Buildings.Fluid.HeatExchangers.CoolingTowers.Examples
Collection of models that illustrate model use and test models
Information
This package contains examples for the use of models that can be found in Buildings.Fluid.HeatExchangers.CoolingTowers.
Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).
Package Content
Name | Description |
---|---|
FixedApproachDryBulb | Test model for cooling tower with fixed approach temperature using the dry-bulb temperature |
FixedApproachWetBulb | Test model for cooling tower with fixed approach temperature using the wet-bulb temperature |
YorkCalc | Test model for cooling tower using the York performance correlation |
BaseClasses | Package with base classes for Buildings.Fluid.HeatExchangers.CoolingTowers.Examples |
Buildings.Fluid.HeatExchangers.CoolingTowers.Examples.FixedApproachDryBulb
Test model for cooling tower with fixed approach temperature using the dry-bulb temperature
Information
This example illustrates the use of the cooling tower model Buildings.Fluid.HeatExchangers.CoolingTowers.FixedApproach, using the outdoor dry-bulb temperature as the potential for heat transfer. Heat is injected into the volumevol
. An on/off controller
switches the cooling loop water pump on or off based on the temperature of
this volume.
The cooling tower outlet temperature has a fixed approach temperature to the
outdoor dry-bulb temperature.
Extends from Modelica.Icons.Example (Icon for runnable examples), BaseClasses.PartialStaticTwoPortCoolingTower (Base class for test models of cooling towers).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Nominal condition | |||
MassFlowRate | mWat_flow_nominal | 0.5 | Design water flow rate [kg/s] |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus |
Modelica definition
Buildings.Fluid.HeatExchangers.CoolingTowers.Examples.FixedApproachWetBulb
Test model for cooling tower with fixed approach temperature using the wet-bulb temperature
Information
This example illustrates the use of the cooling tower model Buildings.Fluid.HeatExchangers.CoolingTowers.FixedApproach, using the outdoor wet-bulb temperature as the potential for heat transfer. Heat is injected into the volumevol
. An on/off controller
switches the cooling loop water pump on or off based on the temperature of
this volume.
The cooling tower outlet temperature has a fixed approach temperature to the
outdoor wet-bulb temperature.
Extends from Modelica.Icons.Example (Icon for runnable examples), BaseClasses.PartialStaticTwoPortCoolingTowerWetBulb (Partial test model for cooling tower with wet bulb temperature as potential for heat transfer).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Nominal condition | |||
MassFlowRate | mWat_flow_nominal | 0.5 | Design water flow rate [kg/s] |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus |
Modelica definition
Buildings.Fluid.HeatExchangers.CoolingTowers.Examples.YorkCalc
Test model for cooling tower using the York performance correlation
Information
This example illustrates the use of the cooling tower model Buildings.Fluid.HeatExchangers.CoolingTowers.YorkCalc. Heat is injected into the volumevol
. An on/off controller
switches the cooling loop water pump on or off based on the temperature of
this volume.
The cooling tower outlet temperature is controlled to track a fixed temperature.
Extends from Modelica.Icons.Example (Icon for runnable examples), BaseClasses.PartialStaticTwoPortCoolingTowerWetBulb (Partial test model for cooling tower with wet bulb temperature as potential for heat transfer).
Parameters
Type | Name | Default | Description |
---|---|---|---|
Nominal condition | |||
MassFlowRate | mWat_flow_nominal | 0.5 | Design water flow rate [kg/s] |
Connectors
Type | Name | Description |
---|---|---|
Bus | weaBus |