikin_WRA420_137kW_4_50COP_R410A | Calibrated parameters for Daikin WRA420 |
Trane_EXW060_21kW_4_30COP_R410A | Calibrated parameters for Trane EXW060 |
Trane_EXW120_40kW_3_90COP_R410A | Calibrated parameters for Trane EXW120 |
Trane_EXW240_76kW_4_10COP_R410A | Calibrated parameters for Trane EXW240 |
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Carrier_50PSW122_38kW_4_29COP_R410A
Calibrated parameters for Carrier 50PSW122
Information
Calibrated parameters for Carrier 50PSW122.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 1.0 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 1881.76772552 | Constant part of the compressor power losses [W] |
Real | volRat | 1.81466473546 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00670253502001 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00764809592483 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 2.96952832147e-16 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 7132.41759701 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 9021.05488178 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Carrier_50PSW180_52kW_4_50COP_R410A
Calibrated parameters for Carrier 50PSW180
Information
Calibrated parameters for Carrier 50PSW180.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.937361296479 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 1811.46067781 | Constant part of the compressor power losses [W] |
Real | volRat | 2.17984156405 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00696068884655 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00108868592572 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 4.04195833004 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 7982.84714185 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 8707.82060032 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Carrier_50PSW210_70kW_4_40COP_R410A
Calibrated parameters for Carrier 50PSW210
Information
Calibrated parameters for Carrier 50PSW210.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.883599976056 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 2744.55441047 | Constant part of the compressor power losses [W] |
Real | volRat | 2.28439860422 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00864092882056 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00423622888067 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 7.01376392106e-16 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 14718.9494319 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 14926.2266407 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Carrier_50PSW240_93kW_4_40COP_R410A
Calibrated parameters for Carrier 50PSW240
Information
Calibrated parameters for Carrier 50PSW240.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 1.0 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 3501.16553626 | Constant part of the compressor power losses [W] |
Real | volRat | 2.06220893804 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.0130449462937 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.0115795099184 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 2.99452373707e-20 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 11572.8594812 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 15632.3350979 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Carrier_50PSW360_105kW_4_50COP_R410A
Calibrated parameters for Carrier 50PSW360
Information
Calibrated parameters for Carrier 50PSW360.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.949322443561 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 3584.93101188 | Constant part of the compressor power losses [W] |
Real | volRat | 2.16843356806 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.0140160866901 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00223124798723 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 3.97822933689 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 15988.0119559 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 16612.2868599 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Carrier_50PSW420_140kW_4_40COP_R410A
Calibrated parameters for Carrier 50PSW420
Information
Calibrated parameters for Carrier 50PSW420.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 1.0 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 5208.69616148 | Constant part of the compressor power losses [W] |
Real | volRat | 2.23739862891 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.0192598232371 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.0156269077066 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 9.97163386698e-17 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 20395.4876127 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 22875.6244158 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.ClimateMaster_TMW036_12kW_4_90COP_R410A
Calibrated parameters for ClimateMaster TMW036
Information
Calibrated parameters for ClimateMaster TMW036.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 1.0 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 334.350812253 | Constant part of the compressor power losses [W] |
Real | volRat | 2.02993657028 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.0017713046171 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.0001 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 4.68810579482e-16 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 925.546637632 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 2434.90888536 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.ClimateMaster_TMW060_21kW_4_60COP_R410A
Calibrated parameters for ClimateMaster TMW060
Information
Calibrated parameters for ClimateMaster TMW060.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 1.0 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 417.744706167 | Constant part of the compressor power losses [W] |
Real | volRat | 2.3017065409 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00343193389885 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.0001 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 9.02301826552e-16 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 1012.57723222 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 6976.43602782 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.ClimateMaster_TMW120_42kW_4_50COP_R410A
Calibrated parameters for ClimateMaster TMW120
Information
Calibrated parameters for ClimateMaster TMW120.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 1.0 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 958.859267653 | Constant part of the compressor power losses [W] |
Real | volRat | 2.2476274626 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00665394781546 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.0001 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 1.25716725318e-15 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 2121.46076035 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 11851.7167307 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.ClimateMaster_TMW170_48kW_4_30COP_R410A
Calibrated parameters for ClimateMaster TMW170
Information
Calibrated parameters for ClimateMaster TMW170.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 1.0 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 3217.60778902 | Constant part of the compressor power losses [W] |
Real | volRat | 2.14272406967 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00593752063272 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.0001 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 4.12544294557 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 6702.69056458 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 7127.67902377 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.ClimateMaster_TMW340_98kW_4_40COP_R410A
Calibrated parameters for ClimateMaster TMW340
Information
Calibrated parameters for ClimateMaster TMW340.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 1.0 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 6407.64092672 | Constant part of the compressor power losses [W] |
Real | volRat | 2.1436051259 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.0118607090337 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.0001 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 4.01978505385 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 13705.1289797 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 14154.9112764 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Daikin_WRA036_13kW_4_50COP_R410A
Calibrated parameters for Daikin WRA036
Information
Calibrated parameters for Daikin WRA036.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.75022416333 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 454.268261392 | Constant part of the compressor power losses [W] |
Real | volRat | 2.18937967922 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00136995091062 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00204441726371 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 10.0 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 14984.5402787 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 2854.56883514 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Daikin_WRA048_16kW_4_60COP_R410A
Calibrated parameters for Daikin WRA048
Information
Calibrated parameters for Daikin WRA048.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.788717592763 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 698.088177298 | Constant part of the compressor power losses [W] |
