Buildings.DHC.ETS.Combined.Validation

Collection of validation models

Information

This package contains validation models for the classes in Buildings.DHC.ETS.Combined.

Extends from Modelica.Icons.ExamplesPackage (Icon for packages containing runnable examples).

Package Content

Name Description
Buildings.DHC.ETS.Combined.Validation.HeatRecoveryHeatPump HeatRecoveryHeatPump Validation of the ETS model with heat recovery heat pump
Buildings.DHC.ETS.Combined.Validation.HeatRecoveryHeatPumpWSE HeatRecoveryHeatPumpWSE Validation of the ETS model with heat recovery chiller and waterside economizer

Buildings.DHC.ETS.Combined.Validation.HeatRecoveryHeatPump Buildings.DHC.ETS.Combined.Validation.HeatRecoveryHeatPump

Validation of the ETS model with heat recovery heat pump

Buildings.DHC.ETS.Combined.Validation.HeatRecoveryHeatPump

Information

This model validates Buildings.DHC.ETS.Combined.HeatRecoveryHeatPump in a system configuration with a simple district loop, building heating and cooling load.

Extends from Buildings.DHC.ETS.Combined.Examples.HeatRecoveryHeatPump (Example of the ETS model with heat recovery heat pump).

Parameters

TypeNameDefaultDescription
StringfilNam"modelica://Buildings/Resour...File name with thermal loads as time series
MassFlowRatemHeaWat_flow_nominal0.9*datHeaPum.mCon_flow_nomi...Nominal heating water mass flow rate [kg/s]
MassFlowRatemChiWat_flow_nominal0.9*datHeaPum.mEva_flow_nomi...Nominal chilled water mass flow rate [kg/s]
WAMAK_220kWdatHeaPum Heat recovery heat pump parameters
GenericDomesticHotWaterWithHeatExchangerdatDhw Performance data of the domestic hot water component
Design parameter
HeatFlowRateQCoo_flow_nominalBuildings.DHC.Loads.BaseClas...Design cooling heat flow rate (<=0) [W]
HeatFlowRateQHea_flow_nominalBuildings.DHC.Loads.BaseClas...Design heat heating flow rate (>=0) [W]
Chilled water
ThermodynamicTemperatureTChiWatSup_nominal7 + 273.15Nominal chilled water supply temperature [K]
TemperatureDifferencedTChiWat_nominal5Nominal chilled water temperature difference [K]
Heating hot water
ThermodynamicTemperatureTHeaWatSup_nominal45 + 273.15Nominal heating hot water supply temperature [K]
TemperatureDifferencedTHeaWat_nominal10Nominal heating hot water temperature difference [K]

Modelica definition

model HeatRecoveryHeatPump "Validation of the ETS model with heat recovery heat pump" extends Buildings.DHC.ETS.Combined.Examples.HeatRecoveryHeatPump( TDisWatSup( tableName="tab1", table=[ 0,11; 49,11; 50,20; 100,20], extrapolation=Modelica.Blocks.Types.Extrapolation.Periodic, timeScale=3600, offset={273.15}, columns={2}, smoothness=Modelica.Blocks.Types.Smoothness.MonotoneContinuousDerivative1), loa( tableOnFile=false, table=[ 0,0,0; 1,0,0; 2,0,1; 3,0,1; 4,0,0.5; 5,0,0.5; 6,0,0.1; 7,0,0.1; 8,0,0; 9,0,0; 10,0,0; 11,0,0; 12,0,0; 13,1,0; 14,1,0; 15,0.5,0; 16,0.5,0; 17,0.1,0; 18,0.1,0; 19,0,0; 20,0,0; 21,0,0; 22,0,0; 23,0,0; 24,0,1; 25,1,1; 26,1,0.5; 27,0.5,0.5; 28,0.5,0.1; 29,0.1,0.1; 30,0.1,0; 31,0,0; 32,0,0; 33,0,0; 34,0,0; 35,0,1; 36,0.1,1; 37,0.1,0.5; 38,0.5,0.5; 39,0.5,0.1; 40,1,0.1; 41,1,0; 42,0,0; 43,0,0; 44,0,0; 45,0,0; 46,0,0.3; 47,0.1,0.3; 48,0.1,0.1; 49,0.3,0.1; 50,0.3,0.1; 51,0.1,0.1; 52,0.1,0; 53,0,0; 54,0,0; 55,0,0; 56,0,0; 57,1,1; 58,1,1; 59,0.5,0.5; 60,0.5,0.5; 61,0.1,0.1; 62,0.1,0.1; 63,0,0; 64,0,0; 65,0,0; 66,0,0; 67,1,0; 68,1,1; 69,0.5,1; 70,0.5,0.5; 71,0.1,0.5; 72,0.1,0.1; 73,0,0.1; 74,0,0.1; 75,0,0; 76,0,0; 77,0,0; 78,0,0; 79,0.1,0; 80,0.1,1; 81,0.5,1; 82,0.5,0.5; 83,1,0.5; 84,1,0.1; 85,0,0.1; 86,0,0.1; 87,0,0; 88,0,0; 89,0,0; 90,0,0; 91,0.1,0; 92,0.1,0.3; 93,0.3,0.3; 94,0.3,0.1; 95,0.1,0.1; 96,0.1,0.1; 97,0,0.1; 98,0,0; 99,0,0], timeScale=3600, offset={0,0}, columns={2,3}), loaNorHea(k=1), loaNorCoo(k=1)); end HeatRecoveryHeatPump;

Buildings.DHC.ETS.Combined.Validation.HeatRecoveryHeatPumpWSE Buildings.DHC.ETS.Combined.Validation.HeatRecoveryHeatPumpWSE

Validation of the ETS model with heat recovery chiller and waterside economizer

Buildings.DHC.ETS.Combined.Validation.HeatRecoveryHeatPumpWSE

Information

This model validates Buildings.DHC.ETS.Combined.HeatRecoveryHeatPump in a system configuration with no geothermal borefield.

Extends from Buildings.DHC.ETS.Combined.Validation.HeatRecoveryHeatPump (Validation of the ETS model with heat recovery heat pump).

Parameters

TypeNameDefaultDescription
StringfilNam"modelica://Buildings/Resour...File name with thermal loads as time series
MassFlowRatemHeaWat_flow_nominal0.9*datHeaPum.mCon_flow_nomi...Nominal heating water mass flow rate [kg/s]
MassFlowRatemChiWat_flow_nominal0.9*datHeaPum.mEva_flow_nomi...Nominal chilled water mass flow rate [kg/s]
WAMAK_220kWdatHeaPum Heat recovery heat pump parameters
GenericDomesticHotWaterWithHeatExchangerdatDhw Performance data of the domestic hot water component
Design parameter
HeatFlowRateQCoo_flow_nominalBuildings.DHC.Loads.BaseClas...Design cooling heat flow rate (<=0) [W]
HeatFlowRateQHea_flow_nominalBuildings.DHC.Loads.BaseClas...Design heat heating flow rate (>=0) [W]
Chilled water
ThermodynamicTemperatureTChiWatSup_nominal7 + 273.15Nominal chilled water supply temperature [K]
TemperatureDifferencedTChiWat_nominal5Nominal chilled water temperature difference [K]
Heating hot water
ThermodynamicTemperatureTHeaWatSup_nominal45 + 273.15Nominal heating hot water supply temperature [K]
TemperatureDifferencedTHeaWat_nominal10Nominal heating hot water temperature difference [K]

Modelica definition

model HeatRecoveryHeatPumpWSE "Validation of the ETS model with heat recovery chiller and waterside economizer" extends Buildings.DHC.ETS.Combined.Validation.HeatRecoveryHeatPump( ets(have_WSE=true), TChiWatSupSet(k=12 + 273.15), TDisWatSup( tableName="tab1", table=[ 0,11; 49,11; 50,20; 100,20], extrapolation=Modelica.Blocks.Types.Extrapolation.Periodic, timeScale=3600, offset={273.15}, columns={2}, smoothness=Modelica.Blocks.Types.Smoothness.MonotoneContinuousDerivative1)); end HeatRecoveryHeatPumpWSE;