Real | volRat | 1.98348644579 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00165211643646 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00243670163031 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 2.36774358188 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 17688.743889 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 2860.44257631 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Daikin_WRA060_19kW_4_50COP_R410A
Calibrated parameters for Daikin WRA060
Information
Calibrated parameters for Daikin WRA060.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.818648566096 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 834.025033052 | Constant part of the compressor power losses [W] |
Real | volRat | 2.02058512825 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00203948729471 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00265331062627 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 10.0 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 22163.5117527 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 3132.54953048 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Daikin_WRA072_24kW_4_30COP_R410A
Calibrated parameters for Daikin WRA072
Information
Calibrated parameters for Daikin WRA072.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.854244522432 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 1299.86121735 | Constant part of the compressor power losses [W] |
Real | volRat | 1.97046126937 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00251615132207 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00317911390448 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 0.0 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 29257.8652993 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 3112.7917639 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Daikin_WRA120_37kW_4_40COP_R410A
Calibrated parameters for Daikin WRA120
Information
Calibrated parameters for Daikin WRA120.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.802185040279 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 1669.72414504 | Constant part of the compressor power losses [W] |
Real | volRat | 2.03662365096 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00402163945373 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00568133095128 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 10.0 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 43952.8437636 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 6395.36493022 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Daikin_WRA150_49kW_4_70COP_R410A
Calibrated parameters for Daikin WRA150
Information
Calibrated parameters for Daikin WRA150.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.727713452257 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 1973.27851471 | Constant part of the compressor power losses [W] |
Real | volRat | 2.11953593283 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00458293691848 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00521346182908 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 2.82899331265e-17 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 52300.8714734 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 10364.1606457 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Daikin_WRA180_63kW_4_50COP_R410A
Calibrated parameters for Daikin WRA180
Information
Calibrated parameters for Daikin WRA180.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.722176661834 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 3128.08507812 | Constant part of the compressor power losses [W] |
Real | volRat | 2.25650476224 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00640722987639 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00303673424194 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 3.10253510583e-16 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 83881.3683749 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 11553.9351864 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Daikin_WRA240_79kW_4_40COP_R410A
Calibrated parameters for Daikin WRA240
Information
Calibrated parameters for Daikin WRA240.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.727791339852 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 4018.51603651 | Constant part of the compressor power losses [W] |
Real | volRat | 2.17536546687 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.0081233732836 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.0070428590136 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 2.84985105778e-23 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 94620.7400986 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 12615.4293459 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Daikin_WRA300_93kW_4_60COP_R410A
Calibrated parameters for Daikin WRA300
Information
Calibrated parameters for Daikin WRA300.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.735457127351 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 5104.2326681 | Constant part of the compressor power losses [W] |
Real | volRat | 2.14540444135 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00946627483153 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00983531785764 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 5.92067681695e-16 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 114049.474787 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 16784.7393136 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Daikin_WRA360_116kW_4_60COP_R410A
Calibrated parameters for Daikin WRA360
Information
Calibrated parameters for Daikin WRA360.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.737581999584 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 4731.51935299 | Constant part of the compressor power losses [W] |
Real | volRat | 2.36231114404 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.0129762607513 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.0106609843642 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 10.0 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 196974.891726 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 25362.0976534 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Daikin_WRA420_137kW_4_50COP_R410A
Calibrated parameters for Daikin WRA420
Information
Calibrated parameters for Daikin WRA420.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.749270140609 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 6263.77526408 | Constant part of the compressor power losses [W] |
Real | volRat | 2.31768014295 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.0151967313394 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.0108643581925 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 10.0 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 297902.470363 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 24801.5921552 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Trane_EXW060_21kW_4_30COP_R410A
Calibrated parameters for Trane EXW060
Information
Calibrated parameters for Trane EXW060.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.894909766227 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 677.578359509 | Constant part of the compressor power losses [W] |
Real | volRat | 1.97339400782 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00299097356737 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00368947815377 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 10.0 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 41007.3610647 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 3260.47025405 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Trane_EXW120_40kW_3_90COP_R410A
Calibrated parameters for Trane EXW120
Information
Calibrated parameters for Trane EXW120.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 1.0 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 2167.94596726 | Constant part of the compressor power losses [W] |
Real | volRat | 1.7751510289 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00568762510737 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00493966413666 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 10.0 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 38367.2250194 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 4233.2477479 | Thermal conductance of condenser between water and refrigerant [W/K] |
Modelica definition
Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Heating.Trane_EXW240_76kW_4_10COP_R410A
Calibrated parameters for Trane EXW240
Information
Calibrated parameters for Trane EXW240.
Extends from Buildings.Fluid.HeatPumps.Data.ScrollWaterToWater.Generic (Record for scroll water to water heat pump).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Compressor | |||
Efficiency | etaEle | 0.771299720173 | Electro-mechanical efficiency of the compressor [1] |
Power | PLos | 3034.42959083 | Constant part of the compressor power losses [W] |
Real | volRat | 2.15191083807 | Built-in volume ratio [1] |
VolumeFlowRate | V_flow_nominal | 0.00932406376397 | Refrigerant volume flow rate at suction [m3/s] |
MassFlowRate | leaCoe | 0.00855730520196 | Leakage coefficient [kg/s] |
Evaporator | |||
TemperatureDifference | dTSup | 2.21163986317 | Superheating at compressor suction [K] |
ThermalConductance | UAEva | 97189.7265209 | Thermal conductance of evaporator between water and refrigerant [W/K] |
Condenser | |||
ThermalConductance | UACon | 14814.6977543 | Thermal conductance of condenser between water and refrigerant [W/K] |